background image

12

8.3 Assembly of Hopper to Cleaning Sections

As previously noted (see 

section 8

), the hopper (lower level) and cleaning section (middle level) supplied for Typhoon Central Dust Collector are 

shipped separately for installation at the jobsite. Follow hoisting instructions from Section 6. Field assembly of these sections will be as follows:

If the baffles of the middle section were shipped separately, they will need to be installed prior to mounting the middle section on the lower section.

Securely mount the middle section on stands. Apply bead of 
silicone along bolting edge.

Insert the middle section baffles and bolt in place with bolt, lock 
washer, washer, washer, nut. Spray with rubber sealant.

Содержание Typhoon TY-10000

Страница 1: ...intenance Manual TYPHOON CENTRAL DUST COLLECTOR Visit our Website for more information on this product www diversitech air com www diversitech ca 1200 55th Avenue Montreal Quebec H8T 3J8 Tel 1 800 361...

Страница 2: ...rk Installation 18 SECTION 9 WATER LEVEL CONTROL OPTIONS 19 SECTION 10 START UP OPERATION 19 10 1 Principles of Operation 19 10 2 Controls 19 10 3 Water Level Monitoring 20 10 4 Alarms 20 10 5 Level S...

Страница 3: ...and comply with NFPA 654 Standard for the Prevention of Fire and Dust Explosions from the Manufacturing Processing and Handling of Combustible Particulate Solids and those other documents referenced t...

Страница 4: ...r incorporates a fan which is close coupled and installed on top of the Typhoon Central Dust Collector or installed separately typically ground mounted and ducted to the outlet of the Typhoon Central...

Страница 5: ...non metallic materials that may not present an explosion hazard As mentioned the Typhoon Central Dust Collector is primarily particularly effective for the collection of dust generated by the working...

Страница 6: ...he make up water connection or by electrical controls that automatically add water as needed to compensate for evaporation and water lost as the collected dust is removed from the unit The Diversitech...

Страница 7: ...the load and strapping it to the handling device Care shall be taken to ensure that the equipment is not dropped or subjected to any impact loads Any missing goods should be noted on the delivery rece...

Страница 8: ...ppropriate hoisting procedure should be followed according to 5 3 Rigging and Hoisting Instructions 5 6 Middle Section Hoisting Hoisting must be done from the hoist mounts Appropriate hoisting procedu...

Страница 9: ...Appropriate hoisting procedure should be followed according to 5 3 Rigging and Hoisting Instructions 5 8 Motor Blower Hoisting Hoisting must be done from the hoist mounts Appropriate hoisting procedur...

Страница 10: ...ations and anchor bolts When locating the Typhoon Central Dust Collector the design engineer shall consider the many factors associated with site selection including but not limited to seismic design...

Страница 11: ...Top section Blower and Motor assembly 8 2 Foundation Installation and Levelling Prepare the foundation by drilling anchor bolt holes according to the supplied dimensional drawings Install the Typhoon...

Страница 12: ...hoisting instructions from Section 6 Field assembly of these sections will be as follows If the baffles of the middle section were shipped separately they will need to be installed prior to mounting...

Страница 13: ...flange to create a gasket with the middle section Lower the middle section carefully onto the flange of the hopper section watching for interference between intermediate sheets and baffles Set the cle...

Страница 14: ...g the flange between the Typhoon Central Dust Collector middle section and the clean air transition section Locate the middle section top flange and wipe clean Place sealant tape or a thick constant b...

Страница 15: ...er and motor can be installed As previously noted see section 8 3 the motor and blower supplied for Typhoon Central Dust Collector ships separately for installation at the jobsite With the clean air s...

Страница 16: ...ill be provided with the Typhoon Central Dust Collector and will need to be installed on site Connect water inlet L piping Connect the water inlet solenoid Connect the blue pressure hose to the water...

Страница 17: ...e and green wires in accordance with wiring diagram Run water level sensor wire cable to the control box and see section 8 8 for electrical connection Secure the electrical cable to body with cable cl...

Страница 18: ...yphoon Central Dust Collector to the customer s drain line or sewer The customer s drain or sewer line MUST be equal to or larger in size to the drain from the Typhoon Central Dust Collector For the f...

Страница 19: ...uct is designed to capture potentially combustible dust particulate from certain industrial applications using a wet filtration process When operating air and dust is drawn into the table passes throu...

Страница 20: ...el will be heard When one of these alarms is present the machine will lock down and will not allow to be started Motor Overload if the main motor overload is tripped The alarm will remain until the si...

Страница 21: ...3 to modify the set point value If no key is pressed within 5 seconds the interface will go back to the main screen To set the level lower limit the button 3 can be pressed Then use the button 2 and 3...

Страница 22: ...cket within 20 seconds 8 Wait until the sensor flashes and changes color 9 Reinstall probe on sensor box 1 Press button 2 2 Using up down keys set the alarm to 95 3 Wait 5 seconds for the reading to b...

Страница 23: ...e in your application turn the unit ON and perform a function test To do so 1 Turn switch to ON position 2 LOOK Is the unit level stable and that nothing is obstructing the extraction path Is there ad...

Страница 24: ...Water Level Control Box see Section 11 2 Pre Use Checklist Every 1 Month or Specific Cleaning Cycle Exchange Water 1 Remove the water using the drain outlet considering 2 Drained material should be k...

Страница 25: ...he static pressure directly upstream of the inlet of the Typhoon Central Dust Collector from the static pressure directly downstream of the exhaust plenum between the Typhoon Central Dust Collector an...

Страница 26: ...26 12 4 Troubleshooting Procedure...

Страница 27: ...maintenance on unit including filter inspection The input power to this unit is high voltage and touching any live electrical parts can cause fatal shocks or severe burns Do not touch live electrical...

Страница 28: ...bicolor LED D rapidly flashes green 5 Releases the button The bicolor LED continues to flash green 6 Within 30s insert an object into position 1 then push and release the setup button The bicolor LED...

Страница 29: ...29 NOTES...

Страница 30: ...are integrated with any products equipment units connections and or systems of a third party Third Party Products we hereby expressly exclude all of the following warranties express or implied namely...

Страница 31: ...Order is for a customized product including without limitation any custom engineered product and b an event set forth at Section 5 2 hereof occurs you will be responsible for payment of the entire amo...

Страница 32: ...An Absolent Group Company 1200 55th Avenue Montreal Quebec H8T 3J8 Email info diversitech ca For full product support visit our website https bit ly 2P6CGBX Scan above on mobile...

Отзывы: