1 Read Immediately

1.1 Important Information

ATTENTION!

When operating or maintaining a heat pump, the legal requirements of the
country where the heat pump is operated apply. Depending on the
refrigerant quantity, the heat pump must be inspected for leaks at regular
intervals by a certified technician, and these inspections must be
recorded.

ATTENTION!

The unit is not suited for operation with a frequency converter.

ATTENTION!

During transport, the heat pump must not be tilted more than 45° (in
either direction).

ATTENTION!

The heat pump and transport pallet are only connected by the packaging
film.

ATTENTION!

The air intake and discharge openings must not be restricted nor
obstructed.

ATTENTION!

Clockwise phase sequence (in the case of multiphase units) must be
ensured: Operating the compressor in the wrong sense of rotation, may
result in damage to the compressor. An incorrect phase sequence causes
the fan to operate in the wrong sense of rotation leading to a significant
reduction in performance.

ATTENTION!

Do not use any cleaning agents containing sand, soda, acid or chloride as
these may damage the surface.

ATTENTION!

To prevent the formation of deposits (e.g. rust) in the plate heat
exchanger of the heat pump, we recommend using an appropriate
corrosion protection system

ATTENTION!

To prevent consequential damage it is imperative that the water circuit be
neutralized after cleaning using appropriate agents.

ATTENTION!

Prior to opening the unit it must be ensured that all electrical circuits are
disconnected from the power supply.

ATTENTION!

Work on the heat pump may be done only by an authorized and qualified
customer service.

1.2 Intended Use

This device is only intended for use as specified by the manufac-
turer. Any other use beyond that intended by the manufacturer is
prohibited. This requires the user to abide by the manufacturers
product information. Please refrain from tampering with or alte-
ring the device.

1.3 Legal Provisions and 

Guidelines

This heat pump is designed for use in a domestic environment
according to Article 1, Paragraph 2 k) of EC directive 2006/42/EC
(machinery directive) and is thus subject to the requirements of
EC directive 2006/95/EC (low-voltage directive). It is thus also in-
tended for use by non-professionals for heating shops, offices
and other similar working environments, in agricultural establish-
ments and in hotels, guest houses and similar / other residential
buildings.
This heat pump was designed and built in compliance with all rel-
evant EU directives, DIN and VDE regulations (see CE Declara-
tion of Conformity).
The electrical connection of the heat pump must be performed
according to and conforming with all relevant VDE, EN and IEC
standards. Beyond that, all technical connection requirements of
the local electrical utility company have to be adhered to.
On connecting the heating system, all relevant regulations have
to be heeded.
Persons, especially children, who are not capable of operating
the device safely due to their physical, sensory or mental abilities
or their inexperience or lack of knowledge, must not operate this
device without supervision or instruction by the person in charge. 
Children must be supervised to ensure that they do not play with
the device.

ATTENTION!

When operating or maintaining a heat pump, the legal requirements of the
country where the heat pump is operated apply. Depending on the
refrigerant quantity, the heat pump must be inspected for leaks at regular
intervals by a certified technician, and these inspections must be
recorded.

1.4 Energy-Efficient Use of the 

Heat Pump

By purchasing this heat pump you contribute to the protection of
the environment. A prerequisite for energy-efficient operation is
the proper design of the heat source system and the heat utiliza-
tion system.
One of the most important factors of heat pump efficiency is
keeping the temperature difference between the heating water
and the heat source as small as possible. It is therefore strongly
recommended that the design of both the heat source system
and the heat distribution system be carried out with great care. 

A

1 Kelvin (1 °C) higher temperature difference corresponds
to an increase in power consumption of approx. 2.5%.

 When

designing the heating system care must be taken that special ap-
plications such as domestic water heating are taken into consid-
eration and dimensioned for low temperature operation. Heat
pumps are optimally suited for 

underfloor heating (surface/ra-

diant heating) applications

 due to the low supply temperatures

(30 °C to 40 °C). 
During operation it is essential that the heat exchangers are not
contaminated as this would increase the temperature difference
resulting in a lower coefficient of performance.

Содержание LA 10MR

Страница 1: ...Water Heat Pump for Outdoor Installation Pompe chaleur air eau pour installation ext rieure Montage und Gebrauchsanweisung Deutsch English Fran ais Instructions d installation et d utilisation Install...

Страница 2: ......

Страница 3: ...llgemein DE 4 5 2 Kondensatleitung DE 4 6 Montage DE 5 6 1 Allgemein DE 5 6 2 Heizungsseitiger Anschluss DE 5 6 3 Elektrischer Anschluss DE 5 7 Inbetriebnahme DE 6 7 1 Allgemein DE 6 7 2 Vorbereitung...

Страница 4: ...urch Laien zur Beheizung von L den B ros und anderen hnlichen Arbeitsum gebungen von landwirtschaftlichen Betrieben und von Hotels Pensionen und hnlichen oder anderen Wohneinrichtungen vor gesehen Bei...

Страница 5: ...nergie eingesetzt um die W rme der Umwelt auf ein h heres Temperaturniveau anzuhe ben Da die der Luft entzogene Energie auf das Heizwasser bertragen wird bezeichnet man dieses Ger t als Luft Wasser W...

Страница 6: ...st Flachdach oder erh hter Kippgefahr z B exponierte Lage hohe Windlast ist eine zu s tzliche Kippsicherung vorzusehen Die Verantwortung f r die Aufstellung der W rmepumpe liegt bei der anlageerrichte...

Страница 7: ...hten kann es zu St rungen der Anlage f hren Frostschutz Bei W rmepumpen die frostgef hrdet aufgestellt sind sollte eine manuelle Entleerung siehe Anhang Hydraulische Prinzip schemen vorgesehen werden...

Страница 8: ...ntemperatur die in der nachstehenden Ta belle angegebene maximale Temperaturspreizung zwischen Heizungsvor und R cklauf ergibt Die Temperaturspreizung ist m glichst nahe an der W rmepumpe zu messen Be...

Страница 9: ...zwassers eingestellt werden 1 Schalter Ein Standby 2 Leuchtdiode gr n leuchtet unabh ngig von der Schal terstellung zeigt Betriebsbereitschaft der W rmepumpe an 3 Schalter Heizen linksseitig gedr ckt...

Страница 10: ...um gestellt Nach Beendigung der Brauchwasserbereitung wird in der glei chen Funktion weitergearbeitet wie vor der Anforderung Heizen oder K hlen 9 Reinigung Pflege 9 1 Pflege Vermeiden Sie zum Schutz...

Страница 11: ...t beheben k nnen Die W rmepumpe l uft nicht Bitte berpr fen Sie ob die Spannungsversorgung sichergestellt ist Sicherung aus gel st Stromausfall der Betriebsschalter an der Fernbedienung und die richti...

Страница 12: ...6 0 47 0 47 0 3 6 Heizwasserdurchfluss m h 1 1 1 3 1 5 1 7 1 9 3 7 Freie Pressung Heizungsumw lzpumpe max Stufe Pa 34800 35600 33800 32700 58900 3 8 K ltemittel Gesamt F llgewicht Typ kg R407C 1 5 R40...

Страница 13: ...Garan tie erstreckt sich auf das Ger t und vom Lieferer bezogene Teile Nicht vom Lieferer bezogene Teile und Ger te Anlagenm ngel die auf nicht vom Lieferer bezogene Teile zur ckzuf hren sind fallen n...

Страница 14: ...D 12 Deutsch 13...

Страница 15: ...Line EN 4 6 Mounting EN 5 6 1 General EN 5 6 2 Heating Side Connection EN 5 6 3 Electrical Connection EN 5 7 Commissioning EN 6 7 1 General EN 6 7 2 Preparatory Steps EN 6 7 3 Procedure EN 6 8 Functio...

Страница 16: ...fessionals for heating shops offices and other similar working environments in agricultural establish ments and in hotels guest houses and similar other residential buildings This heat pump was design...

Страница 17: ...mode electrical energy is used to raise the heat of the environment to a higher temperature level Due to the fact that the energy extracted from the air is transferred to the heating water this type o...

Страница 18: ...or high wind exposure additional protection against tipping over must be provided The responsibility for the heat pump installation lies with the specialist system construction company During the ins...

Страница 19: ...observed Frost Protection On heat pumps installed in a location prone to frost a manual drain valve see Hydraulic Block Diagrams in the Appendix should be provided Properly installed appliances featu...

Страница 20: ...ith the second heat generator To ensure a problem free start up the following procedure is to be implemented 1 Close all consumer circuits 2 Ensure that the heat pump has the correct water flow 3 Use...

Страница 21: ...ump switches off To prevent condensate from forming on the system in the case of surface cooling systems it is recommended that dew point mon itors be installed at critical places of the cold distribu...

Страница 22: ...om the system It is recommended that the heat exchanger be cleaned in the direction opposite to the normal flow direction Owing to their acid content flushing agents must be used with caution To preve...

Страница 23: ...atures too high or too low the air inlet or outlet areas are neither covered obstructed nor severely contaminated valves or stop cocks in the water lines heating lines are closed the water temperature...

Страница 24: ...er flow rate m h 1 1 1 3 1 5 1 7 1 9 3 7 Free pressure heating circulating pump max stage Pa 34800 35600 33800 32700 58900 3 8 Refrigerant total charge weight type kg R407C 1 5 R407C 2 3 R407C 2 7 R40...

Страница 25: ...ensation FR 4 6 Montage FR 5 6 1 G n ralit s FR 5 6 2 Raccordement c t chauffage FR 5 6 3 Raccordement lectrique FR 5 7 Mise en service FR 6 7 1 G n ralit s FR 6 7 2 Travaux pr paratoires FR 6 7 3 D m...

Страница 26: ...niti es des fins de chauf fage de boutiques bureaux et autres environnements de travail quivalents dans les entreprises agricoles et dans les h tels pensions et autres lieux r sidentiels Toutes les di...

Страница 27: ...ectrique la chaleur ab sorb e est pomp e un niveau de temp rature plus lev par augmentation de la pression puis selon le cas d utilisation d livr e l eau de chauffage ou l air vacu par le biais de l c...

Страница 28: ...le sol afin de contrecarrer une ventuelle formation de bruits de corps Si ceci n est pas possible des mesures d absorption acoustique compl mentaires seront ventuellement n cessai res L appareil est...

Страница 29: ...istributeur double sans pression diff rentielle ou d une soupape diff rentielle Vous trouverez des explications quant au r glage d une soupape diff rentielle dans le chapitre Mise en service Un d pass...

Страница 30: ...Pour r gler la soupape diff rentielle correctement nous vous conseillons de proc der de la mani re suivante Fermez tous les circuits de chauffage pouvant l tre en phase de fonctionnement selon l utili...

Страница 31: ...e chauffage en pla ant l interrupteur 3 la position chauffage La temp rature retour souhait e se r gle sur le bouton rota tif 4 la demande aff rente s effectue via le potentiom tre et elle est compris...

Страница 32: ...l installation de la mani re indiqu e ci apr s Attention les la melles de l changeur de chaleur tubes ailettes poss dent des ar tes coupantes risque de blessure par coupure 9 2 Nettoyage c t chauffag...

Страница 33: ...limentation en tension est assur e coupe circuit d clen ch perte de la tension secteur L interrupteur de service la t l commande et le mode de service appropri sont activ s et si la bonne temp rature...

Страница 34: ...0 47 0 3 6 D bit d eau de chauffage m h 1 1 1 3 1 5 1 7 1 9 3 7 Pression libre pompe de circulation de chauffage au r gime max Pa 34800 35600 33800 32700 58900 3 8 Agent r frig rant poids de remplissa...

Страница 35: ...oidissement LA 16TR A XII 3 Stromlaufpl ne Wiring diagrams Sch mas lectriques A XIII 3 1 Steuerung Control Commande LA 6MR LA 10MR A XIII 3 2 Last Load Charge LA 6MR LA 10MR A XIV 3 3 Anschlussplan Te...

Страница 36: ...ER LQVSHFWLRQ VLGH RvWH GH MRQFWLRQ pOHFWULTXH F WH UpYLVLRQ XIWDXVEODVVHLWH LU GLVFKDUJH HQG WH GH VRXIIODJH G DLU RQGHQVDWDEODXI RQGHQVDWH GUDLQ FRXOHPHQW GH O HDX GH FRQGHQVDWLRQ UXQGUDKPHQ DVH IU...

Страница 37: ...LQ N LQFO 3XPSHQOHLVWXQJVDQWHLO 3RZHU FRQVXPSWLRQ LQ N LQFO SRZHU LQSXW WR SXPS RQVRPPDWLRQ GH SXLVVDQFH HQ N FRPSULV SDUW GH FRQVRPPDWLRQ GH OD SRPSH XIWHLQWULWWVWHPSHUDWXU LQ LU LQOHW WHPSHUDWXUH LQ...

Страница 38: ...XPSHQOHLVWXQJVDQWHLO 3RZHU FRQVXPSWLRQ LQ N LQFO SRZHU LQSXW WR SXPS RQVRPPDWLRQ GH SXLVVDQFH HQ N FRPSULV SDUW GH FRQVRPPDWLRQ GH OD SRPSH XIWHLQWULWWVWHPSHUDWXU LQ LU LQOHW WHPSHUDWXUH LQ 7HPSpUDWXU...

Страница 39: ...LVWXQJVDQWHLO 3RZHU FRQVXPSWLRQ LQ N LQFO SRZHU LQSXW WR SXPS RQVRPPDWLRQ GH SXLVVDQFH HQ N FRPSULV SDUW GH FRQVRPPDWLRQ GH OD SRPSH XIWHLQWULWWVWHPSHUDWXU LQ LU LQOHW WHPSHUDWXUH LQ 7HPSpUDWXUH G HQW...

Страница 40: ...XPSHQOHLVWXQJVDQWHLO 3RZHU FRQVXPSWLRQ LQ N LQFO SRZHU LQSXW WR SXPS RQVRPPDWLRQ GH SXLVVDQFH HQ N FRPSULV SDUW GH FRQVRPPDWLRQ GH OD SRPSH XIWHLQWULWWVWHPSHUDWXU LQ LU LQOHW WHPSHUDWXUH LQ 7HPSpUDWXU...

Страница 41: ...OHLVWXQJVDQWHLO 3RZHU FRQVXPSWLRQ LQ N LQFO SRZHU LQSXW WR SXPS RQVRPPDWLRQ GH SXLVVDQFH HQ N FRPSULV SDUW GH FRQVRPPDWLRQ GH OD SRPSH XIWHLQWULWWVWHPSHUDWXU LQ LU LQOHW WHPSHUDWXUH LQ 7HPSpUDWXUH G H...

Страница 42: ...3XPSHQOHLVWXQJVDQWHLO 3RZHU FRQVXPSWLRQ LQ N LQFO SRZHU LQSXW WR SXPS RQVRPPDWLRQ GH SXLVVDQFH HQ N FRPSULV SDUW GH FRQVRPPDWLRQ GH OD SRPSH XIWHLQWULWWVWHPSHUDWXU LQ LU LQOHW WHPSHUDWXUH LQ 7HPSpUDWX...

Страница 43: ...HLVWXQJVDQWHLO 3RZHU FRQVXPSWLRQ LQ N LQFO SRZHU LQSXW WR SXPS RQVRPPDWLRQ GH SXLVVDQFH HQ N FRPSULV SDUW GH FRQVRPPDWLRQ GH OD SRPSH XIWHLQWULWWVWHPSHUDWXU LQ LU LQOHW WHPSHUDWXUH LQ 7HPSpUDWXUH G HQ...

Страница 44: ...XPSHQOHLVWXQJVDQWHLO 3RZHU FRQVXPSWLRQ LQ N LQFO SRZHU LQSXW WR SXPS RQVRPPDWLRQ GH SXLVVDQFH HQ N FRPSULV SDUW GH FRQVRPPDWLRQ GH OD SRPSH XIWHLQWULWWVWHPSHUDWXU LQ LU LQOHW WHPSHUDWXUH LQ 7HPSpUDWXU...

Страница 45: ...HLVWXQJVDQWHLO 3RZHU FRQVXPSWLRQ LQ N LQFO SRZHU LQSXW WR SXPS RQVRPPDWLRQ GH SXLVVDQFH HQ N FRPSULV SDUW GH FRQVRPPDWLRQ GH OD SRPSH XIWHLQWULWWVWHPSHUDWXU LQ LU LQOHW WHPSHUDWXUH LQ 7HPSpUDWXUH G HQ...

Страница 46: ...3XPSHQOHLVWXQJVDQWHLO 3RZHU FRQVXPSWLRQ LQ N LQFO SRZHU LQSXW WR SXPS RQVRPPDWLRQ GH SXLVVDQFH HQ N FRPSULV SDUW GH FRQVRPPDWLRQ GH OD SRPSH XIWHLQWULWWVWHPSHUDWXU LQ LU LQOHW WHPSHUDWXUH LQ 7HPSpUDW...

Страница 47: ...www dimplex de A XIII Anhang Appendix Annexes 3 1 3 Stromlaufpl ne Wiring diagrams Sch mas lectriques 3 1 Steuerung Control Commande LA 6MR LA 10MR...

Страница 48: ...A XIV Anhang Appendix Annexes 3 2 3 2 Last Load Charge LA 6MR LA 10MR...

Страница 49: ...www dimplex de A XV Anhang Appendix Annexes 3 3 3 3 Anschlussplan Terminal diagram Sch ma de branchement LA 6MR LA 10MR JH JQ H JQ MD YH JH JQ H JQ MD YH...

Страница 50: ...eater Contacteur chauffage compl mentaire K24 Relais Warmwasser Anforderung Relay call for hot water Relais demande d eau chaude M1 Verdichter Compressor Compresseur M2 Ventilator Fan Ventilateur M13...

Страница 51: ...www dimplex de A XVII Anhang Appendix Annexes 3 5 3 5 Steuerung Control Commande LA 12TR LA 16TR...

Страница 52: ...A XVIII Anhang Appendix Annexes 3 6 3 6 Last Load Charge LA 12TR LA 16TR...

Страница 53: ...www dimplex de A XIX Anhang Appendix Annexes 3 7 3 7 Anschlussplan Terminal diagram Sch ma de branchement LA 12TR LA 16TR JH JQ H JQ MD YH...

Страница 54: ...mpressor Compresseur M2 Ventilator Fan Ventilateur M13 Heizungsumw lzpumpe Heating circulating pump Pompe de circulation de chauffage N5 Taupunktw chter Dew point monitor D tecteur de point de ros e N...

Страница 55: ...w dimplex de A XXI Anhang Appendix Annexes 4 1 4 Hydraulische Prinzipschemen Hydraulic block diagrams Sch mas hydrauliques 4 1 Monoenergetische Anlage Mono energetic system Installation mono nerg tiqu...

Страница 56: ...A XXII Anhang Appendix Annexes 4 2 4 2 Monoenergetische Anlage und Warmwasserbereitung Mono energetic system and domestic hot water function Installation mono nerg tique et pr paration de l eau chaude...

Страница 57: ...ecting hose Tuyau de raccordement flexible Luft Wasser W rmepumpe Air to water heat pump Pompe chaleur air eau Pufferspeicher Buffer tank Ballon tampon Warmwasserspeicher Hot water tank Ballon d eau c...

Страница 58: ...LYHV DIIpUHQWHV 7RXWH PRGLILFDWLRQ HIIHFWXpH VXU O OHV DSSDUHLO V HQWUDvQH O DQQXODWLRQ GH OD YDOLGLWp GH FHWWH GpFODUDWLRQ H HLFKQXQJ lUPHSXPSHQ HVLJQDWLRQ HDW SXPSV pVLJQDWLRQ 3RPSHV j FKDOHXU 7 S 0...

Страница 59: ...www dimplex de A XXV Anhang Appendix Annexes 5...

Страница 60: ...schland GmbH Gesch ftsbereich Dimplex Am Goldenen Feld 18 D 95326 Kulmbach Irrt mer und nderungen vorbehalten Subject to alterations and errors Sous r serve d erreurs et modifications 49 0 9221 709 56...

Отзывы: