FIREPLACE INSTALLATION

Continued

Figure 29 - Blower Wiring Diagram for Thermostat-Controlled 

Models

blower Wiring Diagram

  CAUtION:  Label  all  wires  prior  to  disconnection 

when servicing controls. Wiring errors can cause im-

proper and dangerous operation. Verify proper opera-

tion after servicing.

3.  Place the blower against the lower rear wall of the firebox outer 

wrapper with the exhaust port directed upward and the thermo-

disc positioned up near the fireplace bottom. The thermodisc 

must be oriented near the fireplace bottom as shown in Figure 28 

in order to sense temperature and properly operate. The blower 

will be held in position against the back wall by the magnets 

incorporated onto the blower housing (see Figure 28).

4.  Be certain that all wire terminals are securely attached to ter-

minals on blower motor and thermal switch, and that the screw 

for the thermodisc bracket and green ground wire is tight. 

5.  Mount the speed control box against the mounting plate provided 

in the lower fireplace cavity by placing the plastic control shaft 

forward through the round hole (see Figure 26, page 15).

6.  While supporting speed control, secure control shaft with lock 

nut by pushing and turning lock nut with pliers clockwise until 

it is tight against mounting plate. Place control knob provided 

on shaft (see Figure 26, page 15).

7.  Check to make sure that the power cord is completely clear of 

the blower wheel and that there are no other foreign objects in 

blower wheel. Also double check all wire leads and make sure 

wire routing is not pinched or in a precarious position. Correct 

accordingly.

8.  Turn on power to duplex outlet if previously turned off per the 

warning in column 2, page 14.

9.  Plug in blower power cord to duplex outlet.

10.  The blower will only run when the speed control knob is in the 

ON position and the thermal switch senses temperature after the 

fireplace begins to heat up. The blower speed can be adjusted by 

rotating the control knob. To turn off, turn knob fully counterclock-

wise until it clicks off. If the blower is ON and has been running 

with the fireplace operating, the blower will continue to run for a 

short time after the fireplace has been turned off. As the thermal 

switch cools down, the blower shuts down automatically.

11.  Peel off the backing paper and stick the supplied wiring diagram 

decal on the firebox bottom approximately 12" in front of the 

blower (see Figure 27, page 15).

Thermodisc

Figure 28 - Blower Model BKT

Air Flow Direction

Route BKT Blower 

Through This Area

Magnets

Blower 

Location

Side View Firebox Bottom

Black 

Wire

Phillips 

Screw

Blue Wire

Ring Terminal 

on Green Wire

White Wire

Thermal Switch

Thermal 

Switch 

Bracket

Power Cord

Air Flow 

Direction

Magnetic 

Strips

INStALLING GAS PIPING tO FIREPLACE 
LOCAtION

 WARNING: A qualified service person must connect 

fireplace to gas supply. Follow all local codes.

  CAUtION:  For  propane/LP  units,  never  connect 

fireplace directly to the propane/LP supply. this heater 

requires  an  external  regulator  (not  supplied).  Install 

the external regulator between the fireplace and pro

-

pane/LP supply.

Installation Items Needed

Before installing fireplace, make sure you have the items listed below.
•  external regulator (supplied by installer)

•  piping (check local codes)

•  sealant (resistant to propane/LP gas)

•  equipment shutoff valve *

•  test gauge connection *

•  sediment trap

•  tee joint

•  pipe wrench

•  approved flexible gas line with gas connector (if allowed by local 

codes)

*  A CSA design-certified equipment shutoff valve with 1/8" NPT tap 

is an acceptable alternative to test gauge connection. Purchase the 

CSA design-certified equipment shutoff valve from your retailer.

Blue

Variable

Fan Switch

Fan Switch

(N.O.)

Green

White

On

110/115 

V.A.C.

Blower

Motor

Black 

Off

1

2

Black

Содержание VR32P Series

Страница 1: ...tly located manufactured mobile home where not prohibited by state or local codes Aftermarket Completion of sale not for purpose of resale from the manufacturer WARNING Iftheinformationinthismanualis...

Страница 2: ...tdoors To prevent performance problems do not use pro pane LP fuel tank of less than 100 lbs capacity 3 If you smell gas shut off gas supply do not try to light any appliance do not touch any electric...

Страница 3: ...res These are a few facts that can help you understand and enjoy your direct vent fireplace The venting system may be routed to the outside of your home in several ways It may vent through the roof ve...

Страница 4: ...18 above top of louver opening When locating termination cap it is important to observe the minimum clearances shown in Figure 7 page 6 If recessing into a wall you can avoid extra framing by position...

Страница 5: ...on Preparation Continued Figure 4 Framing Clearances for Installation Against an Exterior Wall 32 Models 36 Models A 323 8 361 8 B 345 8 411 4 C 19 231 2 C B A D E F G Top of Louver Opening 3 2 1 4 5...

Страница 6: ...ve paved side walk or a paved driveway located on public property 84 213 3 cm minimum M clearance under veranda porch deck 12 30 5 cm minimum N clearance above a roof shall extend a minimum of 24 61 c...

Страница 7: ...ons will void the warranty Installation Precautions Wear gloves and safety glasses for protection Use extreme caution when using ladders or when on roof tops Be aware of electrical wiring locations in...

Страница 8: ...re the vent will be terminated If the wall being penetrated is constructed of noncombustible material such as masonry block or concrete a 7 3 4 hole with zero clearance is acceptable see Figure 9 WARN...

Страница 9: ...e overlap should be a minimum of 11 4 9 Slide wall firestop against interior wall surface and attach with screws provided See Figure 13 for horizontal termination details 10 Place fireplace into posit...

Страница 10: ...ground to termination is possible Venting Installation instructions Continued Adjustable Pipe 12 Max Figure 14 Horizontal Termination Configuration for Square and Round Terminations 45 Elbow Wall Fir...

Страница 11: ...l Termination Wall Firestop 90 Elbow 45 Elbow Figure 16 Snorkel Termination Configurations for Below Ground Installation 12 Minimum Adequate Drainage HORIZONTAL SYSTEM INSTALLATION USING TWO 90 ELBOWS...

Страница 12: ...is an attic space or insulated area install firestop above framed hole 2 Assemble the desired lengths of pipe and elbows necessary to reach from the fireplace flue up through the firestop Be sure all...

Страница 13: ...e 22 Vertical Venting Configuration Using One 90 Elbow Vertical Round High Wind Termination Shown Note Install restrictor into inner collar of fireplace as shown Venting with Two 90 Elbows Vertical V1...

Страница 14: ...Vent Kit Galvanized Includes 45 Elbow 7 12 Adjustable Pipe Horizon tal Termination 6 Pipe 90 Elbow Wall Firestop and 18 Screws HTK Horizontal Round Termination Kit Includes Round Termination Wall Fire...

Страница 15: ...y turning knob fully counterclockwise before continuing 10 Peel off the backing paper and stick the supplied wiring diagram decal on the firebox bottom approximately 12 in front of the blower see Figu...

Страница 16: ...blower will only run when the speed control knob is in the ON position and the thermal switch senses temperature after the fireplace begins to heat up The blower speed can be adjusted by rotatingthec...

Страница 17: ...ip leg in supply line as shown in Figure 31 Locate sediment trap drip leg where it is within reach for cleaning Install in piping system between fuel supply and fireplace Locate sediment trap drip leg...

Страница 18: ...Pa 1 Close equipment shutoff valve see Figure 33 2 Pressurize supply piping system by either opening propane LP supply tank valve for propane LPgas fireplace or opening main gas valve located on or ne...

Страница 19: ...wire from TH to TPTH on control valve see Figure 37 6 Connect wires from receiver to TH and TPTH to control valve see Figure 38 7 Replace the switch bracket Figure 36 Attaching Alkaline Battery to Re...

Страница 20: ...ide 2 Lift up on latches to unlock There are two on top of firebox and two below firebox that hold glass door in place see Figure 41 3 While holding glass door to prevent it from falling and causing i...

Страница 21: ...p of grate Make sure the notches in the bottom of the log fit over the grate see Figure 44 2 Rest log 2 large front log on the pins on the front part of the grate see Figure 45 1 2 Figure 44 Installin...

Страница 22: ...derburner Placing lava rock on burner will cause performance problems 8 Pull ember material apart into pieces no larger than a dime Place these pieces loosely and sparingly directly onto the ex posed...

Страница 23: ...Follow the gas supplier s instructions C Use only your hand to push in or turn the gas control knob Never use tools If the knob will not push in or turn by hand don t try to repairit call a qualified...

Страница 24: ...w locked If the fire is on it will be turned off automatically In the locked state the light will not light up when any button is pressed To Unlock press both buttons togetheron hand held remote contr...

Страница 25: ...ontrol etc The keypad is locked in either on or off Press the POWER and LOCK buttons together to turn the unit on or off Operating optional GWMT1 Wall Mounted Thermostat WARNING Do not connect the the...

Страница 26: ...osened Check mechanical supports such as wall straps for rigidity Cleaning and Maintenance WARNING Turn off fireplace and let cool before cleaning CAUTION Youmustkeepcontrolareas burners and circulati...

Страница 27: ...Dirty or partially clogged pilot 5 Thermocouple connection loose at con trol valve 6 Thermocouple damaged 7 Control valve damaged REMEDY 1 Reconnect ignitor cable 2 Free ignitor cable if pinched by an...

Страница 28: ...from line Have gas line checked by local propane LP or natural gas company 3 Clean burner see Cleaning and Main tenance page 26 or replace burner orifice 1 Adjust the log set so that the flame does no...

Страница 29: ...d 3 Burner flame holes blocked OBSERVED PROBLEM Fireplace produces unwanted odors Fireplace shuts off in use Gas odor even when control knob is in OFF position Gas odor during combustion Dark residue...

Страница 30: ...burners will have delayed ignition fireplace will not produce specified heat propane LP gas supply might be low propane LP units only You may feel your gas pressure is too low If so contact your loca...

Страница 31: ...lligree Louver Polished Brass ROLLED Louver Trim kit Not Shown LT32B 32 Brushed Brass LT32P 32 Platinum LT32PB 32 Polished Brass LT36B 36 Brushed Brass LT36P 36 Platinum LT36PB 36 Polished Brass Defle...

Страница 32: ...MODELS V T32N V T32NB V T32NR V T32NRB V T32P V T32PB V T32PR V T32PRB AND CHDV32NR 6 7 21 18 19 10 13 2 11 20 8 22 2 22 6 22 4 22 5 22 3 22 1 1 14 9 12 17 3 15 4 16 5 16 9 3 9 2 9 1 9 13 9 14 9 18 9...

Страница 33: ...ezo Ignitor 1 9 7 14500 Brass Fitting 2 9 8 14253 Flexible Connector 1 9 9 14511 Ignitor Bracket 1 9 10 14528 Brass Elbow Fitting 1 9 11 104506 25 Orifice Natural 1 14514 Orifice Propane LP 1 9 12 104...

Страница 34: ...ELS V T36N V T36NB V T36NR V T36NRB V T36P V T36PB V T36PR V T36PRB AND CTDV36NR 6 7 21 18 19 10 13 2 11 20 8 12 23 1 23 4 23 3 23 6 23 5 23 2 1 14 9 22 17 3 15 4 16 5 16 9 10 9 12 9 4 9 5 9 9 9 7 9 3...

Страница 35: ...179 Screw 10 24 x 1 4 Zinc 4 9 4 11237 Screw Trilab M4 x 8mm 1 9 5 14389 Millivolt Valve Natural 1 14390 Millivolt Valve Propane LP 1 9 6 14492 Piezo Ignitor 1 9 7 14500 Brass Fitting 2 9 8 14508 Flex...

Страница 36: ...ted to repairing a defective heater will be the responsibility of the owner TO THE FULL EXTENT ALLOWED BY THE LAW OF THE JURISDICTION THAT GOVERNS THE SALE OF THE PRODUCT THIS EXPRESS WARRANTY EXCLUDE...

Отзывы: