RTC 1010 Unit Controller  

BACnet Communication Module User Guide

 

 

www.deos-controls.com

 

Page | 4 

 

Example 3 

 

MAC=0, Max_Master=1 

 

MAC=2, Max_Master=2 

This  is  an  incorrect  configuration.  The  MAC=0  will  never  find  MAC=2  because  it  will  never  poll  for  the  master  MAC 
address=2. 

Example 4 

 

MAC=0. Max_Master=3 

 

MAC=1, Max_Master=3 

 

MAC=2, Max_Master=3 

 

MAC=3, Max_Master=3 

This  is  an  efficient  configuration  as  the  units  are  numbered  consecutively  and  the  MAX_Master  is  set  to  the  most 
efficient  value.  As  a  general  guideline,  the  most  efficient  setup  for  an  MS/TP  network  is  one  in  which  the  units  are 
consecutively  numbered  starting  at  MAC  address  0  and  having  Max_Master=the  maximum  MAC  address  in  the 
system.  If  consecutive  numbering  is  not  possible,  then  the  next  most  efficient  setup  is  one  in  which  all  units  have 
Max_Master=the maximum MAC address in the system. 

Copy Config 

Copy and broadcast the entire configuration of a controller over the network to controllers of the same type using the 
Copy Config feature.  

1. 

Access Operation Mode (jumper set to RUN position).  

2. 

Press and hold both function buttons for 5 seconds to access the Quick Access menu.  

3. 

Enter the password, 

637

4. 

Scroll to 

Copy Config

 programming menu and select 

Yes

. Follow the rest of the onscreen instructions. 

 

Note: A Copy Config can also be executed via BACnet. See AV.468, AV.469, AV.470, and BV.101  in Table 6 - 
Object Table Information: Analog Value (AV) and Table 9 - Object Table Information: Binary Value (BV) for details. 

Network Reset 

Reset  the  controller  via  BACnet  using  the 

Reinitialize  Device 

service.  The  Reinitialize  Device  service  can  be 

accessed using the following password: 

nep. 

The Reinitialize Device service has two types of reset such as:  

 

Warm Reset. 

The Warm Reset restarts the controller with actual configuration. 

 

 

Cold Reset. The Cold Reset restarts the controller with 

Factory configuration

.  

 

Warning:

 The Cold Reset erases the actual configuration when setting the MSTP address. Therefore, exercise 

caution while performing a Cold Reset.  

 

 

 

Содержание RTC 1010

Страница 1: ...RTC 1010 BACnet Guide 170605 docx RTC 1010 Unit Controller BACnet Communication Module User Guide Zoning System...

Страница 2: ...ration 2 Configuration Options 3 Quick Setup 3 Manual Setup 3 MAC Address and Max_Master 3 Copy Config 4 Network Reset 4 Device Object Properties 5 Object Types Supported 6 Out of Service Property 7 O...

Страница 3: ...lay of 15 minutes to ensure a Tusage_timeout value within 20 minutes MS TP Support The controller supports a Full Master Node state machine for MS TP The Max_Master and the instances are configured to...

Страница 4: ...through the WriteProperty service to Device Object Object_Identifier The device s Object_Identifier is a combination of the Device Object_Type 8 and the Device_Instance 0 4194302 therefore its decimal...

Страница 5: ...guarantee efficient operation of the controller and other MS TP units on the MS TP network Some MAC address and Max_Master combinations are more efficient than others BACnet requires token passing uni...

Страница 6: ...uration of a controller over the network to controllers of the same type using the Copy Config feature 1 Access Operation Mode jumper set to RUN position 2 Press and hold both function buttons for 5 s...

Страница 7: ...me and or device ID change Max_APDU_Length_Accepted Always 480 Segmentation_Supported 3 No Segmentation APDU_Timeout 6 000 W Number_of_APDU_Retries Always 3 Local_Time 00 00 00 W Local_Date 02 Jan 201...

Страница 8: ...tion on page 7 for more information Object will automatically return to Normal after a programmable period of time Refer to Proprietary property 1002 of Device Object in Table 2 Device Object Properti...

Страница 9: ...is not writable for MSV Program Description Reliability Program_Change Only LOAD and RESTART are supported for Program Change Use LOAD to apply the new firmware File Description Archive File Size Onl...

Страница 10: ...sure Static pressure reading of 0 to 10 Vdc from SPD sensor on analog input 4 Out_of_Service COV Increment 0 Vdc to 10 Vdc Resolution 0 1 Vdc AI 5 AI5_SupplyRH Supply humidity percentage reading on an...

Страница 11: ...for return air temperature The cooling setpoint is restricted by the heating setpoint Com lost RAT control setpoints Present Value COV Increment 50 F to 104 F or 10 C to 40 C AV 11 to 104 F 40 C Reso...

Страница 12: ...COV Increment 0 RH to 100 RH Resolution 0 1 RH AV 32 USI_RH_Reading UPT 24 H RT humidity percentage sensor reading Out_of_Service COV Increment 0 RH to 100 RH Resolution 0 1 RH AV 35 Cfg_TimeoutDeman...

Страница 13: ...73 CDem3 Third highest cooling demand Out_of_Service 0 to 100 Resolution 0 1 AV 74 CDem4 Fourth highest cooling demand Out_of_Service 0 to 100 Resolution 0 1 AV 75 CDem5 Fifth highest cooling demand...

Страница 14: ...H to 100 RH Resolution 0 5 RH AV 126 Cfg_HumidificationIT Configuration value of integration time for humidification Present Value 0 minutes to 7 200 minutes Resolution 1 minute AV 127 Cfg_PressureDB...

Страница 15: ...cates the device identification instance The instance is configured as per the Auto Instance Setting Present Value 0 to 4194302 Resolution 1 unit AV 468 CopyCfgStartAdd When using copy config this val...

Страница 16: ...scription W Notes BO 1 BO1_W2 Contact status of the binary output 1 for heating 0 Off 1 On Present Value 0 Off 1 On BO 2 BO2_W1 Contact status of the binary output 2 for heating 0 Off 1 On Present Val...

Страница 17: ...inform if the humidity lock is active on outside air temperature 0 Off 1 On Read Only 0 Off 1 On BV 25 OverrideOccupancy Status value to inform whether the user can override the occupancy mode or not...

Страница 18: ...3 5CPH 4 6CPH 5 7CPH 6 8CPH MSV 6 Cfg_CoolingCPH Configuration that indicates cooling CPH 1 3CPH 2 4CPH Present Value 1 3CPH 2 4CPH MSV 12 Cfg_OperationLogic Configuration value to determine the opera...

Страница 19: ...temperature sensor 2 0 100 0 to 10Vdc input converted to 0 to 100 3 On Off Binary Input Present Value 1 Temperature 2 Percentage 3 On Off MSV 100 Cfg_ObjectList Configuration value of the object list...

Страница 20: ...Notes www deos controls com...

Отзывы: