RTC 1010 Unit Controller
BACnet Communication Module User Guide
www.deos-controls.com
Page | 12
ID
Name
Description
W?
Notes
AV.99
CoolingDemandStage2
Status value that represents the cooling demand for the Cooling Ramp 2 for stage 1. This value is
based on zone temperature, zone setpoint and values set for the actual ramp.
Out_of_Service
0% to 100%, Resolution 0.1%
AV.100
Cfg_Anticycle
Configuration value in minutes to prevent the cooling outputs to cycle on and off. This is a
protection feature used when cooling is done through compressors. Applicable on heating and
cooling stages only.
Present Value
0 minutes to 10 minutes, Resolution 1 minute
AV.105
EconoCoolingLimit
Value of the cooling limit that can be set on the economizer.
Out_of_Service
0% to 100%, Resolution 0.1%
AV.120
SupplyAirRhHighLimitDemand
Status value that represents the high limit demand for supply air.
Out_of_Service
0% RH to 100% RH, Resolution 0.1%
AV.121
HumidificationDemand
Status value that represents the humidifier modulation, based on relative humidity.
Out_of_Service
0% to 100%, Resolution 0.1%
AV.122
Cfg_SupplyAirRhDB
Configuration value that represents the range at which the controller will not take an action when
the supply air’s humidity is below the zone’s setpoint.
Present Value
0% to 10% RH, Resolution 0.1% RH
AV.123
Cfg_SupplyAirRhPB
Configuration value that represents the range through which the controller modulates the supply
air’s humidity from 0 to 100%.
Present Value
0% RH to 100% RH, Resolution 0.5% RH
AV.124
Cfg_HumidificationDB
Configuration value that represents the range at which the controller will not take an action when
the humidity is below the zone’s setpoint.
Present Value
0% to 10% RH,
Resolution 0.1% RH
AV.125
Cfg_HumidificationPB
Configuration value that represents the range through which the controller modulates the humidity
from 0 to 100%.
Present Value
0% RH to 100% RH, Resolution 0.5% RH
AV.126
Cfg_HumidificationIT
Configuration value of integration time for humidification.
Present Value
0 minutes to 7,200 minutes, Resolution 1 minute
AV.127
Cfg_PressureDB
Configuration value that represents the range through which the controller will not take an action
when the static pressure is below the zone’s setpoint.
Present Value
0
”W.C. to 5”W.C.
or 0Pa to 1244Pa, Resolution
0.01
”W.C/2.4Pa.
AV.128
Cfg_PressurePB
Configuration value that represents the range through which the controller modulates the static
pressure.
Present Value
0
”W.C to 2”W.C or 0Pa to 498Pa, Resolution
0.01
”W.C/2.4Pa.
AV.129
Cfg_PressureIT
Configuration value of integration time for static pressure control loop.
Present Value
0 minutes to 7,200 minutes, Resolution 1 minute
AV.130
Cfg_SAT_HeatIT
Configuration value of integration time for supply air temperature heat.
Present Value
0 minutes to 7,200 minutes, Resolution 1 minute
AV.131
Cfg_SAT_EconoIT
Configuration value of integration time for economizer.
Present Value
0 minutes to 7,200 minutes, Resolution 1 minute
AV.132
Cfg_SupplyAirRhIT
Configuration value of integration time for supply air temperature humidity.
Present Value
0 minutes to 7,200 minutes, Resolution 1 minute
AV.137
Cfg_ReturnAirTemperatureDB
Configuration value to define the dead band value for return air temperature.
Present Value
0°F to 9°F or 0°C to 5°C, Resolution 0.2°F/0.1°C
AV.138
Cfg_ReturnAirTemperaturePB
Configuration value to define the proportional band value for return air temperature.
Present Value
32°F to 90°F or 0°C to 50°C, Resolution 1°F/0.5°C
AV.139
Cfg_ReturnAirTemperatureIT
Configuration value of integration time for return air temperature.
Present Value
0 minutes to 7,200 minutes, Resolution 1 minute
AV.140
ReturnAirTempHeatingDemand
Status value that represents the heating demand for return air temperature.
Out_of_Service
0% to 100%, Resolution 0.1%
AV.141
ReturnAirTempCoolingDemand
Status value that represents the cooling demand for return air temperature.
Out_of_Service
0% to 100%, Resolution 0.1%