37
BH 5910 / 200217 / 190A
Technical Data
Input
Nominal voltage U
N
:
DC 24 V
Voltage range
at max. 5 % residual ripple:
0,85 ... 1,15 U
N
Nominal consumption:
max. 170 mA
(Semiconductor outputs not connected)
Control voltage on
S11, S13, S21, S23,
S31, S33, S41, S43,
48, 58:
DC 23 V at U
N
Control current on
S12, S14, S22, S24,
S32, S34, S42, S44:
4,5 mA at U
N
each
Min. voltage at
terminals S12, S14, S22,
S24, S32, S34 S42, S44:
DC 16 V
Fusing:
internal with PTC
Output
Contacts
BH 5910.03:
3 NO contacts
BH 5910.22:
2 NO contacts, 1 NC contact
The NC contact can only be used as
indicator contact.
Contact type:
Relay, forcibly guided
Operating time typ. at U
N
Function
Manual start
Auto start
Start
Restart
E-stop
Light curtains
Safety gates
2-hand control
45 ms
45 ms
45 ms (Simulation)
54 ms (Activation)
1,6 s
1,6 s
45 ms
45 ms
90 ms (TS)*
)
*
)
TS = closing of gate
max.
switch off time (reaction time)
Function
E-stop
Light curtains
Safety gates
2-hand control
28 ms
28 ms
28 ms
28 ms
Switching off when failure
in feedback circuit:
max. 100 ms
Nominal output voltage:
AC 250 V
DC: see limit curve for arc-free operation
Switching of low loads:
≥
100 mV
Thermal current I
th
:
5 A
Switching capacity
to AC 15
NO contact:
3 A / AC 230 V
IEC/EN 60947-5-1
NC contact:
2 A / AC 230 V
IEC/EN 60947-5-1
to DC 13 at 0,1 Hz:
8 A / DC 24 V
IEC/EN 60947-5-1
Electrical life
to AC 15 at 2 A, AC 230 V:
10
5
switching cycles IEC/EN 60947-5-1
Permissible switching
frequency:
max. 1 200 switching cycles / h
Short circuit strength
max. fuse rating:
6 A gG / gL
IEC/EN 60947-5-1
line circuit breaker:
C 8 A
Mechanical life:
10 x 10
6
switching cycles
Semiconductor outputs
Output (terminal 48 and 58):
transistor outputs, swi
Nominal output voltage:
DC 24 V, max. 100 mA continuous
current, max. 400 mA for 0,5 s internal
short circuit, over temperature and
overload protection
General Data
Operating mode:
Continuous operation
Temperature range
Operation:
±
0 ... + 50
°
C
Storage :
- 25 ... + 85
°
C
Altitude:
< 2000 m
Clearance and creepage
distances
rated impuls voltage /
pollution degree:
4 kV / 2 (basis insulation) IEC 60664-1
EMC
Electrostatic discharge:
8 kV (air)
IEC/EN 61000-4-2
(according to test degree 3)
HF-irradiation:
10 V / m
IEC/EN 61000-4-3
Fast transients
on wires for power supply A1-A2: 2 kV
IEC/EN 61000-4-4
on signal and control wires:
2 kV
IEC/EN 61000-4-4
Surge voltages
between
wires for power supply:
1 kV
IEC/EN 61000-4-5
between wireand ground:
2 kV
IEC/EN 61000-4-5
HF-wire guided:
10 V
Interference suppression:
Limit value class B
EN 55011
Degree of protection:
according to IEC/EN 61496-1 (1997)
the unit has to be mounted in a control
cabinet with protection class 54
Housing:
IP 40
IEC/EN 60529
Terminals:
IP 20
IEC/EN 60529
Housing:
Thermoplastic with V0 behaviour
according to UL subject 94
Vibration resistance:
according to IEC/EN 61496-1 (1997)
Amplitude 0,35 mm IEC/EN 60068-2-6
frequency 10 ... 55 Hz
Shock proof:
Acceleration:
10 g
Impulse length:
16 ms
Number of shocks:
1000 per ax is on all 3 axes
Climate resistance:
0 / 050 / 04
IEC/EN 60068-1
Terminal designation:
EN 50005
Wire connection:
1 x 2,5 mm
2
stranded wire with sleeve or
1 x 4 mm
2
solid or
2 x 1,5 mm
2
stranded wire with sleeve
DIN 46228-1/-2/-3/-4
Wire fixing:
Plus-minus terminal screws M3,5
box terminals with wire protection
Mounting:
DIN rail
IEC/EN 60715
Weigth:
320 g
Dimensions
Width x height x depth:
45 x 84 x 121 mm
Technical Data