LA 11MAS - LA 16MAS

1 Please Read 

Immediately

1.1 Important Information:

ATTENTION!

When operating or maintaining a heat pump, the legal requirements of the
country where the heat pump is operated apply. Depending on the
refrigerant quantity, the heat pump must be inspected for leaks at regular
intervals by a certified technician, and these inspections must be
recorded.

ATTENTION!

When transporting the heat pump, ensure that it is not tilted more than
45° (in any direction).

ATTENTION!

Before start-up, the transport fastening must be removed.

ATTENTION!

The frost line can vary according to the climatic region. The regulations
of the countries in question must be observed.

ATTENTION!

Do not restrict or block the area around the air intake or outlet.

ATTENTION!

The control line is essential for the operation of air-to-water heat pumps
for outdoor installation. The control line must be laid separately from the
mains cable. It is not permissible for the customer to extend the control
line.

ATTENTION!

Operating the heat pump at low system temperatures may cause the heat
pump to break down completely. After a prolonged power failure, the
commissioning procedure detailed above must be followed.

ATTENTION!

Before opening the device, ensure that all circuits are isolated from the
power supply.

ATTENTION!

Any work on the heat pump may only be performed by authorised and
qualified after-sales service technicians.

1.2 Intended Use

This device is only intended for use as specified by the manufac-
turer. Any other use beyond that intended by the manufacturer is
prohibited. This requires the user to abide by the relevant project
planning documents. Please refrain from tampering with or alter-
ing the device.

1.3 Legal Regulations and 

Directives

This heat pump is designed for use in a domestic environment
according to Article 1, Paragraph 2 k) of EC directive 2006/42/EC
(machinery directive) and is thus subject to the requirements of
EC directive 2006/95/EC (low-voltage directive). It is thus also in-
tended for use by non-professionals for heating shops, offices
and other similar working environments, in agricultural establish-
ments and in hotels, guest houses and similar / other residential
buildings.
The construction and design of the heat pump complies with all
relevant EU directives, DIN/VDE regulations (see CE declaration
of conformity).
When connecting the heat pump to the power supply, the rele-
vant VDE, EN and IEC standards are to be fulfilled. Any further
connection requirements stipulated by local utility companies
must also be observed.
When connecting the heating system, all applicable regulations
must also be adhered to.
Persons, especially children, who are not capable of operating
the device safely due to their physical, sensory or mental abilities
or due to their inexperience or lack of knowledge, must not oper-
ate this device without supervision or instruction by the person in
charge.
Children must be supervised to ensure that they do not play with
the device.

ATTENTION!

When operating or maintaining a heat pump, the legal requirements of the
country where the heat pump is operated apply. Depending on the
refrigerant quantity, the heat pump must be inspected for leaks at regular
intervals by a certified technician, and these inspections must be
recorded.

1.4 Energy-Efficient Use of the 

Heat Pump

With the purchase of this heat pump you are helping to protect
the environment. A prerequisite for energy-efficient operation is
the correct design of the heat source system and heating system
(radiators and circulation pump).
It is particularly important for the efficiency of a heat pump to
keep the temperature difference between heating water and heat
source as small as possible. For this reason, it is advisable to de-
sign the heat source and heating system very carefully. 

A tem-

perature difference of approx. one Kelvin increases the
power consumption by around 2.5 %.

 When designing the

heating system, it should be borne in mind that special consum-
ers such as e.g. hot water preparation should also be considered
and dimensioned for low temperatures. 

Underfloor heating

systems (panel heating)

 are optimally suited for heat pump use

on account of the low flow temperatures (30 °C to 40 °C). 
It is important to ensure that the heat exchangers are not con-
taminated during operation because this increases the tempera-
ture difference, in turn reducing the COP.
Correct adjustment of the heat pump manager is also important
for energy-efficient use of the heat pump. Further information can
be found in the heat pump manager's operating instructions.

Содержание LA 11MAS

Страница 1: ...Pump for Outdoor Installation Pompe chaleur air eau pour installation ext rieure Montage und Gebrauchsanweisung Deutsch English Fran ais Instructions d installation et d utilisation Installation and...

Страница 2: ......

Страница 3: ...E 4 6 1 Allgemein DE 4 6 2 Heizungsseitiger Anschluss DE 5 6 3 Elektrischer Anschluss DE 5 7 Inbetriebnahme DE 6 7 1 Allgemein DE 6 7 2 Vorbereitung DE 6 7 3 Vorgehensweise DE 6 8 Reinigung Pflege DE...

Страница 4: ...Wohneinrichtungen vor gesehen Bei der Konstruktion und Ausf hrung der W rmepumpe wurden alle entsprechenden EG Richtlinien DIN und VDE Vorschriften eingehalten siehe CE Konformit tserkl rung Beim elek...

Страница 5: ...mittel bertragen Mit Hilfe eines elektrisch angetriebenen Verdichters wird die auf genommene W rme durch Druckerh hung auf ein h heres Tem peraturniveau gepumpt und ber den Verfl ssiger W rmetau scher...

Страница 6: ...auchsanweisung beschrie ben 4 Transport ACHTUNG Die W rmepumpe darf beim Transport nur bis zu einer Neigung von 45 in jeder Richtung gekippt werden Der Transport zum endg ltigen Aufstellungsort sollte...

Страница 7: ...gsfreies Abtauen des Verdampfers zu erm gli chen Wartungsarbeiten m ssen problemlos durchgef hrt werden k n nen Dies ist gew hrleistet wenn nachfolgend dargestellter Ab stand eingehalten wird 1 Mindes...

Страница 8: ...ch ein Aufgefrie ren des Plattenw rmetauschers im K ltekreislauf f hren HINWEIS Der Einsatz eines berstr mventils ist nur bei Fl chenheizungen und einem max Heizwasserdurchsatz von 1 3 m h ratsam Bei...

Страница 9: ...weit zu ffnen dass sich bei der aktu ellen W rmequellentemperatur die in der nachstehenden Ta belle angegebene maximale Temperaturspreizung zwischen Heizungsvor und R cklauf ergibt Die Temperatursprei...

Страница 10: ...schlie en Danach muss mit geeigneten neutralisierenden Mitteln gr ndlich nachgesp lt werden um Besch digungen durch eventuell im System verbliebene Reinigungsmittelreste zu verhindern Die S uren sind...

Страница 11: ...7 2 8 9 8 2 6 bei A2 W35 kW 7 9 3 4 11 9 3 1 bei A7 W35 kW 9 5 3 9 14 5 3 7 bei A7 W55 kW 8 2 2 9 13 5 2 4 bei A10 W35 kW 10 4 4 2 15 5 3 9 4 3 Schall Leistungspegel nach EN 12102 Normalbetrieb abges...

Страница 12: ...Lieferer bezogene Teile und Ger te Anlagen m ngel die auf nicht vom Lieferer bezogene Teile zur ckzuf h ren sind fallen nicht unter den Garantieanspruch Bei endg ltig fehlgeschlagener Nachbesserung w...

Страница 13: ...5 6 1 General Information EN 5 6 2 Heating System Connection EN 6 6 3 Electrical Connection EN 6 7 Start UP EN 7 7 1 General Information EN 7 7 2 Preparation EN 7 7 3 Procedure EN 7 8 Maintenance Clea...

Страница 14: ...d similar other residential buildings The construction and design of the heat pump complies with all relevant EU directives DIN VDE regulations see CE declaration of conformity When connecting the hea...

Страница 15: ...m refrigerant in the evaporator The heat is pumped to a higher temperature level by increasing its pressure with the aid of an electrically driven compressor It is then transferred to the heating wate...

Страница 16: ...be the function and use of the heat pump manager 4 Transport ATTENTION When transporting the heat pump ensure that it is not tilted more than 45 in any direction Use a pallet for transporting the heat...

Страница 17: ...in wind di rection to allow unrestricted defrosting of the evaporator It must be possible to carry out maintenance work without hin drance This is ensured if the clearance displayed below is main tain...

Страница 18: ...pump NOTE The use of an overflow valve is only recommended for panel heating and a max heating water flow of 1 3 m h System faults may result if this is not observed Antifreeze Heat pump systems whic...

Страница 19: ...least one heating circuit must remain open e g bathroom The overflow valve should be opened far enough to produce the maximum temperature spread between the heating flow and re turn flow listed in th...

Страница 20: ...eat pump It is important that the system be thoroughly flushed using appro priate neutralising agents to prevent any damage from being caused by cleaning agent residue remaining in the system Acids mu...

Страница 21: ...2 W35 kW 7 9 3 4 11 9 3 1 at A7 W35 kW 9 5 3 9 14 5 3 7 at A7 W55 kW 8 2 2 9 13 5 2 4 at A10 W35 kW 10 4 4 2 15 5 3 9 4 3 Sound power level according to EN 12102 Normal operation reduced operation 5 d...

Страница 22: ...EN 10 452164 66 03 FD 9211 www dimplex de English LA 11MAS LA 16MAS...

Страница 23: ...stallation FR 5 6 1 Remarques d ordre g n ral FR 5 6 2 Branchement c t installation de chauffage FR 6 6 3 Branchements lectriques FR 6 7 Mise en service FR 7 7 1 Remarques d ordre g n ral FR 7 7 2 Pr...

Страница 24: ...ation de la pompe chaleur toutes les normes CE et prescriptions DIN et VDE concern es ont t respect es voir d claration de conformit CE Les normes VDE EN et CEI correspondantes sont respecter lors du...

Страница 25: ...ur A l aide d un compresseur commande lectrique la chaleur ab sorb e est pomp e un niveau de temp rature plus lev par augmentation de pression puis d livr e via le condenseur changeur de chaleur l eau...

Страница 26: ...tructions d utilisation li vr es avec l appareil 4 Transport ATTENTION Lors du transport l angle d inclinaison de la pompe chaleur ne doit pas d passer 45 quel que soit le sens Le transport vers l emp...

Страница 27: ...x d entretien doivent pouvoir tre effectu s sans pro bl me ce qui est le cas lorsque la distance repr sent e ci des sous est respect e 1 cartements minimaux pour un bon fonctionnement de la pompe chal...

Страница 28: ...ues du circuit r fri g rant ATTENTION L utilisation d une soupape diff rentielle est uniquement recommand e pour les chauffages par surfaces et pour un d bit d eau de chauffage max de 1 3 m h Le non r...

Страница 29: ...ains La soupape diff rentielle est ouvrir au maximum de telle sorte que pour la temp rature actuelle des sources d nergie l cart de temp rature maximal indiqu dans le tableau entre circuit d part et r...

Страница 30: ...ondenseur de la pompe chaleur Il faut ensuite soigneusement rincer l aide de produits neutrali sants ad quats afin d viter tous dommages provoqu s par d ventuels restes de produits de nettoyage dans l...

Страница 31: ...9 3 4 11 9 3 1 pour A7 W35 kW 9 5 3 9 14 5 3 7 pour A7 W55 kW 8 2 2 9 13 5 2 4 pour A10 W35 kW 10 4 4 2 15 5 3 9 4 3 Niveau de puissance sonore selon EN 12102 Fonctionnement normal Fonctionnement r du...

Страница 32: ...FR 10 452164 66 03 FD 9211 www dimplex de Fran ais LA 11MAS LA 16MAS...

Страница 33: ...2 Last Load Charge LA 11MAS LA 16MAS A VIII 3 3 Anschlussplan Circuit Diagram Sch ma lectrique LA 11MAS LA 16MAS A IX 3 4 Legende Legend L gende LA 11MAS LA 16MAS A X 4 Hydraulische Einbindungsscheme...

Страница 34: ...WV HQ FDV G LQVWDOODWLRQ VXU HPSODFHPHQW GpJDJp XIWULFKWXQJ LUHFWLRQ RI DLU IORZ 6HQV GH O DLU XIWULFKWXQJ LUHFWLRQ RI DLU IORZ 6HQV GH O DLU HGLHQVHLWH 2SHUDWLQJ VLGH Wp GH FRPPDQGH HL ZDVVHUYRUODXI...

Страница 35: ...FDV G LQVWDOODWLRQ VXU HPSODFHPHQW GpJDJp XIWULFKWXQJ LUHFWLRQ RI DLU IORZ 6HQV GH O DLU XIWULFKWXQJ LUHFWLRQ RI DLU IORZ 6HQV GH O DLU HGLHQVHLWH 2SHUDWLQJ VLGH Wp GH FRPPDQGH HL ZDVVHUYRUODXI XVJDQJ...

Страница 36: ...UXFNYHUOXVW LQ 3D 3UHVVXUH ORVV LQ 3D 3HUWH GH SUHVVLRQ HQ 3D XIWHLQWULWWVWHPSHUDWXU LQ LU LQOHW WHPSHUDWXUH LQ 7HPSpUDWXUH G HQWUpH G DLU HQ XIWHLQWULWWVWHPSHUDWXU LQ LU LQOHW WHPSHUDWXUH LQ 7HPSpUDW...

Страница 37: ...XFNYHUOXVW LQ 3D 3UHVVXUH ORVV LQ 3D 3HUWH GH SUHVVLRQ HQ 3D XIWHLQWULWWVWHPSHUDWXU LQ LU LQOHW WHPSHUDWXUH LQ 7HPSpUDWXUH G HQWUpH G DLU HQ XIWHLQWULWWVWHPSHUDWXU LQ LU LQOHW WHPSHUDWXUH LQ 7HPSpUDWX...

Страница 38: ...XU HDW VRXUFH WHPSHUDWXUH LQOHW 7HPSpUDWXUH G HQWUpH GH OD VRXUFH GH FKDOHXU DVVHUDXVWULWW DWHU RXWOHW 6RUWLH G HDX DVVHUHLQWULWW DWHU LQOHW QWUpH G HDX HL XIW DVVHU lUPHSXPSHQ VWHOOW GLH PLQLPDOH HL...

Страница 39: ...www dimplex de 452164 66 03 FD 9211 A VII Anhang Appendix Annexes LA 11MAS LA 16MAS 3 Stromlaufpl ne Circuit Diagrams Sch mas lectriques 3 1 Steuerung Control Commande LA 11MAS LA 16MAS...

Страница 40: ...A VIII 452164 66 03 FD 9211 www dimplex de Anhang Appendix Annexes LA 11MAS LA 16MAS 3 2 Last Load Charge LA 11MAS LA 16MAS...

Страница 41: ...www dimplex de 452164 66 03 FD 9211 A IX Anhang Appendix Annexes LA 11MAS LA 16MAS 3 3 Anschlussplan Circuit Diagram Sch ma lectrique LA 11MAS LA 16MAS 1 8 9 8 d 9 1 a 1 3 9 3 1...

Страница 42: ...de d part W1 Steuerleitung W rmepumpe W rmepumpenmanager Control lead heat pump manager Connecteur ligne de pompe chaleur gestionnaire de pompe chaleur X1 Klemmenleiste Lasteinspeisung Terminal strip...

Страница 43: ...Einbindungsschemen Hydraulic integration diagrams Sch mas d int gration hydrauliques 4 1 Monoenergetische Anlage mit doppelt differenzdrucklosem Verteiler Mono energy system and dual differential pres...

Страница 44: ...A 11MAS LA 16MAS 4 2 Monoenergetische Anlage mit zwei Heizkreisen und Warmwasserbereitung Mono energy system with two heating circuits and domestic hot water preparation Installation mono nerg tique a...

Страница 45: ...pompe chaleur Reihen Pufferspeicher Buffer tank connected in series Ballon tampon en s rie Warmwasserspeicher Hot water cylinder Ballon d eau chaude sanitaire E9 Flanschheizung Warmwasser Hot water f...

Страница 46: ...Typ LA 11MAS Type s LA 16MAS Type s EG Richtlinien Niederspannungsrichtlinie 2006 96 EG EMV Richtlinie 2004 108 EG Druckger terichtlinie 97 23 EG EC Directives Low voltage directive 2006 95 EC EMC di...

Страница 47: ...www dimplex de 452164 66 03 FD 9211 A XV Anhang Appendix Annexes LA 11MAS LA 16MAS...

Страница 48: ...schland GmbH Gesch ftsbereich Dimplex Am Goldenen Feld 18 D 95326 Kulmbach Irrt mer und nderungen vorbehalten Subject to alterations and errors Sous r serve d erreurs et modifications 49 0 9221 709 56...

Отзывы: