background image

dIXEL

 

Installing and Operating Instructions 

1592020070

 

 

1592020070 XR70CX GB m&M r1.130.11.2007.doc 

XR70CX 

                                                                                                                                                                     31

 

14.1

 

ALARM RECOVERY  

Probe alarms 

P1

”, “

P2”,

 “

P3

” and “

P4

” start some seconds after the fault in the related probe; they 

automatically  stop  some  seconds  after  the  probe  restarts  normal  operation.  Check  connections 

before replacing the probe. 

Temperature  alarms  “

HA

”,  “

LA

”  “

HA2

”  and  “

LA2

”  automatically  stop  as  soon  as  the  temperature 

returns to normal values. 

Alarms 

“EA”

 and 

“CA” 

(with i1F=bAL)

 

recover as soon as the digital input is disabled. 

Alarm “

CA”

 (with i1F=PAL) recovers only by 

switching off and on

 the instrument. 

14.2

 

OTHER MESSAGES 

Pon 

Keyboard unlocked. 

PoF 

Keyboard locked 

noP 

In programming mode

: none parameter is present in Pr1 

On the display

 or in dP2, dP3, dP4: the selected probe is nor enabled 

15.

 

TECHNICAL DATA 

Housing: 

self extinguishing ABS.

 

Case: XR70CX 

frontal 32x74 mm; depth 60mm; 

Mounting: XR70CX 

panel mounting in a 71x29mm panel cut-out 

Protection: 

IP20; 

Frontal protection: XR70CX 

IP65 

Connections: 

Screw terminal block 

 2,5 mm

2

 wiring. 

Power supply: 

according  to  the  model:  12Vac/dc,  ±10%;  24Vac/dc,  ±10%;    230Vac 

±

10%, 

50/60Hz, 110Vac 

±

10%, 50/60Hz

 

Power absorption: 

3VA max

 

Display

: 3 digits, red LED, 14,2 mm high; 

Inputs

: Up to 4 NTC or PTC probes.

 

Digital input: 

 free voltage contact 

Relay outputs: compressor 

SPST 8(3) A, 250Vac; SPST 16(6)A 250Vac

 

 

defrost: 

SPDT 8(3) A, 250Vac or SPST 16(6)A 250Vac 

 

fan: 

SPST 5A, 250Vac or SPST 16(6)A 250Vac 

 

aux: 

SPDT 8(3) A, 250Vac or SPST 16(6)A 250Vac 

Data storing

: on the non-volatile memory (EEPROM). 

Kind of action: 

1B; 

Pollution grade: 

2;

Software class: 

A.;  

Rated impulsive voltage

: 2500V; 

Overvoltage Category

: II

 

Operating temperature: 

0÷60 °C;

Storage temperature: 

-30÷85 °C.  

Relative humidity:

 20

÷

85% (no condensing) 

Measuring and regulation range: NTC probe: 

-40÷110°C (-40÷230°F);  

PTC probe: 

-50÷150°C (-58÷302°F) 

Resolution: 

0,1 °C or 1°C or 1 °F (selectable); 

Accuracy (ambient temp. 25°C)

:  ±0,7 °C ±1 digit 

16.

 

CONNECTIONS 

The X-REP

 

output

 

excludes

 the TTL output.. It’s present in the following codes:  

XR70CX- xx

2

xx, XR70CX –xx

3

xx; 

16.1

 

XR70CX – 8A OR 16A COMP. RELAY - 230VAC OR 120VAC 

 

NOTE: 

The 

compressor relay is 

8(3)A or 16(6)A 

according to the 

model. 

24Vac supply

connect to the 

terminals 5 and 6. 

 

16.2

 

XR70CX –4 X 16A - 12VAC/DC 

 

 

17.

 

DEFAULT SETTING VALUES  

Labe

Name Range 

°C/°F 

Level 

Set 

Set point 

LS÷US 

-5.0 

- - - 

Hy 

Differential 

0,1

÷

25.5°C/ 1

÷

 255°F 

2.0 

Pr1 

LS 

Minimum set point 

-50°C

÷

SET/-58°F

÷

SET 

-50.0 

Pr2 

US 

Maximum set point 

SET

÷

110°C/ SET 

÷

 230°F 

110 

Pr2 

Ot 

Thermostat probe calibration 

-12

÷

12°C /-120

÷

120°F 

0.0 

Pr1 

P2P 

Evaporator probe presence 

n=not present; Y=pres. 

Pr1 

OE 

Evaporator probe calibration 

-12

÷

12°C /-120

÷

120°F 

0.0 

Pr2 

P3P 

Third probe presence 

n=not present; Y=pres. 

Pr2 

O3 

Third probe calibration 

-12

÷

12°C /-120

÷

120°F 

Pr2 

P4P 

Fourth probe presence 

n=not present; Y=pres. 

Pr2 

O4 

Fourth probe calibration 

-12

÷

12°C /-120

÷

120°F 

Pr2 

Labe

Name Range 

°C/°F 

Level 

OdS 

Outputs delay at start up 

0÷255 min 

Pr2 

AC 

Anti-short cycle delay 

÷

 50 min 

Pr1 

rtr 

P1-P2 percentage for regulation 

 0 ÷ 100 (100=P1 , 0=P2) 

100 

Pr2 

CCt 

Continuos cycle duration 

0.0÷24.0h 

0.0 

Pr2 

CCS 

Set point for continuous cycle 

 (-55.0÷150,0°C) (-67÷302°F) 

-5 

Pr2 

COn 

Compressor ON time with faulty probe 

÷

 255 min 

15 

Pr2 

COF 

Compressor OFF time with faulty probe  0 

÷

 255 min 

30 

Pr2 

CF 

Temperature measurement unit 

°C 

÷

 °F 

°C  

Pr2 

rES 

Resolution 

in=integer; dE= dec.point

 

dE  

Pr1 

Lod 

Probe displayed 

P1;P2 

P1 

Pr2 

rEd

X-REP display 

P1 - P2 - P3 - P4 - SEt - dtr 

P1 

Pr2 

dLy 

Display temperature delay   

0 ÷ 20.0 min  (10 sec.)  

Pr2 

dtr 

P1-P2 percentage for disply 

 1 ÷ 99 

50 

Pr2 

tdF 

Defrost type 

EL=el. heater;  in= hot gas 

EL 

Pr1 

dFP 

Probe selection for defrost termination 

nP; P1; P2; P3; P4 

P2 

Pr2 

dtE 

Defrost termination temperature 

-50 

÷

 50 °C 

Pr1 

IdF 

Interval between defrost cycles 

÷

 120 ore 

Pr1 

MdF 

(Maximum) length for defrost 

÷

 255 min 

30 

Pr1 

dSd 

Start defrost delay 

0÷99min 

Pr2 

dFd 

Displaying during defrost 

rt, it, SEt, DEF 

it 

Pr2 

dAd 

MAX display delay after defrost 

0 ÷ 255 min 

30 

Pr2 

Fdt 

Draining time 

0÷120 min 

Pr2 

dPo

 

First defrost after startup 

n=after IdF; y=immed. 

Pr2 

dAF 

Defrost delay after fast freezing 

0 ÷ 23h e 50’ 

0.0 

Pr2 

Fnc 

Fan operating mode 

C-n, o-n, C-y, o-Y 

o-n 

Pr1 

Fnd 

Fan delay after defrost 

0÷255min 

10 

Pr1 

Fct 

Differential  of  temperature  for  forced 

activation of fans 

0÷50°C 

10 

Pr2 

FSt 

Fan stop temperature 

-50÷50°C/-58÷122°F 

Pr1 

Fon 

Fan on time with compressor off 

0÷15 (min.) 

Pr2 

FoF 

Fan off time with compressor off 

0÷15 (min.) 

Pr2 

FAP 

Probe selection for fan management 

nP; P1; P2; P3; P4 

P2 

Pr2 

ALc 

Temperat. alarms configuration 

rE= related to set; 

Ab = absolute 

Ab 

Pr2 

ALU 

MAXIMUM temperature alarm 

Set

÷

110.0°C; Set÷230°F 

110 

Pr1 

ALL 

Minimum temperature alarm 

-50.0°C

÷

Set/ -58°F

÷

Set 

-50.0 

Pr1 

AFH 

Differential for temperat. alarm recovery  (0,1°C÷25,5°C) (1°F÷45°F) 

Pr2 

ALd 

Temperature alarm delay 

÷

 255 min 

15 

Pr2 

dAO 

Delay of temperature alarm at start up 

÷

 23h e 50’ 

1.3 

Pr2 

AP2 

Probe for temperat. alarm of condenser 

nP; P1; P2; P3; P4 

P4 

Pr2 

AL2 

Condenser for low temperat. alarm 

(-55 ÷ 150°C) (-67÷ 302°F) 

-40 

Pr2 

AU2 

Condenser for high temperat. alarm 

(-55 ÷ 150°C) (-67÷ 302°F) 

110 

Pr2 

AH2 

Differ. for condenser temp. alar. recovery  [0,1°C ÷ 25,5°C]  [1°F ÷ 45°F]

Pr2 

Ad2 

Condenser temperature alarm delay  

 0 ÷ 254 (min.) , 255=nU 

15 

Pr2 

dA2 

Delay of cond. temper. alarm at start up 

0.0 ÷ 23h  50’ 

1,3 

Pr2 

bLL 

Compr.  off  for  condenser  low 

temperature alarm 

n(0) - Y(1) 

Pr2 

AC2 

Compr.  off  for  condenser  high 

temperature alarm 

n(0) - Y(1) 

Pr2 

tbA 

Alarm relay disabling 

n=no; y=yes 

Pr2 

oA3 

Fourth relay configuration 

ALr = alarm; dEF = do not select 

it; Lig =Light; AUS =AUX; 

onF=always on; Fan= do not 

select it; db = do not select it; 

dF2 = do not select it 

ALr  

Pr2 

AoP 

Alarm relay  polarity  (oA3=ALr) 

oP; cL 

cL 

Pr2 

i1P 

Digital input polarity 

oP=opening;CL=closing 

cL 

Pr1 

i1F 

Digital input configuration 

EAL, bAL, PAL, dor; dEF; Htr, AUS

dor 

Pr1 

did 

Digital input alarm delay 

0÷255min 

15 

Pr1 

Nps 

Number of activation of pressure switch 

0 ÷15  

15 

Pr2 

odc 

Compress  and  fan  status  when  open 

door 

no; Fan; CPr; F_C 

 

F-c 

Pr2 

rrd 

Regulation restart with door open alarm 

n – Y 

Pr2 

HES 

Differential for Energy Saving 

 (-30°C÷30°C) (-54°F÷54°F) 

Pr2 

PbC 

Kind of probe 

Ptc; ntc 

Pr2 

Adr 

Serrial address 

1÷247 

Pr2 

onF 

on/off key enabling 

nu, oFF; ES 

ntc 

Pr1 

dP1 

Room probe display 

-- 

nu 

Pr2 

dP2 

Evaporator probe display 

-- 

 -- 

Pr1 

dP3 

Third probe display 

-- 

 -- 

Pr1 

dP4 

Fourth probe display 

-- 

 -- 

Pr1 

rSE 

Valore set operativo 

actual set 

 -- 

Pr2 

rEL 

Software release 

-- 

 -- 

Pr2 

Ptb 

Map code 

-- 

 -- 

Pr2 

 

2

 Only for models XR70CX–xx

2

xx, XR70CX–xx

3

xx; XR70CX–xx

6

xx; XR70CX–xx

7

xx 

 

 

Dixell S.p.A.  Z.I. Via dell’Industria, 27 

32010 Pieve d’Alpago (BL) ITALY 

tel. +39 - 0437 - 98 33  -  fax +39 - 0437 - 98 93 13 

E-mail: [email protected] - http://www.dixell.com

 

Содержание XR06CX

Страница 1: ...trumento elettronico di controllo Electronic control instrument Elektronischer Regler Instrumento electrónico de control Instrument électronique de contrôle Centralina elettronica di controllo Electronic control panel Elektronische Steuerung Centralita electrónica de control Platine électronique de contrôle XW60K ...

Страница 2: ...tronischer Regler Instrumento electrónico de control Instrument électronique de contrôle Centralina elettronica di controllo Electronic control panel Elektronische Steuerung Centralita electrónica de control Platine électronique de contrôle XW60K I EN D E F pag 2 I EN F pag 23 I EN D E F pag 40 ...

Страница 3: ...EN I D E F X R 0 6 C X Libretto istruzioni Instruction manual Gebrauchsanleitungen Libro de instrucciones Mode d emploi MAY 2012 Electronic control instrument ...

Страница 4: ... il parametro desiderato scorrendo i parametri visualizzati tramite i tasti e 3 Premere il tasto per visualizzare il valore 4 Modificare il valore tramite i tasti e 5 Premere nuovamente per memorizzare il nuovo valore e passare al successivo parametro Uscita Premere quando si visualizza un parametro o attendere 30s senza premere nessun tasto NOTA il nuovo valore impostato viene memorizzato anche q...

Страница 5: ...azione temperatura 0 15 min quando la temperatura aumenta il valore visualizzato viene aggiornato di 1 C o di un 1 F ogni dy minuti SBRINAMENTO td Tipo di sbrinamento EL in EL sbrinamento a resistenze il compressore è fermo in sbrinamento ad inversione di ciclo gas caldo il compressore è attivo dE Temperatura fine sbrinamento 55 50 C 67 99 F nel caso in cui dE Pb questo parametro indica la tempera...

Страница 6: ...e Fn Ventole OFF cP Compressore OFF Fc compressore e ventole OFF Dopo il tempo impostato nel parametro di viene attivato l allarme di porta aperta e visualizzato a display il messaggio dA Il rientro dell allarme è automatico appena l ingresso digitale viene disattivato Gli allarmi di temperatura sono esclusi a porta aperta ALLARME ESTERNO iF EA Dopo il ritardo dato dal parametro di dall attivazion...

Страница 7: ...ti 0 99 hours L1 4 4 4 4 4 Md Durata massima sbrinamento 0 99 min L1 20 20 20 30 30 dd Ritardo attivazione sbrinamento 0 99 min L2 0 0 0 0 0 dF Visualizzazione durante lo sbrinamento rt it SP dE L2 rt rt rt rt rt dt Tempo di gocciolamento 0 99 min L2 0 2 2 2 2 dP Sbrinamento all accensione n y L2 n n n n n VENTOLE FC Modalità funzionamento ventilatori cn on cY oY L1 oY on on on on Fd Ritardo venti...

Страница 8: ...rost will start HOW TO CHANGE A PARAMETER VALUE To change the parameter s value operate as follows 1 Enter the Programming mode by pressing the keys for 3s C or F LED start blinking 2 Select the required parameter through or keys 3 Press the key to display its value 4 Change its value through or keys 5 Press again to store the new value and move to the following parameter To exit Press or wait 30s...

Страница 9: ...splay P1 P2 P1 thermostat probe P2 evaporator probe dy Display delay 0 15 min when the temperature increases the display is updated of 1 C 1 F after this time DEFROST td Defrost type EL in EL electrical heater compressor OFF in hot gas compressor ON dE Defrost termination temperature 55 50 C 67 99 F if dE Pb it sets the temperature measured by the evaporator probe which causes the end of defrost i...

Страница 10: ...the door is opened after the delay time set through parameter di the door alarm is enabled the display shows the message dA The alarm stops as soon as the external digital input is disabled again With the door open the high and low temperature alarms are disabled EXTERNAL ALARM iF EA As soon as the digital input is activated the unit will wait for di time delay before signalling the EA alarm messa...

Страница 11: ...30 id Interval between defrost cycles 0 99 hours L1 4 4 4 4 4 Md Maximum length for defrost 0 99 min L1 20 20 20 30 30 dd Start defrost delay 0 99 min L2 0 0 0 0 0 dF Display during defrost rt it SP dE L2 rt rt rt rt rt dt Drip time 0 99 min L2 0 2 2 2 2 dP Defrost at power on n y L2 n n n n n FANS FC Fans operating mode cn on cY oY L1 oY on on on on Fd Fans delay after defrost 0 99 min L1 0 3 3 3...

Страница 12: ... anzuzeigen 4 Vorgabe ändern mit oder 5 Zum Speichern 1x der nächste Parameter wird angezeigt Exit 1x während ein Parameter angezeigt wird oder 30s warten BEMERKUNG Die neue Vorgabe wird in jedem Fall gespeichert auch wenn die Taste nicht gedrückt wird VERSTECKTE PARAMETER ALLE PARAMETER In der versteckten Parameter Ebene sind alle Parameter verfügbar Versteckte Ebene betreten 1 Die Programmier Eb...

Страница 13: ... CF CF Masseinheit C F C Celsius F Fahrenheit ACHTUNG bei nachträglicher Änderung der Masseinheit müssen alle betreffenden Parameter und Sollwert kontrolliert werden rE rE Auflösung bei C dE in dE Dezimalpunkt zwischen 9 9 und 9 9 C in ganze Zahlen Ld Standard Anzeige P1 Raumfühler P2 Verdampferfühler dy Trägheit der Temperatur Anzeige 0 15min Wenn sich die Temperatur beispielsweise um 1 Grad erhö...

Страница 14: ...Fc Verdichter und Ventilatoren AUS Nach der Verzögerungszeit di wird Tür Alarm signalisiert Es wird dA im Display angezeigt Der Alarm wird automatisch nach dem Ausschalten des Digitaleingangs wiedereingeschaltet Die Temperatur Alarme werden bei offener Tür ausgeschaltet AUßENALARM iF EA Nach der Verzögerungszeit di wird EA angezeigt Die Regelung bleibt unbeeinflusst Automatische Quittierung des Al...

Страница 15: ... 4 4 4 4 4 Md Max Abtaudauer 0 99 min L1 20 20 20 30 30 dd Abtauverzögerung 0 99 min L2 0 0 0 0 0 dF Anzeige während Abtauung rt it SP dE L2 rt rt rt rt rt dt Entwässerungszeit 0 99 min L2 0 2 2 2 2 dP Sofortige Abtauung bei Inbetriebnahme n y L2 n n n n n VENTILATOREN FC Ventilatoren Funktion cn on cY oY L1 oY on on on on Fd Verzögerungszeit nach Abtauung 0 99 min L1 0 3 3 3 3 FS Ventilatorenstop...

Страница 16: ...RO 1 Entre en el modo de programación presionando la teclas por algunos segundos La unidad de medida C o F parpaderá 2 Seleccione el parámetro requerido a través de las teclas y 3 Presione la tecla para visualizar el valor 4 Use las teclas o para cambiar el valor del parámetro 5 Presione para almacenar el nuevo valor y pasar al parámetro siguiente Para salir Presione cuando se visualiza un parámet...

Страница 17: ...a evaporador dy Retardo visualización temperatura 0 15 min cuando la temperatura aumenta el valor visualizado se actualiza de 1 C o de 1 F cada dy minutos DESESCARCHE td Tipo de desescarche EL in EL desescarche por resistencias eléctricas el compresor está apagado in desescarche por gas caliente el compresor funciona dE Temperatura de final de desescarche 55 50 C 67 99 F Si dE Pb indica la tempera...

Страница 18: ...erta de la cámara Cuando la puerta se abre el compresor y los ventiladores actúan en base al valor del paráme tro dC no ventiladores y compresor funcionan normalmente Fn Ventiladores OFF cP compresor OFF Fc compresor y ventiladores OFF Después del tiempo programado en el parámetro di se activa la alarma de puerta abierta y en la pantalla se visualiza el mensaje dA El rearme de la alarma es automát...

Страница 19: ... In EL EL dE Temperatura de final desescarche 55 50 C 58 122 F L1 50 20 20 30 30 id Intervalo entre ciclos de desescarches 0 99 hours L1 4 4 4 4 4 Md Duración máxima desescarche 0 99 min L1 20 20 20 30 30 dd Retardo inicio desescarche 0 99 min L2 0 0 0 0 0 dF Visualización durante el desescarche rt it SP dE L2 rt rt rt rt rt dt Tiempo de goteo 0 99 min L2 0 2 2 2 2 dP Desescarche a la puesta en ma...

Страница 20: ...RE 1 Entrer en mode programmation en appuyant simultanément sur pendant quelques secondes La led C ou F clignote 2 Choisir le paramètre souhaité parmi les paramètres affichés avec les touches et 3 Appuyer sur pour en afficher la valeur 4 Modifier la valeur avec les touches et 5 Appuyer sur pour mémoriser la nouvelle valeur et passer au paramètre suivant Pour sortir Appuyer sur ou attendre pendant ...

Страница 21: ...15 min quand la température augmente l affichage est augmenté de 1 degré Celsius ou Fahrenheit après cette temporisation DEGIVRAGE td Type de dégivrage EL in EL dégivrage électrique compresseur OFF in gaz chaud compresseur ON dE Température de fin dégivrage 55 50 C 67 99 F lorsque dE Pb ce paramètre indique la température de fin dégivrage id Intervalle entre les cycles de dégivrage 0 99 heures Dét...

Страница 22: ... suivant la valeur du paramètre dC no fonctionnement normal des ventilateurs et du compresseur Fn Ventilateurs OFF cP Compresseur OFF Fc compresseur et ventilateurs OFF Après le temps paramétré en di l alarme porte ouverte est activée et le message dA est affiché L alarme sera arrêtée juste après la désactivation de l entrée digitale Avec la porte ouverte les alarmes haute et basse température son...

Страница 23: ...4 4 4 4 Md Durée maximale dégivrage 0 99 min L1 20 20 20 30 30 dd Temporisation activation du dégivrage 0 99 min L2 0 0 0 0 0 dF Température affichée durant le dégivrage rt it SP dE L2 rt rt rt rt rt dt Temps de drainage 0 99 min L2 0 2 2 2 2 dP Dégivrage au démarrage n y L2 n n n n n VENTILATEURS FC Mode de fonctionnement des ventilateurs cn on cY oY L1 oY on on on on Fd Temporisation ventilateur...

Страница 24: ...EN I F X R 7 0 C X Libretto istruzioni Instruction manual Gebrauchsanleitungen Libro de instrucciones Mode d emploi Electronic control l ol ec nt roni l instrument nstrume t ...

Страница 25: ...tempo Terminato lo sbrinamento parte il tempo di sgocciolamento gestibile attraverso il parametro Fdt 3 3 I VENTILATORI Attraverso il parametro FnC si imposta il funzionamento dei ventilatori Con FnC C_n ventole in parallelo al compressore spente durante lo sbrinamento Con FnC o_n ventole sempre accese sono spente in sbrinamento Con FnC C_Y ventole in parallelo al compressore accese durante lo sbr...

Страница 26: ...o4 dtE FCt FSt ALU ALL devono essere opportunamente reimpostati rES Risoluzione solo per C in 1 C dE 0 1 C permette la visualizzazione con il punto decimale Lod Visualizzazione di default P1 P2 P3 P4 SET dtr seleziona la sonda da visualizzare P1 sonda termostato P2 sonda evaporatore P3 III sonda solo modelli abilitati P4 sonda 4 SET set point dtr percentuale di visualizzazione rEd Visualizzazione ...

Страница 27: ...è automatico appena l ingresso digitale viene disattivato 8 3 ALLARME ESTERNO DI BLOCCO i1F bAL Dopo un ritardo di parametro did dall attivazione dell ingresso viene generato un allarme di blocco viene visualizzato il messaggio CA e disattivate le uscite relay della regolazione Il rientro dell allarme è automatico appena l ingresso digitale viene disattivato 8 4 INTERVENTO PRESSOSTATO i1F PAL Se n...

Страница 28: ...iclo continuo 55 0 150 0 C 5 Pr2 Con Tempo compress ON con sonda guasta 0 255 min 15 Pr2 CoF Tempo compress OFF con sonda guasta 0 255 min 30 Pr2 CF Unità misura Celsius Fahrenheit C F C Pr2 rES Risoluzione per C decimale intero dE in dE Pr1 Lod Visualizzazione strumento P1 P2 P3 P4 SEt dtr P1 Pr2 rEd2 Visualizzazione X REP P1 P2 P3 P4 SEt dtr P1 Pr2 dLy Ritardo visualizzazione temperatura 0 20M0 ...

Страница 29: ...ittenti 0 off 0 50 C 10 Pr2 0 0 0 0 0 FSt Temperatura blocco ventole 55 50 0 C 2 Pr1 40 40 40 40 40 Fon Tempo on con compressore spento 0 15 min 0 Pr2 0 0 0 0 0 FoF Tempo off con compressore spento 0 15 min 0 Pr2 0 0 0 0 0 FAP Selezione sonda per ventilatori nP P1 P2 P3 P4 P2 Pr2 P1 P2 P2 P2 P2 ALC Configurazione allarmi relativi assoluti rE Ab Ab Pr2 rE rE rE rE rE ALU Allarme di alta temperatura...

Страница 30: ... mode is selected by means of the FnC parameter FnC C_n fans will switch ON and OFF with the compressor and not run during defrost FnC o_n fans will run even if the compressor is off and not run during defrost After defrost there is a timed fan delay allowing for drip time set by means of the Fnd parameter FnC C_Y fans will switch ON and OFF with the compressor and run during defrost FnC o_Y fans ...

Страница 31: ... case of faulty thermostat probe With COF 0 compressor is always active DISPLAY CF Temperature measurement unit C Celsius F Fahrenheit WARNING When the measurement unit is changed the SET point and the values of the parameters Hy LS US Ot ALU and ALL have to be checked and modified if necessary rES Resolution for C in 1 C dE 0 1 C allows decimal point display Lod Instrument display P1 P2 P3 P4 SET...

Страница 32: ... as the digital input is de activated 8 4 PRESSURE SWITCH i1F PAL If during the interval time set by did parameter the pressure switch has reached the number of activation of the nPS parameter the CA pressure alarm message will be displayed The compressor and the regulation are stopped When the digital input is ON the compressor is always OFF If the nPS activation in the did time is reached switch...

Страница 33: ...mpressor OFF time with faulty probe 0 255 min 30 Pr2 CF Temperature measurement unit C F C Pr2 rES Resolution in integer dE dec point dE Pr1 Lod Probe displayed P1 P2 P1 Pr2 rEd2 X REP display P1 P2 P3 P4 SEt dtr P1 Pr2 dLy Display temperature delay 0 20 0 min 10 sec 0 Pr2 dtr P1 P2 percentage for disply 1 99 50 Pr2 tdF Defrost type EL el heater in hot gas EL Pr1 dFP Probe selection for defrost te...

Страница 34: ...orced activation of fans 0 50 C 10 Pr2 0 0 0 0 0 FSt Fan stop temperature 55 50 0 C 2 Pr1 40 40 40 40 40 Fon Fan on time with compressor off 0 15 min 0 Pr2 0 0 0 0 0 FoF Fan off time with compressor off 0 15 min 0 Pr2 0 0 0 0 0 FAP Probe selection for fan management nP P1 P2 P3 P4 P2 Pr2 P1 P2 P2 P2 P2 ALC Temperat alarms configuration rE Ab Ab Pr2 rE rE rE rE rE ALU MAXIMUM temperature alarm 0 0 ...

Страница 35: ...lateur est entièrement configurable grâce à ses paramètres facilement programmables à partir du clavier 3 CONTROLE DES CHARGES 3 1 LE COMPRESSEUR Time Temper Compr SET ON La régulation est obtenue par la température mesurée par la sonde d ambiance avec un différentiel positif par rapport au point de consigne lorsque la température augmente et atteint le point de consigne plus le différentiel alors...

Страница 36: ...tionne pour maintenir le point de consigne ccS pendant la durée configurée au paramètre CCt Le cycle peut être terminé avant la fin du temps programmé en appuyant sur la même touche o pendant 3 secondes 6 9 LA FONCTION ON OFF Avec onF oFF et en appuyant sur la touche ON OFF le régulateur est éteint Le message OFF s affiche Pendant l état OFF la régulation est arrêtée En appuyant à nouveau sur la t...

Страница 37: ...r le rétablissement de l alarme température du condensateur 0 1 25 5 C 1 45 F Ad2 Temporisation alarme température du condensateur 0 255 min Intervalle de temps entre la détection d une condition d alarme et sa signalisation dA2 Temporisation alarme température du condenseur au démarrage de 0min à 23 5h résolution 10min bLL Compresseur off avec alarme basse température du condensateur n no le comp...

Страница 38: ... 13 2 DÉCHARGEMENT DE LA HOT KEY VERS LE RÉGULATEUR 1 Eteignez le régulateur 2 Insérez la Hot Key programmée dans le connecteur 5 PIN et rallumez le régulateur 3 La liste des paramètres est automatiquement déchargée dans la mémoire du régulateur et le message doL clignote suivi de End clignotant 4 Après 10 secondes le régulateur redémarre avec la liste des nouveaux paramètres 5 Retirez la Hot Key ...

Страница 39: ...rée ventilateurs OFF avec compresseur off 0 15 min 0 Pr2 FAP Sélection sonde des ventilateurs nP P1 P2 P3 P4 P2 Pr2 ALC Configuration alarmes de température rE Ab Ab Pr2 ALU Alarme température maximale 0 0 50 0 C rel ou ALL 150 C 0 90 F rel ou ALL 302 F 110 Pr1 ALL Alarme température minimale 0 0 50 C rel ou 55 ALU 0 90 F rel ou 67 ALU F 50 0 Pr1 AFH Différentiel pour rétablissement alarme tempéra...

Страница 40: ... 0 50 C 10 Pr2 0 0 0 0 0 FSt Température d arrêt des ventilateurs 55 50 0 C 2 Pr1 40 40 40 40 40 Fon Durée ventilateurs ON avec compresseur off 0 15 min 0 Pr2 0 0 0 0 0 FoF Durée ventilateurs OFF avec compresseur off 0 15 min 0 Pr2 0 0 0 0 0 FAP Sélection sonde des ventilateurs nP P1 P2 P3 P4 P2 Pr2 P1 P2 P2 P2 P2 ALC Configuration alarmes de température rE Ab Ab Pr2 rE rE rE rE rE ALU Alarme temp...

Страница 41: ...EN I D E F X W 6 0 K Libretto istruzioni Instruction manual Gebrauchsanleitungen Libro de instrucciones Mode d emploi Electronic control l ol ec nt roni l panel panel ...

Страница 42: ... l intervallo tra cicli di sbrinamento con MdF la sua durata massima con Con P2P si abilita la seconda sonda fine sbrinamento a temperatura o la si disabilita fine sbrinamento a tempo Terminato lo sbrinamento parte il tempo di sgocciolamento gestibile attraverso il parametro Fdt 3 4 I VENTILATORI Attraverso il parametro FnC si imposta il funzionamento dei ventilatori Con FnC C_n ventole in paralle...

Страница 43: ... dalla programmazione 8 3 PER AVVIARE UN CICLO DI SBRINAMENTO MANUALE Per avviare un ciclo di sbrinamento premere il pulsante per almeno 2s 8 4 PER ACCEDERE AI PARAMETRI IN PR1 Per entrare nel menu parametri Pr1 accessibili dall utente 1 Premere per alcuni secondi i tasti SET n e iniziano a lampeggiare 2 Lo strumento visualizza il primo parametro presente in Pr1 8 5 IL MENU NASCOSTO Il menu nascos...

Страница 44: ... impostati in Fon e FoF Con Fon 0 e FoF 0 le ventole restano sempre spente con Fon 0 e FoF 0 le ventole restano sempre spente FoF Tempo ventole spente con compressore spento 0 15min A compressore spento se ci sono le condizioni di temperatura le ventole vengono accese ciclicamente secondo i tempi impostati in Fon e FoF Con FoF 0 e Fon 0 le ventole restano sempre accese con Fon 0 e FoF 0 le ventole...

Страница 45: ...er ottenere una protezione frontale IP65 utilizzare la gomma di protezione frontale mod RGW V La tastiera CX620 va montata a pannello verticale su foro 29x71 mm e fissata con le staffe appositamente fornite Il controllore XW60K va montato su barra Din e collegato alla tastiera tramite due fili di 1mm Il campo di temperatura ammesso per un corretto funzionamento è compreso tra 0 e 60 C Evitare i lu...

Страница 46: ... C 1 digit 17 SCHEMI DI COLLEGAMENTO XW60K 18 VALORI STANDARD Label Descrizione Range Valore Liv SEt Set point LS US 5 0 Hy Isteresi regolazione compressore 0 1 25 5 C 1 45 F 2 0 Pr1 LS Set Point minimo 50 0 C SET 58 F SET 50 0 Pr2 US Set Point massimo SET 110 C SET 230 F 110 Pr2 ot Calibrazione sonda P1 12 12 C 120 120 F 0 0 Pr1 P2P Presenza sonda P2 n Y Y Pr1 oE Calibrazione sonda P2 12 12 C 120...

Страница 47: ...Funzione ingresso digitale EAL bAL PAL dor dEF Htr AUS dor Pr1 did Ritardo allarme da ingresso digitale configurabile 0 255min 15 Pr1 nPS Num interventi ingresso digitale per allarme pressostato 0 15 15 Pr2 OdC Controllo per porta aperta ventole e compressore no Fan CPr F_C F c Pr2 rrd Ripartenza regolazione con allarme porta aperta n Y y Pr2 HES Incremento temperatura in Energy Saving 30 C 30 C 5...

Страница 48: ...mpo off con compressore spento 0 15 min 0 Pr2 0 0 0 0 0 FAP Selezione sonda ventilatori nP P1 P2 P3 P4 P2 Pr2 nP P2 P2 P2 P2 ACH Tipo azione regolatore ausiliario CL Ht cL Pr2 CL CL CL CL CL SAA Set point regolatore ausiliario 50 0 110 C 58 230 F 0 Pr2 0 0 0 0 0 SHy Differenziale per regolatore ausiliario 0 1 25 5 C 1 45 F 2 Pr2 2 2 2 2 2 ArP Selezione sonda per regolatore ausiliario nP P1 P2 P3 n...

Страница 49: ...d of defrost dripping time is started its length is set in the FSt parameter With FSt 0 the dripping time is disabled CONTROL OF EVAPORATOR FANS The fan control mode is selected by means of the FnC parameter FnC C_n fans will switch ON and OFF with the compressor and not run during defrost FnC o_n fans will run even if the compressor is off and not run during defrost After defrost there is a timed...

Страница 50: ...essing SET n In HIDDEN MENU when a parameter is present in First Level the decimal point is on 5 8 HOW TO CHANGE THE PARAMETER VALUE 1 Enter the Programming mode 2 Select the required parameter with o or n 3 Press the SET key to display its value and LED starts blinking 4 Use o or n to change its value 5 Press SET to store the new value and move to the following parameter To exit Press SET UP or w...

Страница 51: ...ed ALL Low temperature alarm setting ALC rE 0 50 C or 90 F ALC Ab 50 C or 58 F ALU when this temperature is reached and after the ALd delay time the LA alarm is enabled AFH Temperature alarm and fan differential 0 1 25 5 C 1 45 F Intervention differential for temperature alarm set point and fan regulation set point always positive ALd Temperature alarm delay 0 255 min time interval between the det...

Страница 52: ... Wing units can UPLOAD or DOWNLOAD the parameter list from its own E2 internal memory to the Hot Key and vice versa 11 1 DOWNLOAD FROM THE HOT KEY TO THE INSTRUMENT 1 Turn OFF the instrument by means of the ON OFF key remove the TTL serial cable if present insert the Hot Key and then turn the Wing ON 2 Automatically the parameter list of the Hot Key is downloaded into the Wing memory the DoL messa...

Страница 53: ...st delay after fast freezing 0 23h 50 min 0 0 Pr2 FANS FnC Fans operating mode C n C y O n O y o n Pr1 Fnd Fans delay after defrost 0 255 min 10 Pr1 Fct Differential of temperature for forced activation of fans 0 50 C 10 Pr2 Label Name Range Default Level FSt Fans stop temperature 50 0 110 C 58 230 F 2 Pr1 Fon Fan on time with compressor off 0 15 min 0 Pr2 FoF Fan off time with compressor off 0 15...

Страница 54: ...40 40 40 40 Fon Fan on time with compressor off 0 15 min 0 Pr2 0 0 0 0 0 FoF Fan off time with compressor off 0 15 min 0 Pr2 0 0 0 0 0 FAP Probe selection for fan management nP P1 P2 P3 P4 P2 Pr2 nP P2 P2 P2 P2 ACH Kind of action for auxiliary relay CL Ht cL Pr2 CL CL CL CL CL SAA Set Point for auxiliary relay 50 0 110 C 58 230 F 0 Pr2 0 0 0 0 0 SHy Differential for auxiliary relay 0 1 25 5 C 1 45...

Страница 55: ...ung mit Warmgas der Kompressor bleibt eingeschaltet Mit dem Parameter IdF wird der Zeitraum zwischen den Abtauzyklen eingestellt mit MdF dessen maximale Dauer mit P2P wird der zweite Fühler temperaturgesteuertes Ende der Abtauung aktiviert oder deaktiviert zeitgesteuertes Ende der Abtauung Nach der Abtauung beginnt die Abtropfzeit welche mit dem Parameter Fdt verwaltet werden kann 3 4 DIE GEBLÄSE ...

Страница 56: ...erlassen 7 3 ZUM STARTEN EINES MANUELLEN ABTAUZYKLUS Zum Starten eines Abtauzyklus die Taste für mind 2 Sek drücken 7 4 ZUM AUFRUFEN DER PARAMETER IN PR1 Zum Aufrufen des Menüs Pr1 mit den benutzerdefinierbaren Parametern 1 Für einige Sekunden die Tasten SET und n drücken und beginnen zu blinken 2 Das Gerät zeigt den ersten in Pr1 enthaltenen Parameter an 7 5 DAS VERSTECKTE MENÜ Das versteckte Men...

Страница 57: ...3h 50min Zeitintervall zwischen dem Ende des Gefriervorgangs und dem nächsten damit zusammenhängenden Abtauvorgang GEBLÄSE FnC Gebläsebetrieb C n parallel zum Verdichter bei Abtauung ausgesch o n Dauerbetrieb bei der Abtauung abgeschaltet C Y parallel zum Verdichter bei Abtauung eingesch o Y Dauerbetrieb bei der Abtauung abgeschaltet Fnd Einschaltverzögerung Gebläse nach Abtauvorgang 0 255min Zeit...

Страница 58: ...d die Regelung unterbrochen Um den Betrieb wieder normal aufzunehmen muss das Gerät aus und wieder eingeschaltet werden Wenn der Eingang aktiviert ist ist der Verdichter immer ausgeschaltet 9 5 AKTIVIERUNG HILFSRELAIS i1F AUS Bei oA3 AUS kehrt der Digitaleingang den Zustand des Hilfsrelais um 9 6 UMSCHALTUNG DES CONTROLLERS KALT HEISS i1F Htr Solange der Digitaleingang aktiviert ist wird die Aktio...

Страница 59: ... LEDs Höhe 14 2mm Optionaler Ausgang Buzzer Leistungsmodul XW60K Gehäuse 8 DIN 140X176X148 Anschlüsse Schraubenklemmleiste für Leiter 2 5 mm2 oder hitzebeständige 6 3mm Faston Stecker Stromversorgung 230V oder 110V 10 oder 24V Leistungsaufnahme 10VA max Eingänge 4 NTC Fühler Konfigurierbare digitale Eingänge spannungsfreie Kontakte Ausgänge am Relais Gesamtstrom aller Lasten MAX 20A Verdichter Rel...

Страница 60: ...hluss Temperaturalarm beim Power On 0 0 23h 50 1 3 Pr2 bLL Verdichtersperre für Alarm niedrige Temp 2 n 0 Y 1 n Pr2 AC2 Verdichtersperre für Alarm hohe Temp 2 n 0 Y 1 n Pr2 tbA Quittierung Alarmrelais n nein y ja y Pr2 oA3 Konfiguration Funktion Ausgang AUX3 ALr dEF Lig AUS onF Fan db dF2 Lig Pr2 AOP Polarität Alarmausgänge oP cL cL Pr2 i1P Polarität des digitalen Eingangs oP CL cL Pr1 i1F Funktio...

Страница 61: ...erdichter 0 15 min 0 Pr2 0 0 0 0 0 FoF OFF Zeit bei abgeschaltetem Verdichter 0 15 min 0 Pr2 0 0 0 0 0 FAP Wahl des Gebläsefühlers nP P1 P2 P3 P4 P2 Pr2 nP P2 P2 P2 P2 ACH Art des Hilfsregler Betriebs CL Ht cL Pr2 CL CL CL CL CL SAA Setpoint Hilfsregler 50 0 110 C 58 230 F 0 Pr2 0 0 0 0 0 SHy Differenzial für Hilfsregler 0 1 25 5 C 1 45 F 2 Pr2 2 2 2 2 2 ArP Wahl Fühler für Hilfsregler nP P1 P2 P3...

Страница 62: ...arámetro MdF mientras que el parámetro P2P habilita la segunda sonda fin de deshielo a temperatura o queda deshabilitada fin de deshielo a tiempo Al final del deshielo comienza el tiempo de drenaje se controla mediante el parámetro Fdt 3 4 CONTROL DE LOS VENTILADORES DEL EVAPORADOR El modo de control de los ventiladores se selecciona con el parámetro FnC FnC C n ventiladores operan o se detienen c...

Страница 63: ...l tiempo de expiración 15 sg 7 5 2 Como remover un parámetro desde el menu secreto al Pr1 y viceversa Cada parámetro en MENU SECRETO puede removerse o ponerse en Pr1 nivel usuario presionando SET n En el Menu secreto cuando un parámetro está presente en Pr1 el LED de punto decimal está encendido 7 6 COMO VARIAR EL VALOR DE LOS PARAMETROS 1 Entre en el modo Programación 2 Seleccione el parámetro re...

Страница 64: ...iempo de retardo ALd se activa la alarma HA ALL Fijación alarma de baja temperatura 50 0 SET C 58 230 F Cuando se alcanza esta temperatura y después del tiempo de retardo ALd se activa la alarma LA AFH Diferencial recuperación alarmas de temperatura ventiladores 0 1 25 5 C 1 45 F Diferencial para la recuperación de las alarmas de temperatura y las activación de los ventiladores ALd Retardo de la a...

Страница 65: ...alefactores o del punto de mayor temperatura durante el deshielo 12 LINEA SERIE TTL RS485 La linea serie TTL disponible a través del conector HOT KEY permite mediante un módulo intermedio TTL RS485 XJ485 CX el conectar el instrumento a una red compatible ModBUS RTU como el sistema de monitorización Dixell XJ500 Versión 3 0 Los instrumentos pueden ser ordenados con la salida serial RS485 opcional 1...

Страница 66: ...spues del inicio n y n Pr2 dAF Retardo deshielo después enfr rápido 0 23h 50 min 0 0 Pr2 Fnc Modo de control de los ventiladores C n C y O n O y o n Pr1 Fnd Retardo ventiladores después deshielo 0 255 min 10 Pr1 Fct Diferencial temperatura anti ventiladores intermitentes 0 50 C 10 Pr2 FSt Temperatura paro ventiladores 50 50 C 58 122 F 2 Pr2 Fon Tiempo ventiladores encendidos con compresor apagado ...

Страница 67: ...0 0 0 FoF Tiempo ventiladores y compresor apagados 0 15 min 0 Pr2 0 0 0 0 0 FAP Selección sonda ventiladores nP P1 P2 P3 P4 P2 Pr2 nP P2 P2 P2 P2 ACH Tipo de accion para relé auxiliar CL Ht cL Pr2 CL CL CL CL CL SAA Set Point para relé auxiliar 50 0 110 C 58 230 F 0 Pr2 0 0 0 0 0 SHy Diferencial para relé auxiliar 0 1 25 5 C 1 45 F 2 Pr2 2 2 2 2 2 ArP Selección de sonda relé auxiliar nP P1 P2 P3 n...

Страница 68: ...de drainage commence sa durée étant configurée au paramètre Fst Avec FSt 0 le temps de drainage est désactivé 3 4 CONTROLE DES VENTILATEURS D EVAPORATEUR Le mode de contrôle des ventilateurs est sélectionné grâce au paramètre FnC FnC C_n les ventilateurs seront ON et OFF avec le compresseur et ne fonctionneront pas pendant le dégivrage FnC o_n les ventilateurs fonctionneront même si le compresseur...

Страница 69: ...ondes l affichage normal revient 7 2 COMMENT MODIFIER LE POINT DE CONSIGNE 1 Appuyer sur la touche SET pendant plus de 2 secondes 2 La valeur du point de consigne s affiche et la led C ou F clignote 3 Changer la valeur du point de consigne avec les touches o ou n dans les 10s 4 Pour mémoriser la nouvelle valeur du point de consigne appuyer de nouveau sur la touche SET ou attendre 10s 5 COMMENT DEM...

Страница 70: ...rage du dégivrage SEt point de consigne dEF code dEF dEG code dEG dAd Temporisation maximum de l affichage après le dégivrage 0 255 min Indique la durée maximum entre la fin du dégivrage et le réaffichage de la température réelle de la chambre Fdt Durée de drainage 0 60 min Intervalle de temps entre la température atteinte de fin de dégivrage et le redémarrage normal de la régulation Cette durée p...

Страница 71: ...d la sortie alarme est activée et le message dA s affiche et la régulateur redémarre si rrd yES L alarme s arrête dès que l entrée digitale externe est à nouveau désactivée Lorsque la porte est ouverte les alarmes haute et basse température sont désactivées 9 2 ALARME GENERIQUE i1F EAL Quand l entrée digitale est activée le régulateur attend la temporisation did avant de signaler le message d alar...

Страница 72: ...ongtemps que les conditions d alarme demeurent Tous les messages s affichent alternativement avec la température d ambiance sauf P1 qui clignote EE peut être effacé en appuyant sur n importe quelle touche le message rSt est affiché pendant plus de 3 secondes avant que le fonctionnement normal ne reprenne 14 2 INHIBITION BUZZER RELAIS ALARME Si tbA y dès qu un signal d alarme est détecté le buzzer ...

Страница 73: ... 0 15 min 0 Pr2 FAP Sélection sonde des ventilateurs nP P1 P2 P3 P4 P2 Pr2 ACH Type d action relais auxiliaire CL Ht cL Pr2 SAA Point de consigne relais auxiliaire 50 0 110 C 58 230 F 0 0 Pr2 SHy Différentiel relais auxiliaire 0 1 25 5 C 1 45 F 2 0 Pr2 ArP Sélection sonde relais auxiliaire nP P1 P2 P3 P4 nP Pr2 Sdd Sortie relais travaille pendant le dégivrage n y n Pr2 ALP Sélection sonde alarmes ...

Страница 74: ...ON avec compresseur off 0 15 min 0 Pr2 0 0 0 0 0 FoF Durée ventilateurs OFF avec compresseur off 0 15 min 0 Pr2 0 0 0 0 0 FAP Sélection sonde des ventilateurs nP P1 P2 P3 P4 P2 Pr2 nP P2 P2 P2 P2 ACH Type d action relais auxiliaire CL Ht cL Pr2 CL CL CL CL CL SAA Point de consigne relais auxiliaire 50 0 110 C 58 230 F 0 Pr2 0 0 0 0 0 SHy Différentiel relais auxiliaire 0 1 25 5 C 1 45 F 2 Pr2 2 2 2...

Страница 75: ......

Страница 76: ...COD 1MNLE020 ...

Отзывы: