Installation
(N.B. All dimensions are in Millimetres)
A
PPLIANCE
D
IMENSIONS
F
LUE OUTLET POSITION
The flue outlet angle and position is
determined by the orientation of the flue
collar. The outlet can be either vertical or
leant backwards by 30°. To change the angle,
rotate the flue collar by 180°. The effective
centre dimensions in millimeters are shown
below.
A
PPLIANCE
O
PENING
This stove must be fitted on a hearth or base
with adequate load-bearing capacity.
The opening into which this stove is fitted
should be constructed wholly from non-
combustible materials. The dimensions of the
opening should be
at least
those shown in the
diagram. Ensure there is a sufficient overlap
where the convection chamber flange meets
the face of the opening. If not, either the
opening should be made smaller, or a suitable
fire surround should be fitted to reduce the
opening dimensions.
This appliance will fit into a standard 16”
fireplace opening if the clay fireback is
removed.
Any non-combustible walls within 50mm of
this appliance should be at least 200mm
thick and should extend at least 300mm
above the top of the appliance and at least
1.2 metres above the hearth. Any walls more
than 50mm from the appliance may be
reduced to a thickness of 75mm. Ensure the
inter-connecting flue pipe also has adequate
clearances to combustible materials.