CT100G Series Inverter
CHAPTER 4 FUNCTION PARAMETER TABLE
- 34 -
Functio
n code
Name
Detailed instruction of parameters
Default
value
Attrib
ution
F02 Group
Start and stop control
F02.00
Start mode
0: start at the starting frequency
1: start after rotating speed tracking
2: Pre excitation
0
○
F02.01
Start delay time
0.0s
~
1000.0s
0.0
○
F02.02
Starting frequency
0.00Hz
~
10.00Hz
0.00
○
F02.03
Hold time of starting frequency 0.0s
~
100.0s
0.0
☆
F02.04
Start DC braking/Pre excitation
current
0%
~
100%
0
☆
F02.05
Start DC braking/Pre excitation
time
0.0s
~
100.0s
0.0
☆
F02.06
ACC and DEC mode
0: linear type
1: S curve A
2: S curve B
0
☆
F02.07
Terminal DI1 characteristic
selection after power on
0: invalid
1:valid
0
☆
F02.08
Restart after power off
0: invalid
1:valid
0
☆
F02.09
Waiting time for restart
0.0s
~
100.0s
0.0
☆
F02.10
Stop mode
0: decelerate to stop
1: coast to stop
0
○
F02.11
Dead time of FWD/REV
0.0s
~
3000.0s
0.0
○
F02.12
Starting frequency before stop
DC braking
0.00Hz
~
max frequency F00.06
0.00
○
F02.13
Waiting time before stop DC
braking
0s
~
100.0s
0.0
○
F02.14
Stop DC braking current
0.0%
~
100%
0
○
F02.15
Stop DC braking time
0.0s
~
100.0s
0.0
○
F02.16
Braking use reate
0%
~
100%
100
○
F02.17
Delay time of dormancy
0.0
~
6500.0s
0.0
○
F02.18
Actuation when running
frequency is less than lower
limit frequency
0: run at lower limit frequency
1: stop
2: 0 speed run
0
○
F02.19
Delay time of dormancy wake
up
0.0s
~
6500.0s
0.0
○
F02.20
Speed track mode
0:start from stop frequency
1:start from working frequency
2: start from max frequency
0
☆
F02.21
Quick or slow speed track
1
~
100
20
○
F02.22
Speed track KP
0
~
1000
500
○
F02.23
Speed track KI
0
~
1000
800
○
F02.24
Speed track current
30%
~
200%
100
☆
F02.25
Speed track low limit
10
~
100%
30
☆
F02.26
Speed track voltage rise time 5
~
30
11
☆
F02.27
Demagnetizing time
0.00
~
5.00s
1.00
☆
F02.28
S curve first phase time rate
0.0%~(100.0%-F06.29)
30.0
☆
F02.29
S curve final phase time rate
0.0%~(100.0%-F06.28)
30.0
☆