Configure MODBUS Gateway parameters
Digi TransPort User Guide
565
Related CLI commands
Entity
Instance Parameter
Values
Equivalent Web Parameter
modbus n
enabled
1=enabled, 0=disabled
Enable MODBUS Gateway
modbus n
asy_add
0-255
Async Port
modbus n
op_mode
Master/Slave
Operation mode
modbus n
async_mode
RS322 or RS422
Async Mode
modbus n
duplex
0=full,
1=half
Duplex Mode
modbus n
idle_gap
0-2147483647
Idle Gap
modbus n
fix_slave_address
0-255
Fix slave address
modbus n
adj_slave_address
0-255
Adjust slave address
modbus n
ipport0
0-65535
IP Port (row 1)
modbus n
nbsocks0
0 -“currently available”
Number of sockets (row 1)
modbus n
ipmode0
0=TCP,
1=UDP
IP Mode (row 1)
modbus n
rawmode0
1=enabled, 0=disabled
Raw Mode (row 1)
modbus n
Ipport1
0-65535
IP Port (row 2)
modbus n
nbsocks1
0 -“currently available”
Number of sockets (row 2)
modbus n
ipmode1
0=TCP,
1=UDP
IP Mode (row 2)
modbus n
rawmode1
1=enabled, 0=disabled
Raw Mode (row 2)
modbus n
bcasts_on
OFF, ON
Broadcast support
.