XR70CX
EN
STANDARD VALUES
Defrost
Defrost
Defrost
BY AIR
BY HOT GAS
BY HEATERS
Label Description
Range
Default Level TA TN TB TN TB
SEt
Set point
LS - US
-5,0
-
10
0
-20
0
-20
Hy
Differential
(0,1°C÷25,5°C)
2,0
Pr1
2
2
2
2
2
LS
Minimum set point
(-55,0°C÷SET)
-50,0
Pr2
5
-5
-18
5
-18
US
Maximum set point
(SET÷150,0°C)
110
Pr2
15
5
-25
-5
-25
ot
Thermostat probe calibration
(-12,0÷12,0°C)
0,0
Pr1
0
0
0
0
0
P2P
Evaporator probe presence
n – Y
Y
Pr1
0
0
0
0
0
oE
Evaporator probe calibration
(-12,0÷12,0°C)
0,0
Pr2
0
0
0
0
0
P3P
Third probe presence
n – Y
n
Pr2
n
n
n
n
n
o3
Third probe calibration
(-12,0÷12,0°C)
0
Pr2
0
0
0
0
0
P4P
Fourth probe presence
n – Y
n
Pr2
n
n
n
n
n
o4
Fourth probe calibration
(-12,0÷12,0°C)
0
Pr2
0
0
0
0
0
odS
Outputs delay at start up
0÷255 (min.)
0
Pr2
0
0
0
0
0
AC
Anti-short cycle delay
0÷50 (min.)
1
Pr1
2
2
2
2
2
rtr
P1-P2 percentage for regulation
0 ÷ 100 (100=P1 , 0=P2)
100
Pr2
100
100
100
100
100
CCt
Continuos cycle duration
0÷24.0h
0,0
Pr2
0
0
0
0
0
CCS
Set point for continuous cycle
(-55.0÷150,0°C)
-5
Pr2
0
0
0
0
0
Con
Compressor ON time with faulty probe
0÷255 (min.)
15
Pr2
15
15
15
15
15
CoF
Compressor OFF time with faulty probe
0÷255 (min.)
30
Pr2
15
15
15
15
15
CF
Temperature measurement unit
°C - °F
°C
Pr2
°C
°C
°C
°C
°C
rES
Resolution
dE – in
dE
Pr1
in
in
in
in
in
Lod
Probe displayed
P1 - P2 - P3 - P4 - SEt - dtr
P1
Pr2
P1
P1
P1
P1
P1
rEd
2
X-REP display
P1 - P2 - P3 - P4 - SEt - dtr
P1
Pr2
P1
P1
P1
P1
P1
dLy
Display temperature delay
0 ÷ 20M0 (120) (10 sec.)
0
Pr2
0
0
0
0
0
dtr
P1-P2 percentage for disply
1 ÷ 99
50
Pr2
0
0
0
0
0
tdF
Defrost type
EL – in
EL
Pr1
EL
in
in
EL
EL
dFP
Probe selection for defrost termination
nP; P1; P2; P3; P4
P2
Pr2
nP
P2
P2
P2
P2
dtE
Defrost termination temperature
(-55÷50.0°C)
8
Pr1
50
20
20
30
30
IdF
Interval between defrost cycles
0÷120 (hours)
6
Pr1
4
3
3
3
3
MdF
(Maximum) length for defrost
0÷255 (min.)
30
Pr1
30
20
20
30
30
dSd
Start defrost delay
0÷255 (min.)
0
Pr2
0
0
0
0
0
dFd
Displaying during defrost
rt - it - SEt- dEF
it
Pr2
rt
rt
rt
rt
rt
dAd
MAX display delay after defrost
0÷255 (min.)
30
Pr2
0
0
0
0
0
Fdt
Draining time
0÷255 (min.)
0
Pr2
2
2
2
2
2
dPo
First defrost after startup
n – Y
n
Pr2
n
n
n
n
n
dAF
dAF Defrost delay after fast freezing
0÷24.0h
0,0
Pr2
0
0
0
0
0
FnC
Fan operating mode
C_n - O_n - C_Y - O_Y
o-n
Pr1
o-Y
o-n
o-n
o-n
o-n
Fnd
Fan delay after defrost
0÷255 (min.)
10
Pr1
3
3
3
3
3
FCt
Differential of temperature for forced activation of fans
(0÷50°C)
10
Pr2
0
0
0
0
0
FSt
Fan stop temperature
(-55÷50.0°C)
2
Pr1
40
40
40
40
40
Fon
Fan on time with compressor off
0÷15 (min.)
0
Pr2
0
0
0
0
0
FoF
Fan off time with compressor off
0÷15 (min.)
0
Pr2
0
0
0
0
0
FAP
Probe selection for fan management
nP; P1; P2; P3; P4
P2
Pr2
P1
P2
P2
P2
P2
ALC
Temperat. alarms configuration
rE – Ab
Ab
Pr2
rE
rE
rE
rE
rE
ALU
MAXIMUM temperature alarm
0,0÷50,0°C rel. o ALL÷150°C
110
Pr1
5
5
5
5
5
ALL
Minimum temperature alarm
0.0÷50°C rel. o -55÷ALU;
-50,0
Pr1
5
5
5
5
5
AFH
Differential for temperat. alarm recovery
(0,1°C÷25,5°C)
1
Pr2
2
2
2
2
2
ALd
Temperature alarm delay
0÷255 (min.)
15
Pr2
0
0
0
0
0
dAo
Delay of temperature alarm at start up
0÷24.0h
1,3
Pr2
3
3
4
3
4
AP2
Probe for temperat. alarm of condenser
nP; P1; P2; P3; P4
P4
Pr2
nP
nP
nP
nP
nP
AL2
Condenser for low temperat. alarm
(-55 ÷ 150°C)
-40
Pr2
-40
-40
-40
-40
-40
AU2
Condenser for high temperat. alarm
(-55 ÷ 150°C)
110
Pr2
150
150
150
150
150
AH2
Differ. for condenser temp. alar. recovery
[0,1°C ÷ 25,5°C]
5
Pr2
5
5
5
5
5
Ad2
Condenser temperature alarm delay
0 ÷ 254 (min.) , 255=nU
15
Pr2
15
15
15
15
15
dA2
Delay of cond. temper. alarm at start up
0 ÷ 24H0(144)
13
Pr2
13
13
13
13
13
bLL
Compr. off for condenser low temperature alarm
n(0) - Y(1)
n
Pr2
n
n
n
n
n
AC2
Compr. off for condenser high temperature alarm
n(0) - Y(1)
n
Pr2
n
n
n
n
n
tbA
Alarm relay disabling
n=no; y=yes
y
Pr2
y
y
y
y
y
oA3
Fourth relay configuration
ALr = alarm; dEF = do not select it;
ALr
Pr2
ALr
ALr
ALr
ALr
ALr
Lig = Light; AUS = AUX;
onF = always on; Fan = do not select it;
db = do not select it; dF2 = do not select it
AoP
Alarm relay polarity (oA3=ALr)
oP; cL
cL
Pr2
oP
CL
CL
CL
CL
i1P
Digital input polarity
OP – CL
cL
Pr1
oP
Op
oP
oP
oP
i1F
Digital input configuration
EAL - bAL - PAL- dor - dEF
dor
Pr1
dor
dor
dor
dor
dor
AUS - Htr - FAn - ES
did
Digital input alarm delay
0÷255 (min.)
15
Pr1
0
60
60
60
60
nPS
Number of activation of pressure switch
0÷15
15
Pr2
0
10
10
10
10
OdC
Compress and fan status when open door
no - FAn - CP - F - C
F-c
Pr2
F-C
F-C
F-C
F-C
F-C
rrd
Regulation restart with door open alarm
n – Y
y
Pr2
n
n
n
n
n
HES
Differential for Energy Saving
(-30°C÷30°C)
0
Pr2
0
0
0
0
0
Adr
Serrial address
0÷247
1
Pr2
1
1
1
1
1
PbC
Kind of probe
PtC – ntC
ntc
Pr1
ntc
ntc
ntc
ntc
ntc
onF
on/off key enabling
nu, oFF; ES
nu
Pr2
nu
nu
nu
nu
nu
dP1
Room probe display
(value probe)
-
Pr2
-
-
-
-
-
dP2
Evaporator probe display
(value probe)
-
Pr1
-
-
-
-
-
dP3
Third probe display
(value probe)
-
Pr1
-
-
-
-
-
dP4
Fourth probe display
(value probe)
-
Pr1
-
-
-
-
-
rSE
Valore set operativo
actual set
-
Pr2
-
-
-
-
-
rEL
Software release
read only
-
Pr2
-
-
-
-
-
Ptb
Map code
read only
-
Pr2
-
-
-
-
-