The mode is used to suppress
false
reflections
caused by the reflection of
the ultrasonic signal from unevenness
on the tank walls, various partitions,
stirrers or other obstacles. After start
-
ing this mode, the sensor detects false
reflections and stores them in memory.
After that, these false reflections will
not affect the subsequent measure
-
ment (they are masked).
Before starting the mode, it is neces
-
sary to drain the tank as much as pos
-
sible (preferably completely).
In the case of installed stirrers, it is nec-
essary to move the stirrers to a position
below the level meter (direct the stirrer
blade into the ultrasonic signal beam).
Note: If significant obstacles occur in
the upper half of the tank, multiple
false reflections may occur, especially
in closed tanks. In such cases, it is nec
-
essary to drain the level in the tank as
low as possible so that these possible
multiple false reflections are properly
masked.
1/2 volume
barrier
tolerance field for
entering "DISTANCE
TO LEVEL"
dis
ta
nc
e to
th
e s
ur
fac
e
Obr. 17: Water level for entering a value „Set
level distance"
Start teaching in the level meter
A more detailed description is given in the instruction manual for each level meter. The indication
of teaching that is running is shown in the DEVICE INFO menu in the STATUS line, where the
TEACHING RUNNING text is displayed. After teaching is complete, the text changes to TEACH
-
ING ACTIVE.