30
84°
83°
Z
one Temperature (°F)
Zone Temperature Control
Unit Setpoint: 84° F
Cooling Deadband: 2° F
Heating Deadband: 2° F
Cooling Differential: 1° F
Heating Differential: 1° F
The cooling requirement is on above (84° F + 2° F) or 86° F and the cooling requirement is off
below (86° F - 1° F) or 85° F.
The heating requirement is on below (84° F - 2° F) or 82° F and the heating requirement is off
above (82° F + 1° F) or 83° F.
Time
82°
85°
86°
Compressor and Heating Off
Heating Required
Compressor Required for Cooling
Cooling Setpoint = Unit Se Cooling Deadband
Unit Setpoint
Cooling Setpoint - Differential
Heating Setpoint =
Unit Setpoint - Heating Deadband
Heating Se Differential
Zone Temperature
Zone Temperature
Figure 33
84°
83°
Pool Water
Temperature (°F)
Pool Water Temperature Control
Pool Water Setpoint: 85° F
Pool Differential: 1° F
Pool Stage Deadband: 2° F
The LC pool condenser is used below the pool water set point and the aux. pool heat is required
below the pool water set point minus the pool stage deadband.
Time
82°
85°
No Pool Heating Required
LC Pool Condenser Heating Only
LC Pool Condenser & Aux. Heating Required
Pool Water Setpoint - Differential
Pool Water Setpoint
Aux. Pool Heating Required -
Differential
Pool Water Setpoint - Pool Stage Deadband = Aux. Pool Heat Required
Figure 34
Desert Aire - CM3530 Manual
Содержание CM3530 Series
Страница 2: ...2 ...
Страница 5: ...5 Product Warning for the State of California Desert Aire CM3530 Manual ...
Страница 6: ...6 Desert Aire CM3530 Manual ...
Страница 12: ...12 Desert Aire CM3530 Manual ...
Страница 26: ...26 Figure 24 Figure 25 Figure 26 Desert Aire CM3530 Manual ...
Страница 42: ...42 Figure 58 Desert Aire CM3530 Manual ...