6 Mounting

6.1 General

The following connections need to be established on the heat
pump:

supply/return lines of the heating system 

condensate drain

control lead to the remote control

power supply

6.2 Heating-Side Connection

The connections on the heating side of the heat pump are pro-
vided with 1" external thread (flat sealing). When making the
connections to the heat pump, use a wrench to counterhold at
the transitions.
Before completing the heat pump connections on the heating
water side, the heating installation must be flushed in order to re-
move any impurities that may be present, as well as any residues
of sealing material, and the like. Any accumulation of deposits in
the condenser may result in a total failure of the heat pump. On
systems equipped with heating water flow shut-off devices such
as radiator or thermostat valves, an overflow valve, to be pro-
vided by the customer, needs to be installed at the outlet of the
heat pump in a heating system bypass. This assures a minimum
heating water flow through the heat pump and thus prevents any
malfunctions from occurring.
Once the installation on the heating side has been completed,
the heating system must be filled, de-aerated and pressure-
tested.
Consideration must be given to the following when filling the sys-
tem:

Untreated filling water and make-up water must be of drink-
ing water quality
(colourless, clear, free from sediments)

Filling water and make-up water must be pre-filtered (pore
size max. 5µm).

Scale formation in hot water heating systems cannot be com-
pletely avoided, but in systems with flow temperatures below
60°C the problem can be disregarded.
With medium and high-temperature heat pumps, temperatures
above 60°C can be reached.
The following standard values should therefore be adhered to
concerning the filling water and make-up water (according to VDI
2035 Sheet 1):

Heating water minimum flow rate

The  minimum  heating  water  flow  rate  through  the  heat  pump
must  be  assured  in  all  operating  states  of  the  heating  sys-
tem. This can be accomplished, for example, by installing either
a dual differential pressureless manifold or an overflow valve.
The procedure for adjusting an overflow valve is described in the
Chapter Start-Up. When the minimum flow rate is undershot
drastically, the plate steel exchanger in the refrigerating cycle
can freeze, which can lead to total loss of the heat pump.

NOTE

The use of an overflow valve is only recommended for panel heating and
a max. heating water flow of 1.3 m³/h. System faults may result if this is
not observed.

Frost Protection

On heat pumps installed in a location prone to frost, a manual
drain valve (see “Hydraulic Block Diagrams” in the Appendix)
should be provided. Properly installed appliances feature an in-
ternal frost protection feature. If the heat pump is taken out of
service or in the event of a power failure, the system must be
drained. In heat pump installations where a power failure cannot
be readily detected (e.g. holiday houses), the heating circuit must
contain a suitable antifreeze product.

6.3 Electrical Connection

The power connection of the heat pump is effected via a stand-
ard 3-core (for 1-phase units) or a 5-core (for 3-phase units) ca-
ble.
In the case of the 1-phase units, an additional 3-core cable must
be installed for the electric back-up heater.
The cable(s) has (have) to be supplied by the client; the cross-
sectional area is to be selected in accordance with the power
consumption of the heat pump (see Equipment Data in the ap-
pendix) as well as all relevant VDE (EN) and VNB regulations.
An all-pole isolating switch with at least 3 mm clearance on each
pole (e.g. utility company shut-off contactor, power contactor) as
well as a 3-pole circuit breaker (for 3-phase appliances) or a
1-pole circuit-breaker (for 1-phase appliances) with simultaneous
tripping of all external conductors (tripping current as stated in
the Equipment Data) must be provided in the electrical supply cir-
cuit of the heat pump.

optionally, an additional three-core cable is required for the
domestic hot water supply.

When connecting multiphase units the clockwise phase se-
quence of the motor electrical supply must be assured.
Phase sequence: L1, L2, L3.

ATTENTION!

Clockwise phase sequence (in the case of multiphase units) must be
ensured: Operating the compressor in the wrong sense of rotation, may
result in damage to the compressor. An incorrect phase sequence causes
the fan to operate in the wrong sense of rotation leading to a significant
reduction in performance.

The control voltage for the remote control is provided by the
power supply of the unit.
The connecting lead (control lead) from the remote control to the
heat pump (not included in the scope of delivery) must be suita-
ble for 230 V mains power supply. The lead must have (at least)
6 cores and the cross-section of the single cores must be at least
0.5 mm².
The power supply of the heat pump must be as specified in the
Technical Data of the applicance, i.e. 230 V AC 50 Hz or 3-L/N/
PE 400 V.
The connection inside the heat pump is to be effected using the
terminal strips in the control box. For detailed information refer to
the Wiring Diagrams in the Appendix.

Total heat

output in [kW]

Total alkaline earths

in mol/m³ and/or

mmol/l

Total

hardness in °dH

up to 200



2.0



11.2

200 to 600



1.5



8.4

> 600

< 0.02

< 0.11

Содержание LA 10MR

Страница 1: ...Water Heat Pump for Outdoor Installation Pompe chaleur air eau pour installation ext rieure Montage und Gebrauchsanweisung Deutsch English Fran ais Instructions d installation et d utilisation Install...

Страница 2: ......

Страница 3: ...llgemein DE 4 5 2 Kondensatleitung DE 4 6 Montage DE 5 6 1 Allgemein DE 5 6 2 Heizungsseitiger Anschluss DE 5 6 3 Elektrischer Anschluss DE 5 7 Inbetriebnahme DE 6 7 1 Allgemein DE 6 7 2 Vorbereitung...

Страница 4: ...urch Laien zur Beheizung von L den B ros und anderen hnlichen Arbeitsum gebungen von landwirtschaftlichen Betrieben und von Hotels Pensionen und hnlichen oder anderen Wohneinrichtungen vor gesehen Bei...

Страница 5: ...nergie eingesetzt um die W rme der Umwelt auf ein h heres Temperaturniveau anzuhe ben Da die der Luft entzogene Energie auf das Heizwasser bertragen wird bezeichnet man dieses Ger t als Luft Wasser W...

Страница 6: ...st Flachdach oder erh hter Kippgefahr z B exponierte Lage hohe Windlast ist eine zu s tzliche Kippsicherung vorzusehen Die Verantwortung f r die Aufstellung der W rmepumpe liegt bei der anlageerrichte...

Страница 7: ...hten kann es zu St rungen der Anlage f hren Frostschutz Bei W rmepumpen die frostgef hrdet aufgestellt sind sollte eine manuelle Entleerung siehe Anhang Hydraulische Prinzip schemen vorgesehen werden...

Страница 8: ...ntemperatur die in der nachstehenden Ta belle angegebene maximale Temperaturspreizung zwischen Heizungsvor und R cklauf ergibt Die Temperaturspreizung ist m glichst nahe an der W rmepumpe zu messen Be...

Страница 9: ...zwassers eingestellt werden 1 Schalter Ein Standby 2 Leuchtdiode gr n leuchtet unabh ngig von der Schal terstellung zeigt Betriebsbereitschaft der W rmepumpe an 3 Schalter Heizen linksseitig gedr ckt...

Страница 10: ...um gestellt Nach Beendigung der Brauchwasserbereitung wird in der glei chen Funktion weitergearbeitet wie vor der Anforderung Heizen oder K hlen 9 Reinigung Pflege 9 1 Pflege Vermeiden Sie zum Schutz...

Страница 11: ...t beheben k nnen Die W rmepumpe l uft nicht Bitte berpr fen Sie ob die Spannungsversorgung sichergestellt ist Sicherung aus gel st Stromausfall der Betriebsschalter an der Fernbedienung und die richti...

Страница 12: ...6 0 47 0 47 0 3 6 Heizwasserdurchfluss m h 1 1 1 3 1 5 1 7 1 9 3 7 Freie Pressung Heizungsumw lzpumpe max Stufe Pa 34800 35600 33800 32700 58900 3 8 K ltemittel Gesamt F llgewicht Typ kg R407C 1 5 R40...

Страница 13: ...Garan tie erstreckt sich auf das Ger t und vom Lieferer bezogene Teile Nicht vom Lieferer bezogene Teile und Ger te Anlagenm ngel die auf nicht vom Lieferer bezogene Teile zur ckzuf hren sind fallen n...

Страница 14: ...D 12 Deutsch 13...

Страница 15: ...Line EN 4 6 Mounting EN 5 6 1 General EN 5 6 2 Heating Side Connection EN 5 6 3 Electrical Connection EN 5 7 Commissioning EN 6 7 1 General EN 6 7 2 Preparatory Steps EN 6 7 3 Procedure EN 6 8 Functio...

Страница 16: ...fessionals for heating shops offices and other similar working environments in agricultural establish ments and in hotels guest houses and similar other residential buildings This heat pump was design...

Страница 17: ...mode electrical energy is used to raise the heat of the environment to a higher temperature level Due to the fact that the energy extracted from the air is transferred to the heating water this type o...

Страница 18: ...or high wind exposure additional protection against tipping over must be provided The responsibility for the heat pump installation lies with the specialist system construction company During the ins...

Страница 19: ...observed Frost Protection On heat pumps installed in a location prone to frost a manual drain valve see Hydraulic Block Diagrams in the Appendix should be provided Properly installed appliances featu...

Страница 20: ...ith the second heat generator To ensure a problem free start up the following procedure is to be implemented 1 Close all consumer circuits 2 Ensure that the heat pump has the correct water flow 3 Use...

Страница 21: ...ump switches off To prevent condensate from forming on the system in the case of surface cooling systems it is recommended that dew point mon itors be installed at critical places of the cold distribu...

Страница 22: ...om the system It is recommended that the heat exchanger be cleaned in the direction opposite to the normal flow direction Owing to their acid content flushing agents must be used with caution To preve...

Страница 23: ...atures too high or too low the air inlet or outlet areas are neither covered obstructed nor severely contaminated valves or stop cocks in the water lines heating lines are closed the water temperature...

Страница 24: ...er flow rate m h 1 1 1 3 1 5 1 7 1 9 3 7 Free pressure heating circulating pump max stage Pa 34800 35600 33800 32700 58900 3 8 Refrigerant total charge weight type kg R407C 1 5 R407C 2 3 R407C 2 7 R40...

Страница 25: ...ensation FR 4 6 Montage FR 5 6 1 G n ralit s FR 5 6 2 Raccordement c t chauffage FR 5 6 3 Raccordement lectrique FR 5 7 Mise en service FR 6 7 1 G n ralit s FR 6 7 2 Travaux pr paratoires FR 6 7 3 D m...

Страница 26: ...niti es des fins de chauf fage de boutiques bureaux et autres environnements de travail quivalents dans les entreprises agricoles et dans les h tels pensions et autres lieux r sidentiels Toutes les di...

Страница 27: ...ectrique la chaleur ab sorb e est pomp e un niveau de temp rature plus lev par augmentation de la pression puis selon le cas d utilisation d livr e l eau de chauffage ou l air vacu par le biais de l c...

Страница 28: ...le sol afin de contrecarrer une ventuelle formation de bruits de corps Si ceci n est pas possible des mesures d absorption acoustique compl mentaires seront ventuellement n cessai res L appareil est...

Страница 29: ...istributeur double sans pression diff rentielle ou d une soupape diff rentielle Vous trouverez des explications quant au r glage d une soupape diff rentielle dans le chapitre Mise en service Un d pass...

Страница 30: ...Pour r gler la soupape diff rentielle correctement nous vous conseillons de proc der de la mani re suivante Fermez tous les circuits de chauffage pouvant l tre en phase de fonctionnement selon l utili...

Страница 31: ...e chauffage en pla ant l interrupteur 3 la position chauffage La temp rature retour souhait e se r gle sur le bouton rota tif 4 la demande aff rente s effectue via le potentiom tre et elle est compris...

Страница 32: ...l installation de la mani re indiqu e ci apr s Attention les la melles de l changeur de chaleur tubes ailettes poss dent des ar tes coupantes risque de blessure par coupure 9 2 Nettoyage c t chauffag...

Страница 33: ...limentation en tension est assur e coupe circuit d clen ch perte de la tension secteur L interrupteur de service la t l commande et le mode de service appropri sont activ s et si la bonne temp rature...

Страница 34: ...0 47 0 3 6 D bit d eau de chauffage m h 1 1 1 3 1 5 1 7 1 9 3 7 Pression libre pompe de circulation de chauffage au r gime max Pa 34800 35600 33800 32700 58900 3 8 Agent r frig rant poids de remplissa...

Страница 35: ...oidissement LA 16TR A XII 3 Stromlaufpl ne Wiring diagrams Sch mas lectriques A XIII 3 1 Steuerung Control Commande LA 6MR LA 10MR A XIII 3 2 Last Load Charge LA 6MR LA 10MR A XIV 3 3 Anschlussplan Te...

Страница 36: ...ER LQVSHFWLRQ VLGH RvWH GH MRQFWLRQ pOHFWULTXH F WH UpYLVLRQ XIWDXVEODVVHLWH LU GLVFKDUJH HQG WH GH VRXIIODJH G DLU RQGHQVDWDEODXI RQGHQVDWH GUDLQ FRXOHPHQW GH O HDX GH FRQGHQVDWLRQ UXQGUDKPHQ DVH IU...

Страница 37: ...LQ N LQFO 3XPSHQOHLVWXQJVDQWHLO 3RZHU FRQVXPSWLRQ LQ N LQFO SRZHU LQSXW WR SXPS RQVRPPDWLRQ GH SXLVVDQFH HQ N FRPSULV SDUW GH FRQVRPPDWLRQ GH OD SRPSH XIWHLQWULWWVWHPSHUDWXU LQ LU LQOHW WHPSHUDWXUH LQ...

Страница 38: ...XPSHQOHLVWXQJVDQWHLO 3RZHU FRQVXPSWLRQ LQ N LQFO SRZHU LQSXW WR SXPS RQVRPPDWLRQ GH SXLVVDQFH HQ N FRPSULV SDUW GH FRQVRPPDWLRQ GH OD SRPSH XIWHLQWULWWVWHPSHUDWXU LQ LU LQOHW WHPSHUDWXUH LQ 7HPSpUDWXU...

Страница 39: ...LVWXQJVDQWHLO 3RZHU FRQVXPSWLRQ LQ N LQFO SRZHU LQSXW WR SXPS RQVRPPDWLRQ GH SXLVVDQFH HQ N FRPSULV SDUW GH FRQVRPPDWLRQ GH OD SRPSH XIWHLQWULWWVWHPSHUDWXU LQ LU LQOHW WHPSHUDWXUH LQ 7HPSpUDWXUH G HQW...

Страница 40: ...XPSHQOHLVWXQJVDQWHLO 3RZHU FRQVXPSWLRQ LQ N LQFO SRZHU LQSXW WR SXPS RQVRPPDWLRQ GH SXLVVDQFH HQ N FRPSULV SDUW GH FRQVRPPDWLRQ GH OD SRPSH XIWHLQWULWWVWHPSHUDWXU LQ LU LQOHW WHPSHUDWXUH LQ 7HPSpUDWXU...

Страница 41: ...OHLVWXQJVDQWHLO 3RZHU FRQVXPSWLRQ LQ N LQFO SRZHU LQSXW WR SXPS RQVRPPDWLRQ GH SXLVVDQFH HQ N FRPSULV SDUW GH FRQVRPPDWLRQ GH OD SRPSH XIWHLQWULWWVWHPSHUDWXU LQ LU LQOHW WHPSHUDWXUH LQ 7HPSpUDWXUH G H...

Страница 42: ...3XPSHQOHLVWXQJVDQWHLO 3RZHU FRQVXPSWLRQ LQ N LQFO SRZHU LQSXW WR SXPS RQVRPPDWLRQ GH SXLVVDQFH HQ N FRPSULV SDUW GH FRQVRPPDWLRQ GH OD SRPSH XIWHLQWULWWVWHPSHUDWXU LQ LU LQOHW WHPSHUDWXUH LQ 7HPSpUDWX...

Страница 43: ...HLVWXQJVDQWHLO 3RZHU FRQVXPSWLRQ LQ N LQFO SRZHU LQSXW WR SXPS RQVRPPDWLRQ GH SXLVVDQFH HQ N FRPSULV SDUW GH FRQVRPPDWLRQ GH OD SRPSH XIWHLQWULWWVWHPSHUDWXU LQ LU LQOHW WHPSHUDWXUH LQ 7HPSpUDWXUH G HQ...

Страница 44: ...XPSHQOHLVWXQJVDQWHLO 3RZHU FRQVXPSWLRQ LQ N LQFO SRZHU LQSXW WR SXPS RQVRPPDWLRQ GH SXLVVDQFH HQ N FRPSULV SDUW GH FRQVRPPDWLRQ GH OD SRPSH XIWHLQWULWWVWHPSHUDWXU LQ LU LQOHW WHPSHUDWXUH LQ 7HPSpUDWXU...

Страница 45: ...HLVWXQJVDQWHLO 3RZHU FRQVXPSWLRQ LQ N LQFO SRZHU LQSXW WR SXPS RQVRPPDWLRQ GH SXLVVDQFH HQ N FRPSULV SDUW GH FRQVRPPDWLRQ GH OD SRPSH XIWHLQWULWWVWHPSHUDWXU LQ LU LQOHW WHPSHUDWXUH LQ 7HPSpUDWXUH G HQ...

Страница 46: ...3XPSHQOHLVWXQJVDQWHLO 3RZHU FRQVXPSWLRQ LQ N LQFO SRZHU LQSXW WR SXPS RQVRPPDWLRQ GH SXLVVDQFH HQ N FRPSULV SDUW GH FRQVRPPDWLRQ GH OD SRPSH XIWHLQWULWWVWHPSHUDWXU LQ LU LQOHW WHPSHUDWXUH LQ 7HPSpUDW...

Страница 47: ...www dimplex de A XIII Anhang Appendix Annexes 3 1 3 Stromlaufpl ne Wiring diagrams Sch mas lectriques 3 1 Steuerung Control Commande LA 6MR LA 10MR...

Страница 48: ...A XIV Anhang Appendix Annexes 3 2 3 2 Last Load Charge LA 6MR LA 10MR...

Страница 49: ...www dimplex de A XV Anhang Appendix Annexes 3 3 3 3 Anschlussplan Terminal diagram Sch ma de branchement LA 6MR LA 10MR JH JQ H JQ MD YH JH JQ H JQ MD YH...

Страница 50: ...eater Contacteur chauffage compl mentaire K24 Relais Warmwasser Anforderung Relay call for hot water Relais demande d eau chaude M1 Verdichter Compressor Compresseur M2 Ventilator Fan Ventilateur M13...

Страница 51: ...www dimplex de A XVII Anhang Appendix Annexes 3 5 3 5 Steuerung Control Commande LA 12TR LA 16TR...

Страница 52: ...A XVIII Anhang Appendix Annexes 3 6 3 6 Last Load Charge LA 12TR LA 16TR...

Страница 53: ...www dimplex de A XIX Anhang Appendix Annexes 3 7 3 7 Anschlussplan Terminal diagram Sch ma de branchement LA 12TR LA 16TR JH JQ H JQ MD YH...

Страница 54: ...mpressor Compresseur M2 Ventilator Fan Ventilateur M13 Heizungsumw lzpumpe Heating circulating pump Pompe de circulation de chauffage N5 Taupunktw chter Dew point monitor D tecteur de point de ros e N...

Страница 55: ...w dimplex de A XXI Anhang Appendix Annexes 4 1 4 Hydraulische Prinzipschemen Hydraulic block diagrams Sch mas hydrauliques 4 1 Monoenergetische Anlage Mono energetic system Installation mono nerg tiqu...

Страница 56: ...A XXII Anhang Appendix Annexes 4 2 4 2 Monoenergetische Anlage und Warmwasserbereitung Mono energetic system and domestic hot water function Installation mono nerg tique et pr paration de l eau chaude...

Страница 57: ...ecting hose Tuyau de raccordement flexible Luft Wasser W rmepumpe Air to water heat pump Pompe chaleur air eau Pufferspeicher Buffer tank Ballon tampon Warmwasserspeicher Hot water tank Ballon d eau c...

Страница 58: ...LYHV DIIpUHQWHV 7RXWH PRGLILFDWLRQ HIIHFWXpH VXU O OHV DSSDUHLO V HQWUDvQH O DQQXODWLRQ GH OD YDOLGLWp GH FHWWH GpFODUDWLRQ H HLFKQXQJ lUPHSXPSHQ HVLJQDWLRQ HDW SXPSV pVLJQDWLRQ 3RPSHV j FKDOHXU 7 S 0...

Страница 59: ...www dimplex de A XXV Anhang Appendix Annexes 5...

Страница 60: ...schland GmbH Gesch ftsbereich Dimplex Am Goldenen Feld 18 D 95326 Kulmbach Irrt mer und nderungen vorbehalten Subject to alterations and errors Sous r serve d erreurs et modifications 49 0 9221 709 56...

Отзывы: