3–14
Site Preparation and Maintenance
3.5.2
10BaseT Ethernet Connection
The 10BaseT Ethernet installation must conform to the following configuration
rules:
•
The twisted-pair cable must not exceed the maximum distance listed in
Table 3-3.
•
No other signal should be used in the same cable sheath. For example, voice
and data signals cannot be run within the same sheath.
•
Unshielded twisted-pair cable must remain at least 30.48 cm (12 in) from any
type of high-voltage power device or electrical noise source.
3.5.3
ThinWire Ethernet Connection
The ThinWire cable segment must conform to the following configuration rules:
•
The maximum cable segment length must not exceed 185 m (606 ft).
•
There must be a 50-ohm terminator at each end of the cable segment, unless
the cable ends in a DEMPR or DESPR. Both these devices have built in
50-ohm terminators.
•
There must be only one ground per cable segment.
•
There must be at least 0.5 m (19 in) between T-connectors.
•
The maximum number of stations, between terminators, must not exceed 30
stations.
•
ThinWire cable segments must not be configured in a loop.
•
ThinWire cable segments must not have any branch segments.