Chapter 6 - GP RUN Mode and Errors
GP-377 Series Users Manual
6-13
This section explains the messages that appear when an error has occurred in the
GP unit during RUN mode. The problem causing the error message and its
related countermeasure are explained in the table below.
After a problem has been solved, unplug the GP's power cord and then reattach it.
(Only the most recent error message will appear on the GP screen)
Error Message
Problem
Countermeasure
SYSTEM ERROR
(03 : **)
During screen data transfer, an
unrecoverable error occurred.
6.4.2 Error Message Details
SYSTEM ERROR
(*** : *** : ***)
During screen data transfer, an
unrecoverable error occurred.
6.4.2 Error Message Details
ILLEGAL ADDRESS IN
SCREEN DATA
Settings are used that overlap addresses.
Set the addresses correctly
after checking the screen data.
UNSUPPORTED TAG IN
SCREEN DATA
The GP currently in use does not support
the desired Tag.
Set the Tag correctly after
checking the screen data.
PLC NOT CONNECTED
(02 : FF) and (02 : F7)
The communication cable is not connected
correctly.
Re-connect the
communication cable correctly.
PLC's power is not turned ON.
Turn ON the PLC's power.
GP unit INITIALIZE settings (Setup I/O, PLC
Setting) are incorrect.
Check the INITIALIZE settings
and make any necessary
corrections.
The host and GP Powering up sequence
was incorrect.
Turn ON the PLC's power and
wait for 2-3 seconds, then turn
ON the GP's power.
The communication cable is not connected
properly.
Check the communication
cable and connect it correctly.
The communication cable was
disconnected while the GP was ON.
Turn the GP OFF and then ON
again.
The GP is powered OFF, then ON during
communication with PLC.
Turn the GP OFF and then ON
again.
Noise occurred in the communication cable. Check the communication
cable and connect it correctly.
This GP's station number is same as
another GP.
Check all GP station numbers,
and set them so they are all
unique.
PLC is powered OFF, then ON during
communication with GP.
Turn the GP OFF and then ON
again.
NETWORK ADDRESS
ERROR (02 : F8)
The SIO address used for this GP is
different from other GP's. (Only for the Multi-
Link connection)
Check all GP's SIO address
settings, and correct any that
are incorrect.
PLC COM. ERROR
(02 : **)
Specific PLC related error, or an error has
occurred with the PLC.
6.4.2 Error Message Details
PLC NOT RESPONDING
(02 : FE)
RECEIVE DATA ERROR
(02 : FD)
GP STATION NO.
DUPLICATION ERROR
(02 : F9)
6.4
Error Messages