31
BH 5910 / 200217 / 190A
Safety gates and E-stop
(switch 1 in position 4)
With switch 10 the maximum number of gates is selected. Open (unused)
inputs (S_1/S_2 and S_3/S_4) have to be linked with a wire bridge.
K1 and K2 can only be activated, if the e-stop loop is closed and all con-
nected gates have been opened and closed again.
Both gate contacts have to be operated within 3 s. If the time difference is
longer, the gate has to be opened before it can be closed again. When all
gates are closed the unit can also be activated by an external connected
simulation button.
After e-stop or power failure the unit can only be reset by manual start.
If changeover contacts are used on the gate switches the switchover time
has to be less then 50 ms. If it is longer the outputs K1 and K2 are switched
off and the unit gives failure code 7. This failure is stored and can only be
reset by disconnecting the auxiliary supply.
Gate monitor and E-stop,
1 gate with 3 NO gate contacts and e-stop loop
Function diagram
NO contacts must be closed when gate is closed, NC contacts must be
open when gate is closed.
E-stop
Auxiliary
voltage (A1/A2)
Gate S1 (S11/S12)
Gate S2 (S13/S14)
Simulation button
(S43/S44)
Gate S3 (S21/S22)
K1/K2 (13-14,
23-24, 33-34)
48 (gates open
or E-stop)
58 (all gates closed,
e-stop loop closed)
: off
: on
: flashing
M8442
Settings on switch 10
Switch
10
No. of
gates
Number and
type of
gate switches
Simulation
button
Feedback circuit
for external con-
tactors
0
2
2 NO contacts
yes
no
1
1
2 C/O contacts
yes
no
2
1
3 NO contacts
yes
no
3
2
2 NO contacts
yes
yes
4
1
2 C/O contacts
yes
yes
5
1
3 NO contacts
yes
yes
6-9
position not allowed (failure 5)
Terminal designation
Ter-
minal
1 gate with
3 NO
gate contacts
2 gate with
2 NO
gate contacts
1 gate with
2 C/O
gate contacts
Feedback cir-
cuit for external
contactors
S11
S12
gate 1, S1
gate 1, S1
gate 1, S1
NO contact
gate 1, S1
common
connector
S14
S13
gate 1, S2
gate 1, S2
gate 1, S1
common
connector
gate 1, S1
NC contact
S21
S22
gate 1, S3
gate 2, S1
gate 1, S2
NC contact
gate 1, S2
common
connector
S24
S23
not connected
gate 2, S2
gate 1, S2
common
connector
gate 1, S2
NO contact
1 E-stop button,
1 Simulation or start button
S31
S32
E-stop, channel 1
S34
S33
E-stop, channel 2
S41
S42
Feedback
circuit
S44
S43
Simulation or start button
Semiconductor outputs
Output
Flashing signal
Continuous signal
48
Open gate, e-stop loop open
or failure in feedback circuit or
failure on simulation button
58
Gates are closed but starting
conditions not fulfilled or E-stop
loop has been opened and closed
again.
K1, K2 can be activated with the
simulation button
Gates are closed and
contacts K1, K2 are
active