10

Door Strike Relay Operation

When the user code sent from the reader is verified by the panel, the keypad door strike 

relay activates for five seconds. During this time, the access door connected to Zone 2 

must be opened to start the programmed entry/exit timer and Zone Bypass if 

programmed and used. The five second door strike is panel programmable when the 

keypad is used on an XR150/XR550 Series panel. 

Zone 2 Door Contact with Bypass

If the door being released by the 7073/A and 7173 keypad is protected, you can provide 

a programmed bypass time by connecting its contact to Zone 2 (white/red pair) on the 

keypad and enabling the bypass feature. Door contacts may be N/C or N/O. 

Zone 3 Request to Exit

You can also connect a N/O PIR (or other motion sensing device) or a mechanical switch 

to Zone 3 (white/orange pair) on the 7073/A and 7173 keypad to provide Request to Exit 

(REX) capability. When Zone 3 shorts, the keypad relay activates for 5 seconds. During 

this time, the user can open the protected door to start the programmed Bypass entry/exit 

timer. If the door is not opened within five seconds, the relay restores to its locked state. A 

Zone 3 REX is inhibited for three seconds after the keypad reads a card and a door strike 

occurs. This is to allow area entry and pass under a REX PIR.

Use for Access Control

Содержание 7133

Страница 1: ...THINLINETM AND AQUALITETM LCD KEYPAD Installation Guide FRI 2 52 PM 1 2 3 4 5 6 7 8 9 0 CMD A C B D F E G I H J L K V X W S U T P R Q M O N Y Z ENTE R BACK ...

Страница 2: ... 2017 Digital Monitoring Products Inc Information furnished is believed to be accurate and reliable This information is subject to change without notice ...

Страница 3: ...eyboard lighting in alarm conditions Simple harness connection to 4 wire keypad bus Optional back boxes for conduit or wall mount applications Models 7070 A 7073 A 7170 and 7173 Provide four fully programmable Class B Style A supervised power limited protection zones that can be programmed for a variety of burglary and access control applications Models 7063 A 7073 A 7163 and 7173 Provide a built ...

Страница 4: ...eed 500 feet When using 18 gauge wire do not exceed 1 000 feet Install an additional power supply to increase the wire length or add devices Maximum distance for any one circuit length of wire is 2 500 feet regardless of the wire gauge This distance can be in the form of one long wire run or multiple branches with all wiring totaling no more than 2 500 feet As wire distance from the panel increase...

Страница 5: ...he Keypad Bus Wiring Application Note LT 2031 and the 710 Module Installation Sheet LT 0310 for more information Keypad Specifications MODEL NORMAL STANDBY CURRENT ALARM CURRENT FOUR ZONES INTERNAL PROX READER WIEGAND INPUT INTERNAL DOOR STRIKE RELAY 7060 A 7160 72mA 87mA 7063 A 7163 85mA 100mA X 7070 A 7170 72mA 1 6mA per active zone 87mA 2mA per active zone X 7073 A 7173 85mA 1 6mA per active zo...

Страница 6: ...nt from the base and set the cover and components aside See Figure 1 Harness Wiring Use 1k Ohm EOL resistors DMP Model 311 on keypad zones 1 4 Models 7060 A 7063 A 7160 and 7163 Supplied with a 4 wire harness for panel keypad bus connection Models 7070 A 7073 A 7170 and 7173 Supplied with a 12 wire data bus zone harness Four wires connect to the keypad bus The remaining eight wires are for the fou...

Страница 7: ...rrent by adding a Model 505 12 auxiliary power supply 1 Connect all keypad black ground wires to the power supply negative terminal 2 Run a jumper wire from the power supply negative terminal to the panel common ground terminal 3 Connect all keypad power 12VDC wires to the power supply positive terminal Do not connect the power supply positive terminal to any panel terminal Refer to the 505 12 Pow...

Страница 8: ...te Brown Black Ground Green Receive Data Yellow Send Data Red Keypad Power Zone 4 Zone 3 Zone 2 Zone 1 ExternalReader Door Strike 7073 7073A 7173 Keypads All Keypads Zones 1 4 7070 7070A 7073 7073A 7170 7173 Keypads Surface and Backbox Mounting Holes Combined 4 square and 3 gang switch box Mounting Holes Surface and Backbox Mounting Holes All zones are supervised and suitable for fire applications...

Страница 9: ...h DMP proximity keypads If you are using HID cards that have not been purchased directly from DMP it is recommended to thoroughly test the application fully before installation DMP does not guarantee compatibility with credentials not purchased from DMP For listed access control applications the keypad must be installed within the protected area External Access Control Reader To accept Wiegand dat...

Страница 10: ...or Contact optional Zone 1 7 0 Panic optional To Keypad Bus External Card Reader Figure 4 12VDC Reader Wiring Use for Access Control Magnetic Lock and Door Strike Wiring The 7073 A and 7173 keypads provide one internal programmable Form C single pole double throw SPDT relay for controlling door strikes or magnetic locks Three wires on the 5 wire harness violet normally closed N C gray common COM a...

Страница 11: ... wires install the suppressor on the N O and C wires If the device is connected to the N C and C wires install the 333 on N C and C wires See Figure 5 Model 333 Supressor Common Magnetic Door Lock DMP 502 or 505 Power Supply Normally Open Green White D0 White D1 Orange N O Gray C Violet N C N O C N C Normally Closed Keypad 5 Wire Harness Figure 5 5 Wire Harness and 333 Suppressor Installation ...

Страница 12: ...onnecting its contact to Zone 2 white red pair on the keypad and enabling the bypass feature Door contacts may be N C or N O Zone 3 Request to Exit You can also connect a N O PIR or other motion sensing device or a mechanical switch to Zone 3 white orange pair on the 7073 A and 7173 keypad to provide Request to Exit REX capability When Zone 3 shorts the keypad relay activates for 5 seconds During ...

Страница 13: ...ypad brightness tone and volume level Programming Cards into the System 7063 A 7163 7073 A and 7173 only 1 When MENU NO YES displays choose YES and present your proximity credential to the reader or manually enter your user code into the keypad 2 From the user menu select USER CODES Choose ADD At the ENTER CODE display present the credential to the reader ...

Страница 14: ...6 7 8 Power LED Armed LED 32 Character Display Select Keys Command Back Arrow 9 0 CMD JONES RESIDENCE Panic Keys Backlit Logo and Proximity Antenna A C B D F E G I H J L K V X W S U T P R Q M O N Y Z ENTE R BACK Figure 6 7000 Series LCD Keypad ...

Страница 15: ...C SECURITY FRI 2 52 PM 1 2 3 4 5 6 7 8 Power LED Armed LED 32 Character Display Select Keys Command Back Arrow 9 0 CMD A C B D F E G I H J L K V X W S U T P R Q M O N Y Z ENTE R BACK Figure 7 Thinline 7100 Series LCD Keypad ...

Страница 16: ...See Figure 8 Entering Non Alphanumeric Characters Each key has a non alpha special character that is not shown on the keypad Non alphanumeric characters are entered into the keypad the same way as alphanumeric characters See Figure 9 First Letter Second Letter Third Letter Special Character A B C Figure 8 Entering Alpha Characters 1 2 3 4 9 0 CMD 5 6 7 8 A C B D F E G I H J L K V X W S U T P R Q M...

Страница 17: ...ll keypads allow the user to initiate a panic alarm by pressing the 7 and 0 zero keys at the same time for one half 1 2 second Enable the 7 0 Panic function in Installer Options When enabled all keypads send a Zone Short message to the panel for the first zone of the keypad address When the keys are released a Zone Restore message can be sent from the initiating keypad To produce a panic alarm pro...

Страница 18: ...sounded for 30 seconds the user selected brightness level restores Internal Speaker Tone Adjust the keypad internal speaker tone At SET TONE use the left select key to decrease the tone and the right select key to increase the tone Internal Volume Level Adjust the keypad internal speaker volume for key presses and entry delay tone conditions During alarm and trouble conditions the volume is always...

Страница 19: ...electively enable the 2 button Panic keys Bypass REX and set entry card options All programming options display on all keypads However actual operation for some programming options is restricted to the appropriate model Programming Keypad Options Keypad Options KPD OPT To program keypad options press KPD OPT Current Keypad Address Set the current keypad address from 01 to 08 for XT30 XT50 XR150 Se...

Страница 20: ...used when Device Fail Output has a programmed value other than zero Default Keypad Message Enter a DEFAULT KPD MSG of up to sixteen characters to appear at the top of the keypad display Press any select key to clear the current message and enter a new custom display Arm Panic Keys Use this option to configure the top row select key as as two button panic keys To enable or disable a panic option pr...

Страница 21: ...er the number of seconds Once the door strike relay is activated the user has five seconds to open the door connected to Zone 2 The zone is then bypassed for the programmed time or until the contact restores to normal Ten seconds prior to the expiration of the bypass time the keypad beeps if the door is still open If the door remains open when the timer expires a zone open short is sent to the pan...

Страница 22: ...nge is from 5 to 250 seconds Press any select key to enter the number The default is 5 seconds Arming Disarming Wait Time 7063 A 7073 A 7163 7173 Select the number of seconds 1 9 the keypad should wait when an area system displays ALL NO YES during arming disarming or a HOME SLEEP AWAY system waits during arming only If NO or YES or HOME SLEEP or AWAY is not manually selected before the delay expi...

Страница 23: ...ess any top row select key to enter a number between 0 255 to equal the number of bits Default is 26 bits An access card contains data bits for a site code a user code and start stop parity bits The starting position location and code length must be determined and programmed into the keypad See Figure 10 CARD OPTIONS DMP CUSTOM WIEGAND CODE LENGTH 26 0 1 1 1 0 1 0 1 1 0 1 1 0 1 0 1 0 0 0 1 1 0 0 1...

Страница 24: ...number of user code bits Press any select key to enter a custom number Custom numbers can only be a number between 16 40 Press CMD to save the entry The default is the DMP value of 16 Require Site Code 7063 A 7073 A 7163 7173 Press the top row select key under YES to use a site code and press CMD to view the site code entry display Default is NO Door access is only granted when any one site code p...

Страница 25: ...range is 0 999 Number of User Code Digits 7063 A 7073 A 7163 7173 The keypad recognizes user codes from 4 to 12 digits in length Press any select key to enter the user code digit length being used by the panel Default is 5 For an XR150 XR550 Area System use 4 to 10 digits typically 5 For all other systems and panels use 4 digits Any selection above 5 digits require entry of the custom card definit...

Страница 26: ...ode Door access is granted when the Wiegand site code string received matches any site code programmed at SITE CODE ENTRY 3 Press the third select key to choose ANY Any Wiegand Read Door access is granted when any Wiegand string is received 4 Press the fourth select key to choose ON Relay Always On The relay is always on 5 Press CMD and then the first select key to choose LAST Keep Last State The ...

Страница 27: ...me to begin testing individual keys Test Individual Keys The display changes to PRESS KEY TO TEST This option tests each key on the keyboard to ensure it is operating properly Press and hold each key for about two seconds The key number being held appears in the display Verify the correct number displays before testing the next key Zone Test 7070 7073 A 7170 7173 This option allows the keypads to ...

Страница 28: ...ut from proximity credentials The display shows OKAY each time a good proximity read is received Exiting the Installer Options When done press CMD once to return to the Installer Options screen Press the select key under STOP to exit the Installer Options function INPUT WIEGAND Keypad Diagnostics ...

Страница 29: ...keypad Keypad Arming and Disarming Area System Arming and Disarming 1 Press CMD until the keypad displays ARM DISARM 2 Press the select key under the preferred option 3 The keypad displays ENTER CODE The user presents their card to the reader Once validated by the system all areas assigned to that code arm or disarm automatically and the 7073 A and 7173 keypad door strike relay activates See Figur...

Страница 30: ...ctivates Home Away System Arming and Disarming Present your card to the reader If the system is armed once the card is validated all areas are disarmed and the keypad displays ALL SYSTEM OFF If the system is disarmed when you present your card once the card is validated HOME SLEEP AWAY displays Manually select HOME SLEEP AWAY or after a short time out all areas automatically arm in the AWAY mode P...

Страница 31: ...y activate the 7073 A and 7173 Door Strike relay when arming and disarming ABC SECURITY MON 10 20 AM While the keypad displays the Status List present your access card Typically the relay activates for 5 seconds during which time you can open the door Once you open the door you have 40 seconds to exit and close the door before the Zone 2 Bypass expires Figure 13 Present Access Card End User Traini...

Страница 32: ...lidated the system disarms all areas accessible by you and activates the 7073 7073A 7173 Door Strike relay Area systems provide a delay to allow selected areas only to be disarmed See Keypad Arming and Disarming Entry delay starts The System disarms the area and activates the Door Strike Relay ABC SECURITY ENTER CODE Figure 14 Entry Delay End User Training ...

Страница 33: ...31 ...

Страница 34: ...st harmful interference in a residential installation This equipment generates uses and can radiate radio frequency energy and if not installed and used in accordance with the instructions may cause harmful interference to radio communications However there is no guarantee that interference will not occur in a particular installation If this equipment does cause harmful interference to radio or te...

Страница 35: ...out brouillage radioélectrique subi même si le brouillage est susceptible d en compromettre le fonctionnement This system has been evaluated for RF Exposure per RSS 102 and is in compliance with the limits specified by Health Canada Safety Code 6 The system must be installed at a minimum separation distance from the antenna to a general bystander of 7 87 inches 20 cm to maintain compliance with th...

Страница 36: ...alifornia State Fire Marshall CSFM FCC Part 15 RFID Reader FCC ID CCKPC0086 Thinline and Aqualite Industry Canada ID 5251A PC0086 Thinline and Aqualite New York City FDNY COA 6167 Underwriters Laboratory UL Listed ANSI UL 294 Access Control System Units ANSI UL 365 Police Connected Burglar ANSI UL 609 Local Burglar ANSI UL 1023 Household Burglar ANSI UL 1076 Proprietary Burglar ANSI UL 1610 Centra...

Страница 37: ... 12 wire harness 300 512 12 wire harness 5 ft long 330 4 wire dual end harness Proximity Credentials 1306P Prox Patch 1306PW Prox Patch 26 Bit 1326 HID ProxCard II Card 1386 HID ISOProx II Card 1346 HID ProxKey II Access Device Proximity Readers for 7073 AA and 7173 keypads PP 6005B ProxPoint Plus 30mA Standby 75mA Peak MP 5365 MiniProx 20mA Standby 110mA Peak PR 5455 ProxPro II 25mA Standby 125mA...

Страница 38: ...36 ...

Страница 39: ...37 ...

Страница 40: ...LT 0883 1 03 17433 ...

Отзывы: