OPU-1
UNIVERSAL POWER-LINE CARRIER SYSTEM TYPE OPU-1
GENERAL DESCRIPTION - Rev 7 (May 2019)
28/67
2.5.2
Teleprotection terminals
There are several teleprotection terminals, based on the use of digital signal processing.
2.5.2.1
Teleprotection terminal using single tone
The analog teleprotection terminal using single tone is able to transmit and receive in a
4 kHz analog band up to three independent commands and in any combination or up to
four commands according to a certain logic.
Teleprotection system type ABIT-CDIT
The terminal can be constituted by either one or two different modules according to the
number of commands. For one or two commands, ABIT.01 module (commands A and B) is
only necessary. For three or four commands, in addition to the previous one, CDIT.01
module (commands C and D) is also necessary.
ABIT.01
This module contains the Digital Signal Processor (DSP), which
generates the guard and command tones and implements a bank of
filters for the reception of commands.
It also has the software necessary for decision making in the
transmission and reception of commands, as well as software for
input/output management, link supervision and the carrying out of tests.
It contains two command input and output circuits together with five
relays for signalling and/or alarm, configurable by the user.
CDIT.01
This module contains two command input and output circuits together
with four relays for signalling and/or alarm, configurable by the user.
Teleprotection system type TPPU
The terminal is constituted by a single module.
TPPU.00
This module contains the Digital Signal Processor (DSP), which
generates the guard and command tones and implements a bank of
filters for the reception of commands.