5
Firmly grasp the wires near the base and hold the outside
edges of the keypad housing. Line up the red and yellow
wires with the guides on the board to inset the connector
into the J5 keypad terminal. Observe wire colors when
connecting the red, yellow, green, and black wires to the
keypad bus. See Figure 2.
•
Connect red wire to panel terminal 7
•
Connect yellow wire to panel terminal 8
•
Connect green wire to panel terminal 9
•
Connect black wire to panel terminal 10
Additional Power Supply
If the current draw for all keypads exceeds the panel output,
provide additional current by adding a Model 505-12 auxiliary power supply.
1.
Connect all keypad black ground wires to the power supply negative terminal.
2. Run a jumper wire from the power supply negative terminal to the panel common
ground terminal.
3. Connect all keypad power (+12VDC) wires to the power supply positive terminal.
Do not connect the power supply positive terminal to any panel terminal. Refer to
the 505-12 Power Supply Installation Guide if needed (LT-0453).
Keypad Bus Monitor
For listed fire protective systems, the 893A Module or 277 Trouble Sounder must be installed
on the XR150/XR550 Series panel to monitor the keypad bus. It should be programmed to
sound when the keypad bus fails to operate.
Figure 2: Keypad Back Showing