background image

www.desatech.com

108661-01F

5

OPERATING FIREPLACE

Continued

INSPECTING bURNERS

Check pilot flame pattern and burner flame patterns often.

PILOT ASSEMbLY

The pilot assembly is factory preset for the proper flame height. 

Alterations may have occurred during shipping and handling. Call 

a qualified service person to readjust the pilot if necessary.

The height of the thermopile must be 3/8" to 1/2" above the pilot 

flame as shown in Figure 54. The thermocouple must be at a height 

of about 1/8" above the pilot flame. The flame from the pilot burner 

must extend beyond both the thermocouple and thermopile.

If you pilot assembly does not meet these requirements:
•  turn fireplace off (see 

To Turn Off Gas to Appliance

, page 23)

•  see 

Troubleshooting

, page 27

bURNER FLAME PATTERN

Burner flames will be steady; not lifting or floating. Flame patterns 

will be different from unit to unit and will vary depending on instal-

lation type and weather conditions.

If the vent configuration is installed incorrectly, the flames will lift 

or "ghost". This can be dangerous. Inspect the flames after instal-

lation to ensure proper installation and performance.

Figure 55 shows a typical flame pattern for these models.

If burner flame pattern differs from that described:
•  turn fireplace off (see 

To Turn Off Gas to Appliance

, page 23)

•  see 

Troubleshooting

, page 27

Figure 55 - Typical Flame Pattern

Thermocouple

Thermopile

1/8"

Pilot Burner

Piezo 

Ignitor

Figure 54 - Pilot Assembly

3/8" to 1/"

Key Pad Lock Feature

This feature allows the user to lock/unlock the keypad on the 

hand-held remote in the MANU or AUTO mode to prevent 

inadvertent operation (i.e. children operating the hand-held 

remote control, etc.). The keypad is locked in either on or off. 

Press the POWER and LOCK buttons together to turn the 

unit on or off.

OPERATING OPTIONAL GWMT1 

WALL MOUNTED THERMOSTAT

  WARNING:  Do  not  connect  the  thermostat  to  a 

power  source.  Electrical  shock  and/or  a  fire  hazard 

will occur.

Light the fireplace as instructed in 

Lighting Instructions

 on page 

23. Set wall thermostat to desired temperature.

This thermostat has been electronically calibrated at the factory 

and requires no adjustment or leveling.

Upon installation, the thermostat must be allowed to stabilize 

at room temperature for a minimum of 30 minutes for proper 

operation.

To turn the fireplace off, adjust thermostat to the lowest setting 

and turn the gas control knob back to PILOT. The pilot will 

remain lit.

IMPORTANT:

 To turn the pilot off, turn the gas control knob 

on the heater to the OFF position.

OPERATING OPTIONAL 

BLOWER ACCESSORY

Locate the blower controls by opening the lower louver panel 

on the fireplace. Blower controls are located on the right side of 

the switch bracket to the left just inside the louver panel.

The BK manual blower and the BKT thermostatically-controlled 

blower have an ON setting and an OFF setting. The blower 

will only run when the switch is in the ON position. In the OFF 

position, the blower will not operate.

Note for bKT Only:

 If you are using BKT blower with optional 

thermostat (wall mounted or remote control) for the fireplace, 

your fireplace and blower will not turn on and off at the same 

time. The fireplace may run for several minutes before the blower 

turns on. After the heater modulates to the pilot position, the 

blower will continue to run. The blower will shut off after the 

firebox temperature decreases.

The blower helps distribute heated air from the fireplace. Peri

-

odically check the louvers of the firebox and remove any dust, 

dirt or other obstructions that will hinder the flow of air.

Содержание VR32P Series

Страница 1: ...tly located manufactured mobile home where not prohibited by state or local codes Aftermarket Completion of sale not for purpose of resale from the manufacturer WARNING Iftheinformationinthismanualis...

Страница 2: ...tdoors To prevent performance problems do not use pro pane LP fuel tank of less than 100 lbs capacity 3 If you smell gas shut off gas supply do not try to light any appliance do not touch any electric...

Страница 3: ...res These are a few facts that can help you understand and enjoy your direct vent fireplace The venting system may be routed to the outside of your home in several ways It may vent through the roof ve...

Страница 4: ...18 above top of louver opening When locating termination cap it is important to observe the minimum clearances shown in Figure 7 page 6 If recessing into a wall you can avoid extra framing by position...

Страница 5: ...on Preparation Continued Figure 4 Framing Clearances for Installation Against an Exterior Wall 32 Models 36 Models A 323 8 361 8 B 345 8 411 4 C 19 231 2 C B A D E F G Top of Louver Opening 3 2 1 4 5...

Страница 6: ...ve paved side walk or a paved driveway located on public property 84 213 3 cm minimum M clearance under veranda porch deck 12 30 5 cm minimum N clearance above a roof shall extend a minimum of 24 61 c...

Страница 7: ...ons will void the warranty Installation Precautions Wear gloves and safety glasses for protection Use extreme caution when using ladders or when on roof tops Be aware of electrical wiring locations in...

Страница 8: ...re the vent will be terminated If the wall being penetrated is constructed of noncombustible material such as masonry block or concrete a 7 3 4 hole with zero clearance is acceptable see Figure 9 WARN...

Страница 9: ...e overlap should be a minimum of 11 4 9 Slide wall firestop against interior wall surface and attach with screws provided See Figure 13 for horizontal termination details 10 Place fireplace into posit...

Страница 10: ...ground to termination is possible Venting Installation instructions Continued Adjustable Pipe 12 Max Figure 14 Horizontal Termination Configuration for Square and Round Terminations 45 Elbow Wall Fir...

Страница 11: ...l Termination Wall Firestop 90 Elbow 45 Elbow Figure 16 Snorkel Termination Configurations for Below Ground Installation 12 Minimum Adequate Drainage HORIZONTAL SYSTEM INSTALLATION USING TWO 90 ELBOWS...

Страница 12: ...is an attic space or insulated area install firestop above framed hole 2 Assemble the desired lengths of pipe and elbows necessary to reach from the fireplace flue up through the firestop Be sure all...

Страница 13: ...e 22 Vertical Venting Configuration Using One 90 Elbow Vertical Round High Wind Termination Shown Note Install restrictor into inner collar of fireplace as shown Venting with Two 90 Elbows Vertical V1...

Страница 14: ...Vent Kit Galvanized Includes 45 Elbow 7 12 Adjustable Pipe Horizon tal Termination 6 Pipe 90 Elbow Wall Firestop and 18 Screws HTK Horizontal Round Termination Kit Includes Round Termination Wall Fire...

Страница 15: ...y turning knob fully counterclockwise before continuing 10 Peel off the backing paper and stick the supplied wiring diagram decal on the firebox bottom approximately 12 in front of the blower see Figu...

Страница 16: ...blower will only run when the speed control knob is in the ON position and the thermal switch senses temperature after the fireplace begins to heat up The blower speed can be adjusted by rotatingthec...

Страница 17: ...ip leg in supply line as shown in Figure 31 Locate sediment trap drip leg where it is within reach for cleaning Install in piping system between fuel supply and fireplace Locate sediment trap drip leg...

Страница 18: ...Pa 1 Close equipment shutoff valve see Figure 33 2 Pressurize supply piping system by either opening propane LP supply tank valve for propane LPgas fireplace or opening main gas valve located on or ne...

Страница 19: ...wire from TH to TPTH on control valve see Figure 37 6 Connect wires from receiver to TH and TPTH to control valve see Figure 38 7 Replace the switch bracket Figure 36 Attaching Alkaline Battery to Re...

Страница 20: ...ide 2 Lift up on latches to unlock There are two on top of firebox and two below firebox that hold glass door in place see Figure 41 3 While holding glass door to prevent it from falling and causing i...

Страница 21: ...p of grate Make sure the notches in the bottom of the log fit over the grate see Figure 44 2 Rest log 2 large front log on the pins on the front part of the grate see Figure 45 1 2 Figure 44 Installin...

Страница 22: ...derburner Placing lava rock on burner will cause performance problems 8 Pull ember material apart into pieces no larger than a dime Place these pieces loosely and sparingly directly onto the ex posed...

Страница 23: ...Follow the gas supplier s instructions C Use only your hand to push in or turn the gas control knob Never use tools If the knob will not push in or turn by hand don t try to repairit call a qualified...

Страница 24: ...w locked If the fire is on it will be turned off automatically In the locked state the light will not light up when any button is pressed To Unlock press both buttons togetheron hand held remote contr...

Страница 25: ...ontrol etc The keypad is locked in either on or off Press the POWER and LOCK buttons together to turn the unit on or off Operating optional GWMT1 Wall Mounted Thermostat WARNING Do not connect the the...

Страница 26: ...osened Check mechanical supports such as wall straps for rigidity Cleaning and Maintenance WARNING Turn off fireplace and let cool before cleaning CAUTION Youmustkeepcontrolareas burners and circulati...

Страница 27: ...Dirty or partially clogged pilot 5 Thermocouple connection loose at con trol valve 6 Thermocouple damaged 7 Control valve damaged REMEDY 1 Reconnect ignitor cable 2 Free ignitor cable if pinched by an...

Страница 28: ...from line Have gas line checked by local propane LP or natural gas company 3 Clean burner see Cleaning and Main tenance page 26 or replace burner orifice 1 Adjust the log set so that the flame does no...

Страница 29: ...d 3 Burner flame holes blocked OBSERVED PROBLEM Fireplace produces unwanted odors Fireplace shuts off in use Gas odor even when control knob is in OFF position Gas odor during combustion Dark residue...

Страница 30: ...burners will have delayed ignition fireplace will not produce specified heat propane LP gas supply might be low propane LP units only You may feel your gas pressure is too low If so contact your loca...

Страница 31: ...lligree Louver Polished Brass ROLLED Louver Trim kit Not Shown LT32B 32 Brushed Brass LT32P 32 Platinum LT32PB 32 Polished Brass LT36B 36 Brushed Brass LT36P 36 Platinum LT36PB 36 Polished Brass Defle...

Страница 32: ...MODELS V T32N V T32NB V T32NR V T32NRB V T32P V T32PB V T32PR V T32PRB AND CHDV32NR 6 7 21 18 19 10 13 2 11 20 8 22 2 22 6 22 4 22 5 22 3 22 1 1 14 9 12 17 3 15 4 16 5 16 9 3 9 2 9 1 9 13 9 14 9 18 9...

Страница 33: ...ezo Ignitor 1 9 7 14500 Brass Fitting 2 9 8 14253 Flexible Connector 1 9 9 14511 Ignitor Bracket 1 9 10 14528 Brass Elbow Fitting 1 9 11 104506 25 Orifice Natural 1 14514 Orifice Propane LP 1 9 12 104...

Страница 34: ...ELS V T36N V T36NB V T36NR V T36NRB V T36P V T36PB V T36PR V T36PRB AND CTDV36NR 6 7 21 18 19 10 13 2 11 20 8 12 23 1 23 4 23 3 23 6 23 5 23 2 1 14 9 22 17 3 15 4 16 5 16 9 10 9 12 9 4 9 5 9 9 9 7 9 3...

Страница 35: ...179 Screw 10 24 x 1 4 Zinc 4 9 4 11237 Screw Trilab M4 x 8mm 1 9 5 14389 Millivolt Valve Natural 1 14390 Millivolt Valve Propane LP 1 9 6 14492 Piezo Ignitor 1 9 7 14500 Brass Fitting 2 9 8 14508 Flex...

Страница 36: ...ted to repairing a defective heater will be the responsibility of the owner TO THE FULL EXTENT ALLOWED BY THE LAW OF THE JURISDICTION THAT GOVERNS THE SALE OF THE PRODUCT THIS EXPRESS WARRANTY EXCLUDE...

Отзывы: