Dometic VARC 48 Скачать руководство пользователя страница 9

 

 

Fault 

Provides a Normally Open (NO) contact point. Any fault condition will close the NO contact. This output can be used to power a 
light, relay, or interface to a ship

’s monitoring system. The output on this terminal will be 230 VAC. 

 
 
 

SYSTEM OVERVIEW 

System  Power-up 

 

S

oftware  Revision 

 
Upon applying power to the system, the display will indicate the software revision number or display it on the main status screen. 

 

VARC is enabled and waiting for user selection. 
 

MODBUS 

 

The VARC comes with a 3 wire Modbus connection as part of the electrical box. This connection is used for multistage configuration, 
touchscreen and networking to a boat management system. 

 

Startup 

 

The VARC Chiller controller can be operated as a single or a multistage chiller plant. During initial setup, the system will be configured for 
the number of stages and the available options. System is set for Return water control but can be modified for Supply water control if 
needed. The user has the option to select between metric values being displayed or Imperial values being displayed during operation of 
the system. 

 

In a multistage configuration the user will be able to change the different operating startup modes. The two startup modes are: normal 
stage startup or accelerated mode startup. The normal startup is when the system has a time delay between the staging up of the various 
stages. Stage one will be initiated and will start its operation once the PID determines that more capacity is required the second stage will 
be initiated. While in operation and the system has maintained the chilled water loop and the PID has determined that that no additional 
stage is required or has met capacity demand it will reduce the speed of the compressors. The compressors will operate at minimal 
speed to maintain the chilled water loop. If the speed of the compressor still exceeds the demand the stage with the most run hours will 
be turned off. 

 

The VARC chiller allows the user to select between three operating modes. Econo mode, normal mode and boost mode. These three 
modes allow the user to have predefined current limits. The economy mode is the energy efficient mode where the compressor is limited 
to default five amp configuration. The normal mode is the typical mode of operation where the current limit is set to 9 Amps for both heat 
and cool modes. The boost mode allows the system to run at maximum capacity without current limitation other than the full limits of the 
frequency drives which is 12 amps. 

 

Chilled water setpoint will be entered for Cool and Heat mode.  
Once enabled, CW and SW pumps will be turned on for operation. 

 

 

Operational Checks 

 

 

Once the VARC is enabled the system will conduct pre-startup checks. The VARC program will check all CW flow switches for faults. The 
VARC will also check HP and LP (optional) switches for faults. 
Individual stage faults will only disable that stage. 

 

Compressor Startup 

 

The VARC utilizes a BLDC compressor that is capable of operating at a very high frequency. This requires that the compressor have a 
ramped startup to establish proper lubrication as to not damage the compressor. This startup has a ramp time and a minimal speed 
operation that will last for 100 seconds to allow the compressor to properly warm-up before operating at maximum speed. 
 
The compressor minimum on time is 100 seconds and minimum off time is also 100 seconds with a minimum time between starts of 120 
seconds. These default parameters allow the compressor to operate in a safe mode that will not damage the compressor.

      

Содержание VARC 48

Страница 1: ...ieval system or transmitted in any form or by any means electronic mechanical photocopying recording or otherwise without prior written consent by Dometic Corporation Every precaution has been taken i...

Страница 2: ...erational Checks 7 Compressor Startup 7 SETPOINTS 8 Cooling 8 Heating 8 Compressor Staging Time 8 Run Mode Cooling 8 Run Mode Reverse Cycle Heating 8 Run Mode Electric Heating optional heater barrel 8...

Страница 3: ...s in current on the generator The VARC48 also uses the advanced technology of an Electronic Expansion Valve EEV This provides more precise control of superheat across a broad range of conditions with...

Страница 4: ...gation Pressing enter repeatedly will move it to that location Esc Button The Esc button is used to exit your present screen and take you back one screen Pressing it multiple times will take you back...

Страница 5: ...icons will appear to view additional information Forward and back buttons will navigate to the next stage Trends Touching this icon will take you to the trending screen where you can view graphically...

Страница 6: ...tem is in cooling Touch this icon to put the system in cool mode and the word cool will appear on the screen Heat Icon Heat will be illuminated only if the system is in heating Touch this icon to put...

Страница 7: ...start up must be verified and cleared via the VARC before system will start normal operation Chilled Water Flow Switch With the system in either heating or cooling mode the Flow switch must be closed...

Страница 8: ...s equipped with a temperature sensor mounted to the condenser coil This sensor is there to sense the coil temperature In heat mode if the coil temperature drops below 40 F the VARC controls will autom...

Страница 9: ...met capacity demand it will reduce the speed of the compressors The compressors will operate at minimal speed to maintain the chilled water loop If the speed of the compressor still exceeds the demand...

Страница 10: ...sor with the lowest running hours will be enabled first and compressor with the highest running hours will be disabled first First stage will be enabled and the compressor will start after CW and SW f...

Страница 11: ...oil lubrication of the system o If the system calls for a stage to be toggled on off the next available stage will be used that meets the staging criteria o Load shedding will occur in multistage oper...

Страница 12: ...screen will also indicate if there is an alarm present on the system by flashing the word alarm in the lower right hand corner The smaller PLD Pro LCD screen also has an audible tone that you will hea...

Страница 13: ...e bottom of the screen the unit will display the envelope status for the operation of the compressor The envelope status basically tells you if the unit is functioning within the control parameters fo...

Страница 14: ...Figure 14 Main Menu Items Screen Navigation Tree Press enter to select items to view and up down the screen will automatically return to the main status screen Menu A On Off Unit o Unit Address 1 Def...

Страница 15: ...active relay outputs This will change depending on what is enabled in the system configuration o D Analog Outputs o NOT USED Menu E Alarm History Will capture the status of the following parameters a...

Страница 16: ...sion the system and must select between yes or no then press enter This will save the information and once commissioned cannot be changed Sub Menu C Working Hours o Compressor o Run hours Actual o Num...

Страница 17: ...ut Actual Value o Output Actual Value o Setpoint 8 9 Default o Band 11 0 Default o Integration Time 20 Default Sub Menu D User Save This is used to save any user specific settings o Save No Default Ye...

Страница 18: ...Disabled o Stage 3 Enabled Default Disabled o Stage 4 Enabled Default Disabled Sub Menu F Manual Management This menu allows the technician to manually operate the relay outputs as well as enable or...

Страница 19: ...ut 12 Amps 230 V Max Breaker 25 Amps 230 VAC Note Increase breaker size to include pump current if running pumps directly off system Maximum Ambient Operating Temperature 140 F 60 C Maximum Rh Conditi...

Страница 20: ...18 Appendix I Touchscreen Navigation MAIN PAGE Figure 15 CHILLER ENABLE Figure 16...

Страница 21: ...19 CHILLER SETPOINTS Figure 17...

Страница 22: ...20 Figure 18 CHILLER STAGE Figure 19...

Страница 23: ...21 Figure 20 PLC HMI Screen With an EEV installed you can monitor the valve position and view your suction pressure and temperature Superheat setpoint and actual will be displayed...

Страница 24: ...22 TRENDS Figure 21 Figure 22...

Страница 25: ...23 ACTIVE ALARMS Figure 23 ALARM HISTORY Figure 24...

Страница 26: ...24 ALARM HELP Figure 25 Figure 26...

Страница 27: ...25 REMOTE SUPPORT Figure 27 REMOTE ENABLE Figure 28...

Страница 28: ...26 REMOTE CONFIGURATION Figure 29...

Страница 29: ...mp F Discharge Temperature F Pressure psi Saturation Temp F Super heat temp F Subcooling temp F Varc 2 4 repeat as above Varc 1 information will show the stage the display is connected to Varc 1 Infor...

Страница 30: ...its psi bar Clock Scheduler Date Hour Day DST Enable Disable DST Enable Transition Time Start End Input Output Analog Input Digital Input Relay Output Analog Outputs Analog Input CW Return Input B001...

Страница 31: ...h Service Settings See page 30 Manual Management Analog Input Digital Input Relay Output Compressor EEV Analog Input Manual Control Manual Pos Status Value CW Return B001 On Off CW Supply B002 On Off...

Страница 32: ...et F S2 probe F S3 offset psig S3 probe psig S4 offset F S4 probe F Working Hour Set Set Point Reset to Zero Run Hours Compressor h Yes No h Chilled Water Pump h Yes No h Seawater Pump h Yes No h Cont...

Страница 33: ...e Buzzer Yes No Startup delay s Enable Unit by Digital Input On Off Supervisor On Off pLAN network On Off Schedule On Off Unit Control Custom 1 On Off Custom 2 On Off Custom 3 On Off Custom 4 On Off A...

Страница 34: ...gs Flow Prove Delay s Off Delay s Reversing valve RV delay time s RV toggle time s Electric Heat Stage Up delay s Stage Down delay s Compressor Alarm Retry Setup Alarm Retry Setup Temperature Limits S...

Страница 35: ...at fixed pos valve forced closed no action Use backup S3 valve at fixed pos valve forced closed no action valve at fixed pos valve forced closed no action Regulation Valve opening at start up Valve o...

Страница 36: ...ag Current A Stator Resistance mOhm Rotor Resistance mOhm Stator Ld inductance mH Leakage factor Lq Inductance mH Speed Loop Kp Speed Loop Ki ms Magnetizing Time ms Starting Current A Freq for Start C...

Страница 37: ...ff min variation bar Control period s Restart delay s Max Retry Speed Management Start up forced speed rps Max speed rps Min speed rps Deceleration rate rps s Acceleration rate rps s Switch off rate r...

Страница 38: ...its Temp Press Other Temp Press Other Temp Press Other Digital Inputs Switches Enable Channel Action Delay Status Flow On Off Open Close s Open Close EH Flow On Off Open Close s Open Close High Pressu...

Страница 39: ...37 Display Address Display Address Display address setting I O Board address Terminal config Terminal configuration P 02 Adr Priv Shared Trm1 Pr Sh Trm2 Pr Sh Trm3 Pr Sh...

Страница 40: ...wired as part of the build process Please also note that as part of a correctly configured multistage system there is no need to set differential hysteresis settings Initial Wiring Seawater and chill...

Страница 41: ...39 Basic wiring diagram...

Страница 42: ...up then but cause networking problems later down the line Press Prg button to the left Scroll up or down to Technician if prompted for a password 3156 Select Information Scroll down for Version Repeat...

Страница 43: ...down Enter Technician Password 3156 Go to stage address Hit enter change address to 2 for chiller 2 3 for chiller 3 etc Exit screen back to main menu and you will see confirmation of change in the to...

Страница 44: ...ove and ensure display address and I O board address is correct for stage Press enter to go into the terminal config settings Trm1 17 for stage 2 18 if stage 3 etc and Pr ID 32 Sh this will allow for...

Страница 45: ...make the following changes to each stage Press enter until the cursor is on Num of stages change from 1 to the correct number of stages for current system Repeat for all stages Go to Technician Scroll...

Страница 46: ...r the press up and or down to select the correct day Press enter to select the year and or up down buttons to select the correct year Press enter again and the cursor drops down to the Hour field Use...

Страница 47: ...45 Enabling Electric Heat Press Prg button Enter service password 3156 Scroll down to Electric Heat enter to select up or down to toggle setting Enter to save...

Страница 48: ...wn to Temperature Units screen Hit enter to select Up or down button to toggle between options Once changed hit enter to return the cursor to the top of the screen You will need to make this change to...

Страница 49: ...the screen 2 Insert USB memory 3 On the touch screen hold your finger on the screen until a pop window is displayed 4 Select update 5 Another pop up will appear and check the box that says Auto select...

Страница 50: ...48 Deleting old program 1 Project manager a On the touch screen hold your finger on the screen until a pop window is displayed b Select Project Manager 2 Select the project you wish to delete...

Страница 51: ...49 3 Click delete project then click yes to confirm 4 The screen will display the following as it in progress of deleting...

Страница 52: ...nager screen will not display the project any longer Click X to exit out of the project manager window Setting Screen Address Time Backlight 1 Find a spot on the Touchscreen that is not a hot spot Tou...

Страница 53: ...51 2 Select Show system settings 3 Use the Next or Back button to spin the wheel until you find Set Device Address...

Страница 54: ...ss the Set Device Address button and you will get another screen 5 Touch the arrow button to select Com1 and change the 31 to 30 6 Then press ok to save changes and click X to close the Device Address...

Страница 55: ...53 7 Use Next or Back to scroll to Display Settings 8 Select Display Settings...

Страница 56: ...9 Click on the checkmark to automatically turn off backlight while on battery power and external power so they are not enabled as shown below 10 Press OK then click X 11 Now press Next to scroll to Ti...

Страница 57: ...55 12 The Date Time Properties window will pop up Look at the time zone and select Eastern Time 13 The Current Time should show the correct time press OK then X to close window...

Страница 58: ...ouchscreen remote screen Ensure you have a 24 Vdc supply to power the display and that the 3 core communication cable is correctly plugged into Serial port 1 not port 2 3 core communication cable term...

Страница 59: ...while maintaining full functionality for the other stages Find below the instructions to access maintenance mode Enabling via PGD1 Display 1 Ensure unit mode is set to OFF In the main screen press ent...

Страница 60: ...5 Scroll to Stage Disable press enter 6 For Stage Control change No to Yes press enter scroll up and press enter 7 The different stages will display on the screen press enter to access each stage and...

Страница 61: ...59 Enabling via Touchscreen 1 Tap the touchscreen to view the menu buttons and select Chiller Summary 2 On Chiller Summary screen click on the wrench to access the maintenance mode pop up...

Страница 62: ...l select Yes from the drop down menu this will enable Maintenance Mode 4 To disable a stage click on the drop down menu to the right of the stage number and select disabled Once complete press X to ex...

Страница 63: ...clogged Check for defective flow switch Bleed air out of the loop water Check loop water pump High Discharge Pressure After 3 retries every 30 mins must be reset Manually Immediate Yes Shut off Unit C...

Страница 64: ...Hours Exceeded Yes Off Heater Check heater voltage Envelope Alarm Manual 60 sec Yes Off compressor Clock Board Fault or Not connected Automatic Immediate Yes Warning Signal Inverter model not compatib...

Страница 65: ...otor and motor cables for ground faults Check the input and output circuits for phase loss detection and rectify Check the condition of the motor and load wiring 16 Drive disabled 17 Motor Phase 18 Fa...

Страница 66: ...ode Retain Mode Electric Heat No No No Logo Dometic BLK Dometic BLK Dometic BLK Background Ocean Ocean Ocean Flow Switch Yes Yes Yes High Pressure Switch Yes Yes Yes ow Pressure Switch No No No Load S...

Страница 67: ...10 10 10 Minutes CW Flow 10 10 10 Seconds Retries 3 3 3 Retry delay 10 10 10 Minutes High Discharge Pressure 550 550 550 PSI Retries 3 3 3 Retry delay 30 30 30 Minutes High Pressure Switch Retry 3 3 3...

Страница 68: ...re AI 7 B7 Discharge Pressure Digital Inputs DI 1 DI1 High Pressure Switch Optional DI 2 DI2 Low Pressure Switch Optional DI 3 DI3 Flow Switch DI 4 DI4 Load Shedding Input DI 5 DI5 Electric Heat Flow...

Страница 69: ...67 VARC Standard Wiring Diagram Figure...

Страница 70: ...68 NOTES...

Страница 71: ...69 NOTES...

Страница 72: ...es dometicusa com 24 7 TECH SUPPORT FOR UNITED STATES AND CANADA 8 00 AM to 5 00 PM Eastern Time 800 542 2477 After hours and weekends 888 440 4494 INTERNATIONAL SALES AND SERVICE Europe and the Middl...

Отзывы: