3.8 Anti-Pass Back
The programming steps below will allow you to set up and program
some basic functions
for the anti-pass back feature (APB).
However,
you must set up the IN and OUT relay programming table in the Remote Account Manager software.
Anti-Pass
Back tables
cannot
be set from the system keypad. Refer to “Remote account manager for windows” manual 1835-066.
3.8.1 Programming the Anti-Pass Back Mode
Anti-Pass Back (APB) can be set to operate in one of
three different modes
.
PASSIVE APB
records an APB Violation and
will
allow
entry or exit.
ACTIVE APB
records an APB Violation and
will not allow
entry or exit.
TRAP APB
records an APB Violation
and
will allow entry but not exit.
1.
Press and enter your four-digit MASTER CODE (
beep
).
2.
Enter for
OFF
, for
PASSIVE
, for
ACTIVE
or for
TRAP
, then press (
beep
).
3.
Press together to end this programming sequence (
beeeeeep
).
??
??
??
??
33
DEF
DEF
44
GHI
GHI
00
OPER
OPER
00
OPER
OPER
11
OPER
OPER
22
ABC
ABC
33
DEF
DEF
This programming step is used to
allow all cards one ‘move’
either in or out without causing an APB Violation to be recorded.
3.8.2 Re-Sync All Devices
1.
Press and enter your four-digit MASTER CODE (
beep
).
2.
Press to
Re-Sync ALL devices
or press to
NOT Re-Sync
, then press (
beeeeeep
).
3.
The programming sequence will end itself after all cards have been re-synced.
??
??
??
??
55
JKL
JKL
44
GHI
GHI
11
OPER
OPER
00
OPER
OPER
This programming step is used to
re-sync a single card
only.
3.8.3 Re-Sync Individual Devices
1.
Press and enter your four-digit MASTER CODE (
beep
).
2.
Enter the
five-digit device number
, then press (
beep
).
3.
Press together to end this programming sequence (
beeeeeep
).
??
??
??
??
66
MNO
MNO
44
GHI
GHI
00
OPER
OPER
This programming step is used to
reset the facility counter.
The facility counter keeps track of the number of “IN’s” and
“OUT’s” when using APB mode.
3.8.4 Reset Facility Counter
1.
Press and enter your four-digit MASTER CODE (
beep
).
2.
Enter a
five-digit number
that you want the count to start at, then press (
beep
).
Example:
to start the count at 25, enter 00025.
3.
Press together to end this programming sequence (
beeeeeep
).
??
??
??
??
88
TUV
TUV
44
GHI
GHI
00
OPER
OPER