EN-2

English

1

1 Please read 

immediately

1.1 Important information

ATTENTION!

The device is not suitable for operation with a frequency converter.

ATTENTION!

Never use cleaning agents containing sand, soda, acid or chloride, as
these can damage the surfaces.

ATTENTION!

Before opening the device, ensure that all circuits are powered down.

ATTENTION!

The hydro tower is to be fixed to the transport pallet with screws.

ATTENTION!

Work on the system must only be performed by authorised and qualified
after-sales service technicians.

The operational reliability of the safety valve should be checked
at regular intervals. We recommend having an annual service in-
spection carried out by a qualified specialist company.
The outflow from the safety valve should visibly flow into a waste
water drain.
The installer of the heating system is responsible for checking
whether an additional expansion vessel is required.
Operating the system in a sensible way can provide significant
energy savings. The heating water temperature should be as low
as required during heat pump operation. The planner of the heat-
ing system is responsible for determining the system tempera-
ture.
When installing an underfloor heating system, a sensible value
for the maximum flow and return temperature should be set on
the heat pump controller. The position of the temperature sensor
is important in this regard.

1.2 Legal regulations and 

guidelines

This heat pump is designed for use in a domestic environment
according to Article 1, Paragraph 2 k) of EC directive 2006/42/EC
(machinery directive) and is thus subject to the requirements of
EC directive 2006/95/EC (low-voltage directive). It is thus also in-
tended for use by non-professionals for heating shops, offices
and other similar working environments, in agricultural establish-
ments and in hotels, guest houses and similar / other residential
buildings.
The construction and design of the hydro tower complies with all
relevant EU directives, DIN and VDE regulations (see CE de-
claration of conformity).
When connecting the hydro tower to the power supply, the rele-
vant VDE, EN and IEC standards must be fulfilled. Any further
connection requirements stipulated by the mains supply network
operator must also be observed.
When connecting the heating system, all applicable regulations
must also be adhered to.

Persons, especially children, who are not capable of operating
the device safely due to their physical, sensory or mental abilities
or due to their inexperience or lack of knowledge, must not oper-
ate this device without supervision or instruction by the person in
charge.
Children must be supervised to ensure that they do not play with
the device.

2 Purpose of the hydro 

tower

2.1 Application

The hydro tower constitutes the interface between a non-revers-
ible heat pump and the heating system in the building. The hydro
tower contains all hydraulic components required between heat
generation and heat distribution with an unmixed heating circuit.
A dual differential pressureless manifold with a buffer tank allows
an energetically optimised hydraulic integration of the heat gen-
erator and the heat consumers.

ATTENTION!

The device is not suitable for operation with a frequency converter.

2.2 General properties

„

Low installation effort

„

All components easily accessible

„

Ready-to-connect, contains all essential components, i.e.
pumps, shut-offs, safety devices and heat pump manager
(HWK 332 Econ)

„

Integrated 300l hot water cylinder

„

Integrated buffer tank reduces operating cycles of the heat
pump, thus increasing the efficiency of the system

„

The infinitely adjustable operation of the circulating pump in
the heating circuit allows the output to be adjusted according
to need.

„

Optional immersion heater up to 6 kW

„

Switchable pipe heater (2 / 4 / 6 kW) for supplementary heat-
ing.

3 Scope of supply

3.1 Basic device

Hydraulic components

„

Dual differential pressureless manifold

„

Buffer tank, 100 litres

„

Unmixed heating circuit including controlled circulating
pump (infinitely adjustable or 3 stages), shut-offs and back-
pressure features

„

Primary circuit heat generation including circulating pump (3
stages), shut-offs 

„

2nd heat generator, electrical pipe heater, heat output 2 / 4 /
6 kW, secured via safety temperature limiter

„

300 litre hot water cylinder

Содержание HWK 332

Страница 1: ...HPM Tour hydraulique combin e avec gestionnaire de PAC Tour hydraulique combin e sans gestionnaire de PAC Montage und Gebrauchsanweisung Deutsch English Fran ais Instructions d installation et d utili...

Страница 2: ......

Страница 3: ...rmepumpenmanager DE 3 4 Transport DE 3 5 Aufstellung DE 3 5 1 Allgemein DE 3 5 2 Schall DE 3 6 Montage DE 4 6 1 Allgemein DE 4 6 2 Heizungsseitiger Anschluss DE 4 6 3 Elektrischer Anschluss DE 4 7 Inb...

Страница 4: ...chluss des Hydro Towers sind die ent sprechenden VDE EN und IEC Normen einzuhalten Au er dem m ssen die Anschlussbedingungen der Versorgungsnetz betreiber beachtet werden Beim Anschlie en der Heizungs...

Страница 5: ...sport zum endg ltigen Aufstellungsort sollte mit Holz rost erfolgen Das Grundger t bietet einerseits die Transport m glichkeit mit Hubwagen Sackkarre o ACHTUNG Hydro Tower und Transportpalette sind mi...

Страница 6: ...bsbereit sind arbeitet die Frost schutzfunktion des Reglers Bei Au erbetriebnahme der W rme pumpe oder Stromausfall ist die Anlage zu entleeren Bei W r mepumpenanlagen an denen ein Stromausfall nicht...

Страница 7: ...ssigkeit Raumtempera tur haben Es ist empfehlenswert den W rmeaustauscher ent gegen der normalen Durchflussrichtung zu sp len Um zu verhindern dass s urehaltiges Reinigungsmittel in den Heizungsanlag...

Страница 8: ...Beachten Sie dass der Platzbedarf f r Rohranschluss Bedienung und Wartung gr er ist 1920 x 740 x 950 1920 x 740 x 950 4 2 Kippma mm 2000 2000 4 3 Ger teanschl sse f r W rmeerzeuger Zoll 1 1 4 AG FL 1...

Страница 9: ...p manager EN 3 4 Transport EN 3 5 Installation EN 3 5 1 General EN 3 5 2 Sound EN 3 6 Assembly EN 4 6 1 General EN 4 6 2 Heating system connection EN 4 6 3 Electrical connection EN 4 7 Start up EN 5 7...

Страница 10: ...cting the hydro tower to the power supply the rele vant VDE EN and IEC standards must be fulfilled Any further connection requirements stipulated by the mains supply network operator must also be obse...

Страница 11: ...its final installation location The basic device can be transported with a lift truck a pushcart or similar ATTENTION The hydro tower is to be fixed to the transport pallet with screws 5 Installation...

Страница 12: ...heat pumps which are exposed to frost The frost protection function of the heat pump controller is active whenever the controller and the heat circulating pump are ready for operation The system has t...

Страница 13: ...acid solution for cleaning purposes However if cleaning needs to be performed more frequently a 5 formic acid solu tion should be used In either case the cleaning fluid should be at room temperature W...

Страница 14: ...operation and maintenance 1920 x 740 x 950 1920 x 740 x 950 4 2 Tilting dimension mm 2000 2000 4 3 Device connections for heat generator inches 1 1 4 external thread flange 1 1 4 external thread flang...

Страница 15: ...pe chaleur FR 3 4 Transport FR 3 5 Installation FR 3 5 1 G n ralit s FR 3 5 2 Bruit FR 4 6 Montage FR 4 6 1 G n ralit s FR 4 6 2 Raccordement c t chauffage FR 4 6 3 Branchements lectriques FR 5 7 Mise...

Страница 16: ...s et autres lieux r sidentiels Lors de la construction et de la r alisation de la tour hydraulique combin e toutes les normes CE et prescriptions DIN et VDE concern es ont t respect es voir d claratio...

Страница 17: ...t de r gulation lectronique facile utiliser Il commande et surveille l ensemble de l installation de chauffage en fonction de la temp rature ext rieure la production d eau chaude sanitaire et les disp...

Страница 18: ...effectuer les raccordements c t chauffage il convient de rincer l installation de chauffage pour liminer les impuret s restes de mat riau d tanch it ventuellement pr sents ou autres Une accumulation...

Страница 19: ...i re doit tre effectu e par un service apr s vente agr par le construc teur Le respect de cette clause permet une prorogation de la ga rantie sous certaines conditions voir Garantie 7 2 Pr paratifs Av...

Страница 20: ...le raccord PE de la languette d embo tement de l anode anticorrosion 2 brancher l amp rem tre 0 0 50mA entre le raccord PE et la languette d embo tement 3 valuation du degr d usure de l anode anticorr...

Страница 21: ...ordement des tuyaux la commande et l entretien 1920 x 740 x 950 1920 x 740 x 950 4 2 Hauteur appareil bascul mm 2000 2000 4 3 Raccordements du g n rateur de chaleur pouce s 1 1 4 filet ext joint plat...

Страница 22: ...FR 8 Fran ais 11...

Страница 23: ...lan Circuit diagram Sch ma lectrique HWK 332 Econ A VIII 3 6 Legende Legend L gende HWK 332 Econ A IX 3 7 Steuerung Control Commande HWK 332 A XI 3 8 Last Load Charge HWK 332 A XII 3 9 Anschlussplan C...

Страница 24: ...SHU F OLQGHU FRYHU OHFWULF KHDWLQJ HOHPHQW N 5HWXUQ WR WKH KHDW SXPS H WHUQDO WKUHDG IODW VHDOLQJ ORZ IURP WKH KHDW SXPS H WHUQDO WKUHDG IODW VHDOLQJ LQWHUQDO WKUHDG RU RSWLRQDO LPPHUVLRQ KHDWHU FRQQH...

Страница 25: ...Z UDWH LQ P K pELW G HDX GH FKDXIIDJH HQ P K XUFKIOXVV LQ P K ORZ UDWH LQ P K pELW HQ P K XUFKIOXVV LQ P K ORZ UDWH LQ P K pELW HQ P K HL NUHLV KHDWLQJ FLUFXLW FLUFXLW GH FKDXIIDJH 6WXIH HYHO 1LYHDX 6...

Страница 26: ...iagrams Sch mas lectriques 3 1 Steuerung Control Commande HWK 332 Econ 9 9 12 12 12 5 7 5 7 1 1 95 9 WHUP 9 1 1 12 12 12 12 1 12 12 12 12 1 12 1 12 1 1 5 G 1 1 5 5 1 1 1 1 1 3 5 7 7 DDDD EEEE FFFF GGG...

Страница 27: ...A V Anhang Appendix Annexes 3 2 3 2 Steuerung Control Commande HWK 332 Econ 1 1 5 1 1 5 1 12 1 12 1 12 12 12 1...

Страница 28: ...A VI Anhang Appendix Annexes 3 3 3 3 Last Load Charge HWK 332 Econ 7 67 75 7 67 75 7 67 75 1 3 9 1 3 1 3 9 1 3...

Страница 29: ...Sch ma lectrique HWK 332 Econ 9 9 12 12 12 5 7 5 7 1 1 95 9 WHUP 9 1 1 12 12 12 12 1 12 12 12 12 1 12 1 12 1 1 7 7 5 G 5 G 1 1 5 5 1 1 1 1 1 3 1 3 9 3 5 7 7 DDDD EEEE FFFF GGG HHH IIII JJJ 1 5 G 5 1 1...

Страница 30: ...A VIII Anhang Appendix Annexes 3 5 3 5 Anschlussplan Circuit diagram Sch ma lectrique HWK 332 Econ 1 1 1 12 1 12 1 12 12 12 5 G 1 G 5 5 1 1 1 5 0 3 1 0 3 1 3 9 0 1 7 7 7 1 1 W 1 7 1...

Страница 31: ...rfernanzeige Remote fault indicator lamp Voyant de t l d tection de pannes J1 Spannungsversorgung N1 Voltage supply N1 Alimentation en tension N1 J2 3 Analogeing nge Analogue inputs Entr es analogiqu...

Страница 32: ...rbindungsleitung Manager W rmepumpe 25 V AC Connecting cable plug Heat pump manager 25 V AC Connecteur c ble de raccordement gestionnaire pompe chaleur 25 V AC X13 2 Stecker Verbindungsleitung Manager...

Страница 33: ...A XI Anhang Appendix Annexes 3 7 3 7 Steuerung Control Commande HWK 332 0 0 0 0 0 0 G 5 5 G 5 5 1 1 3 3 3 3 3...

Страница 34: ...A XII Anhang Appendix Annexes 3 8 3 8 Last Load Charge HWK 332 7 67 75 7 67 75 7 67 75 1 3 9 1 3 1 3 9 1 3...

Страница 35: ...A XIII Anhang Appendix Annexes 3 9 3 9 Anschlussplan Circuit diagram Sch ma lectrique HWK 332 0 0 0 0 0 0 G 5 5 G 5 5 1 1 3 1 3 3 3 3...

Страница 36: ...tstemperaturbegrenzer E9 Safety temperature limiter E9 Limiteur de temp rature de s curit E9 K20 Sch tz E10 11 Contactor E10 11 Contacteur E10 11 K20 2 Sch tz E10 12 Contactor E10 12 Contacteur E10 12...

Страница 37: ...ische W rmepumpenheizungsanlage f r einen Heizkreis Puffer und Warmwasserspeicher Mono energy heat pump heating system for one heating circuit buffer tank and hot water cylinder Installation de chauff...

Страница 38: ...meverbraucher Heat consumer Consommateur de chaleur Temperaturf hler Temperature sensor Sonde de temp rature R ckschlagklappe Check valve Clapet anit retour W rmepumpe Heat pump Pompe chaleur Hydro To...

Страница 39: ...A XVII Anhang Appendix Annexes 4 2...

Страница 40: ...sales service addres ses please refer to the Installation and Operating Instructions for Heat Pumps Pour les conditions de garantie et les adresses SAV se r f rer aux instructions de montage et d tili...

Отзывы: