background image

www.desatech.com

108661-01F

14

VENTING INSTALLATION 

INSTRUCTIONS

Continued

HIGH ALTITUDE INSTALLATION

Your DESA direct-vent fireplace has been CSA tested and approved 

for elevations from 0-2000 feet (USA) and elevations from 0-4500 

feet (Canada).

When installing this fireplace at an elevation above 2000 feet (in the 

USA), you may need to decrease the input rating by changing the 

existing burner orifice to a smaller size. Reduce input 4% for each 

1000 feet above sea level. Check with your  local gas company for 

proper orifice size identification.

When installing this fireplace at an elevation above 4500 feet (in 

Canada), check with local authorities.

Consult your local gas company to help determine the proper orifice 

for your location.

For assistance with any high altitude installation contact DESA 

Customer Service Department at 1-866-672-6040.

PARTS LISTS FOR VENTING KITS AND 

COMPONENtS

DESA Pipe & Vent Kits

Number  Description

P47-6 

6" Section Coaxial Pipe - Galvanized

P47-1 

1" Section Coaxial Pipe - Galvanized

P47-4 

4" Section Coaxial Pipe - Galvanized

P47-36 

36" Section Coaxial Pipe - Galvanized

P47-48 

48" Section Coaxial Pipe - Galvanized

PA47-71  Adjustable 7"-1" Section Coaxial Pipe - Galvanized
VKG-47 

Ground Floor Vent Kit - Galvanized

 

Includes: 45° Elbow, 7"-1" Adjustable Pipe, Wall Fire-
stop, Horizontal Square Termination, and 16 Screws

VKB-47 

Basement Vent Kit - Galvanized

 

Includes: 45° Elbow, 7"-1" Adjustable Pipe, Wall 
Firestop, Horizontal Square Termination, 4' Pipe, 90° 
Elbow, and 0 Screws

VKS-47 

Snorkel Kit - Galvanized

 

Includes: 45° Elbow, 7"-1" Adjustable Pipe, Wall Fire-
stop, 36" Snorkel Termination, 4' Pipe, 90° Elbow, and 
6 Screws

VKR-47 

Roof Vent Kit - Galvanized

 

Includes: 45° Elbow, 7"-1" Adjustable Pipe, Flue 
Restrictor, Vertical High Wind Termination, ' Pipe, 4' 
Pipe, Firestop Plate, Roof Flashing (0/1-6/1), and 
6 Screws

VKC-47 

Corner Vent Kit - Galvanized

 

Includes: 45° Elbow, 7"-1" Adjustable Pipe, Horizon-
tal Termination, 6" Pipe, 90° Elbow, Wall Firestop, and 
18 Screws

HTK 

Horizontal Round Termination Kit

 

Includes: Round Termination, Wall Firestop, and 45° 
Elbow

DESA Elbows

Number  Description

E47-45 

45° Elbow - Galvanized

E47-90 

90° Elbow - Galvanized

DESA Terminations

Number  Description

HT-47 

Horizontal Round Termination - Galvanized

HTS-47 

Horizontal Square Termination - Galvanized

VT-47 

Vertical Round Termination - Galvanized

ST-47-14  14" Snorkel Termination - Galvanized
ST-47-36  36" Snorkel Termination - Galvanized

DESA Venting Accessories

Number  Description

SC-47 

Storm Collar - Galvanized

WF-47 

Wall Firestop - Galvanized

RF-47-6  Roof Flashing - 0 to 6/1 Pitch - Galvanized
RF-47-1  Roof Flashing - 6/1 to 1/1 Pitch - Galvanized
VR-47 

Vertical Restrictor - Galvanized

S-47 

Combustible Siding Standoff - Galvanized

WS-47 

Wall Strap

FP-47 

Firestop Plate

FIREPLACE INSTALLATION

CHECK GAS tYPE

Use proper gas type for the fireplace unit you are installing. If you 

have  conflicting  gas  types,  do  not  install  fireplace.  See  retailer 

where you purchased the fireplace for proper fireplace according 

to your gas type.

INSTALLING OPTIONAL bLOWER 

ACCESSORIES

NOtICE: If installing blower in an existing fireplace with 

gas connections, shut off gas supply and disconnect 

heater  from  gas  supply.  Contact  a  qualified  service 

person to do this.

 WARNING: If there is a duplex electrical outlet in-

stalled in the right side of the bottom of the fireplace 

base area, be sure that the electrical power to the outlet 

is turned off before proceeding with blower installation. 

Failure to do this may result in serious injury.

Model bK Installation

Follow all instructions provided in the blower accessory kit.
1.  Attach the power cord to the blower motor by firmly pushing 

the two female terminals at the end of the power cord onto the two 

spade terminals on the blower motor (see Figure 25, page 15).

2.  Attach green ground wire from power cord to blower housing 

using screw provided (see Figure 25, page 15). Tighten screws 

securely.

Содержание VR32P Series

Страница 1: ...tly located manufactured mobile home where not prohibited by state or local codes Aftermarket Completion of sale not for purpose of resale from the manufacturer WARNING Iftheinformationinthismanualis...

Страница 2: ...tdoors To prevent performance problems do not use pro pane LP fuel tank of less than 100 lbs capacity 3 If you smell gas shut off gas supply do not try to light any appliance do not touch any electric...

Страница 3: ...res These are a few facts that can help you understand and enjoy your direct vent fireplace The venting system may be routed to the outside of your home in several ways It may vent through the roof ve...

Страница 4: ...18 above top of louver opening When locating termination cap it is important to observe the minimum clearances shown in Figure 7 page 6 If recessing into a wall you can avoid extra framing by position...

Страница 5: ...on Preparation Continued Figure 4 Framing Clearances for Installation Against an Exterior Wall 32 Models 36 Models A 323 8 361 8 B 345 8 411 4 C 19 231 2 C B A D E F G Top of Louver Opening 3 2 1 4 5...

Страница 6: ...ve paved side walk or a paved driveway located on public property 84 213 3 cm minimum M clearance under veranda porch deck 12 30 5 cm minimum N clearance above a roof shall extend a minimum of 24 61 c...

Страница 7: ...ons will void the warranty Installation Precautions Wear gloves and safety glasses for protection Use extreme caution when using ladders or when on roof tops Be aware of electrical wiring locations in...

Страница 8: ...re the vent will be terminated If the wall being penetrated is constructed of noncombustible material such as masonry block or concrete a 7 3 4 hole with zero clearance is acceptable see Figure 9 WARN...

Страница 9: ...e overlap should be a minimum of 11 4 9 Slide wall firestop against interior wall surface and attach with screws provided See Figure 13 for horizontal termination details 10 Place fireplace into posit...

Страница 10: ...ground to termination is possible Venting Installation instructions Continued Adjustable Pipe 12 Max Figure 14 Horizontal Termination Configuration for Square and Round Terminations 45 Elbow Wall Fir...

Страница 11: ...l Termination Wall Firestop 90 Elbow 45 Elbow Figure 16 Snorkel Termination Configurations for Below Ground Installation 12 Minimum Adequate Drainage HORIZONTAL SYSTEM INSTALLATION USING TWO 90 ELBOWS...

Страница 12: ...is an attic space or insulated area install firestop above framed hole 2 Assemble the desired lengths of pipe and elbows necessary to reach from the fireplace flue up through the firestop Be sure all...

Страница 13: ...e 22 Vertical Venting Configuration Using One 90 Elbow Vertical Round High Wind Termination Shown Note Install restrictor into inner collar of fireplace as shown Venting with Two 90 Elbows Vertical V1...

Страница 14: ...Vent Kit Galvanized Includes 45 Elbow 7 12 Adjustable Pipe Horizon tal Termination 6 Pipe 90 Elbow Wall Firestop and 18 Screws HTK Horizontal Round Termination Kit Includes Round Termination Wall Fire...

Страница 15: ...y turning knob fully counterclockwise before continuing 10 Peel off the backing paper and stick the supplied wiring diagram decal on the firebox bottom approximately 12 in front of the blower see Figu...

Страница 16: ...blower will only run when the speed control knob is in the ON position and the thermal switch senses temperature after the fireplace begins to heat up The blower speed can be adjusted by rotatingthec...

Страница 17: ...ip leg in supply line as shown in Figure 31 Locate sediment trap drip leg where it is within reach for cleaning Install in piping system between fuel supply and fireplace Locate sediment trap drip leg...

Страница 18: ...Pa 1 Close equipment shutoff valve see Figure 33 2 Pressurize supply piping system by either opening propane LP supply tank valve for propane LPgas fireplace or opening main gas valve located on or ne...

Страница 19: ...wire from TH to TPTH on control valve see Figure 37 6 Connect wires from receiver to TH and TPTH to control valve see Figure 38 7 Replace the switch bracket Figure 36 Attaching Alkaline Battery to Re...

Страница 20: ...ide 2 Lift up on latches to unlock There are two on top of firebox and two below firebox that hold glass door in place see Figure 41 3 While holding glass door to prevent it from falling and causing i...

Страница 21: ...p of grate Make sure the notches in the bottom of the log fit over the grate see Figure 44 2 Rest log 2 large front log on the pins on the front part of the grate see Figure 45 1 2 Figure 44 Installin...

Страница 22: ...derburner Placing lava rock on burner will cause performance problems 8 Pull ember material apart into pieces no larger than a dime Place these pieces loosely and sparingly directly onto the ex posed...

Страница 23: ...Follow the gas supplier s instructions C Use only your hand to push in or turn the gas control knob Never use tools If the knob will not push in or turn by hand don t try to repairit call a qualified...

Страница 24: ...w locked If the fire is on it will be turned off automatically In the locked state the light will not light up when any button is pressed To Unlock press both buttons togetheron hand held remote contr...

Страница 25: ...ontrol etc The keypad is locked in either on or off Press the POWER and LOCK buttons together to turn the unit on or off Operating optional GWMT1 Wall Mounted Thermostat WARNING Do not connect the the...

Страница 26: ...osened Check mechanical supports such as wall straps for rigidity Cleaning and Maintenance WARNING Turn off fireplace and let cool before cleaning CAUTION Youmustkeepcontrolareas burners and circulati...

Страница 27: ...Dirty or partially clogged pilot 5 Thermocouple connection loose at con trol valve 6 Thermocouple damaged 7 Control valve damaged REMEDY 1 Reconnect ignitor cable 2 Free ignitor cable if pinched by an...

Страница 28: ...from line Have gas line checked by local propane LP or natural gas company 3 Clean burner see Cleaning and Main tenance page 26 or replace burner orifice 1 Adjust the log set so that the flame does no...

Страница 29: ...d 3 Burner flame holes blocked OBSERVED PROBLEM Fireplace produces unwanted odors Fireplace shuts off in use Gas odor even when control knob is in OFF position Gas odor during combustion Dark residue...

Страница 30: ...burners will have delayed ignition fireplace will not produce specified heat propane LP gas supply might be low propane LP units only You may feel your gas pressure is too low If so contact your loca...

Страница 31: ...lligree Louver Polished Brass ROLLED Louver Trim kit Not Shown LT32B 32 Brushed Brass LT32P 32 Platinum LT32PB 32 Polished Brass LT36B 36 Brushed Brass LT36P 36 Platinum LT36PB 36 Polished Brass Defle...

Страница 32: ...MODELS V T32N V T32NB V T32NR V T32NRB V T32P V T32PB V T32PR V T32PRB AND CHDV32NR 6 7 21 18 19 10 13 2 11 20 8 22 2 22 6 22 4 22 5 22 3 22 1 1 14 9 12 17 3 15 4 16 5 16 9 3 9 2 9 1 9 13 9 14 9 18 9...

Страница 33: ...ezo Ignitor 1 9 7 14500 Brass Fitting 2 9 8 14253 Flexible Connector 1 9 9 14511 Ignitor Bracket 1 9 10 14528 Brass Elbow Fitting 1 9 11 104506 25 Orifice Natural 1 14514 Orifice Propane LP 1 9 12 104...

Страница 34: ...ELS V T36N V T36NB V T36NR V T36NRB V T36P V T36PB V T36PR V T36PRB AND CTDV36NR 6 7 21 18 19 10 13 2 11 20 8 12 23 1 23 4 23 3 23 6 23 5 23 2 1 14 9 22 17 3 15 4 16 5 16 9 10 9 12 9 4 9 5 9 9 9 7 9 3...

Страница 35: ...179 Screw 10 24 x 1 4 Zinc 4 9 4 11237 Screw Trilab M4 x 8mm 1 9 5 14389 Millivolt Valve Natural 1 14390 Millivolt Valve Propane LP 1 9 6 14492 Piezo Ignitor 1 9 7 14500 Brass Fitting 2 9 8 14508 Flex...

Страница 36: ...ted to repairing a defective heater will be the responsibility of the owner TO THE FULL EXTENT ALLOWED BY THE LAW OF THE JURISDICTION THAT GOVERNS THE SALE OF THE PRODUCT THIS EXPRESS WARRANTY EXCLUDE...

Отзывы: