JINDLU04 Rev G 21/04/16
If you have any doubts about the suitability
of your chimney, consult your local
dealer/stockist.
Both the chimney and flue pipe must be
accessible for cleaning and if ANY part of the
chimney cannot be reached through the
stove (with baffle removed), a soot door
must be fitted in a suitable position
.
F
LUE
D
RAUGHT
If the draught exceeds the recommended
maximum, a draught stabiliser must be fitted
so that the rate of burning can be controlled
and to prevent over firing.
If the reading is less than the recommended
minimum then the performance of the
appliance will be compromised.
The flue draught should be checked under fire
at high output.
Minimum Draught – 1.2mm Water Gauge
Maximum Draught – 2.5mm Water Gauge
R
EMOVING INTERNAL COMPONENTS
All internal components must be removed
prior to fitting the stove. This will make
handling the stove easier; allow access to
fixings and the flue outlet; as well as protect
the internal components from damage
during the installation process.
1.
To open the stove door, press on the
door lever to release it from the latch.
Swing the handle out to the right until
the mechanism engages and the door
catch is released.
N.B.
When closing the door keep the door handle
out to the right until the door is closed.
Terminal
Position
Clearances to Flue
Outlet
a
At or within
600mm of
the ridge
At least 600m above the ridge
b
Elsewhere
on a roof
(whether
pitched or
flat)
At least 2300mm horizontally
from the nearest point on the
weather surface and:
a)
At least 1000mm above
the highest point of
intersection of the
chimney and the weather
surface or
b)
At least as high as the ridge
c
Below (on a
pitched
roof) or
within
2300mm
horizontally
to an
openable
rooflight,
dormer
window or
other
opening.
At least 1000mm above the top
of the opening.
d
Within
2300mm of
an adjoining
or adjacent
building,
whether or
not beyond
the
boundary.
At least 600mm above any part
of the adjacent building within
2300mm
Table 2
- Flue terminal positions