POWER WIRE GAUGE CALCULATOR
STEP BY STEP
WORKSPACE
COLUMN
EXAMPLE
Specify total Current load, in Amps, of all devices sharing this trunk.
4 Amps
Specify Distance (in feet) of actual Wire Run from power supply to
the most remote load.
125’
Multiply figures from above two lines.
Match final number to Table below to determine Wire Gauge
needed to provide adequate Voltage.
500
IF YOUR FIGURE EXCEEDS 680
, YOU MAY;
BREAK THE LOAD UP INTO SEPARATE WIRE
RUNS, OR
CONSULT YOUR POWER CABLE SUPPLIER
FOR THEIR RECOMMENDATION FOR YOUR
APPLICATION.
FINAL
NUMBER
WIRE
GAUGE
up to 45
22 AWG
45 to 90
18 AWG
90 to 170
16 AWG
170 to 275
14 AWG
275 to 415
12 AWG
415 to 680
10 AWG