RTC 1010 Unit Controller  

BACnet Communication Module User Guide

 

 

www.deos-controls.com

 

Page | 11 

 

ID 

Name 

Description 

W? 

Notes 

AV.63

 

HDem3AVERAGE 

Average of the 3 highest heating demands. 

Out_of_Service

 

0% to 100%, Resolution 0.1%

 

AV.64

 

HDem4AVERAGE 

Average of the 4 highest heating demands. 

Out_of_Service

 

0% to 100%, Resolution 0.1%

 

AV.65

 

HDem5AVERAGE 

Average of the highest heating demands. 

Out_of_Service

 

0% to 100%, Resolution 0.1%

 

AV.68

 

HeatingDemandStage1 

Status value that represents the heating demand in percentage for the Heating Ramp 1 for stage 
1. This value is based on zone temperature, zone setpoint, and values set for the actual ramp. 

Out_of_Service

 

0% to 100%, Resolution 0.1% 

AV.69

 

HeatingDemandStage2 

Status value that represents the heating demand in percentage for the Heating Ramp 2 for stage 
2. This value is based on zone temperature, zone setpoint, and values set for the actual ramp. 

Out_of_Service

 

0% to 100%, Resolution 0.1% 

AV.70

 

CoolingWeightedDemand 

Last cooling demand received from the zone. 

Out_of_Service

 

0% to 100%, Resolution 0.1% 

AV.71

 

CDem1 

Highest cooling demand. 

Out_of_Service

 

0% to 100%, Resolution 0.1% 

AV.72

 

CDem2 

Second highest cooling demand. 

Out_of_Service

 

0% to 100%, Resolution 0.1% 

AV.73

 

CDem3 

Third highest cooling demand. 

Out_of_Service

 

0% to 100%, Resolution 0.1% 

AV.74

 

CDem4 

Fourth highest cooling demand. 

Out_of_Service

 

0% to 100%, Resolution 0.1% 

AV.75  CDem5 

Fifth highest cooling demand. 

Out_of_Service

 

0% to 100%, Resolution 0.1% 

AV.81

 

CDem1MAC 

Zone MAC address for highest cooling demand. 

Out_of_Service

 

0 to 254, Resolution 1 unit

 

AV.82

 

CDem2MAC 

Zone MAC address for second highest cooling demand. 

Out_of_Service

 

0 to 254, Resolution 1 unit 

AV.83

 

CDem3MAC 

Zone MAC address for third highest cooling demand. 

Out_of_Service

 

0 to 254, Resolution 1 unit 

AV.84

 

CDem4MAC 

Zone MAC address for fourth highest cooling demand. 

Out_of_Service

 

0 to 254, Resolution 1 unit 

AV.85

 

CDem5MAC 

Zone MAC address for fifth highest cooling demand. 

Out_of_Service

 

0 to 254, Resolution 1 unit

 

AV.92

 

CDem2AVERAGE 

Average of 2 highest cooling demands. 

Out_of_Service

 

0% to 100%, Resolution 0.1% 

AV.93

 

CDem3AVERAGE 

Average of 3 highest cooling demands. 

Out_of_Service

 

0% to 100%, Resolution 0.1% 

AV.94

 

CDem4AVERAGE 

Average of 4 highest cooling demands. 

Out_of_Service

 

0% to 100%, Resolution 0.1% 

AV.95

 

CDem5AVERAGE 

Average of 5 highest cooling demands. 

Out_of_Service

 

0% to 100%, Resolution 0.1% 

AV.98

 

CoolingDemandStage1 

Status value that represents the cooling demand for the Cooling Ramp 1 for stage 1. This value is 
based on zone temperature, zone setpoint and values set for the actual ramp. 

Out_of_Service

 

0% to 100%, Resolution 0.1% 

Содержание RTC 1010

Страница 1: ...RTC 1010 BACnet Guide 170605 docx RTC 1010 Unit Controller BACnet Communication Module User Guide Zoning System...

Страница 2: ...ration 2 Configuration Options 3 Quick Setup 3 Manual Setup 3 MAC Address and Max_Master 3 Copy Config 4 Network Reset 4 Device Object Properties 5 Object Types Supported 6 Out of Service Property 7 O...

Страница 3: ...lay of 15 minutes to ensure a Tusage_timeout value within 20 minutes MS TP Support The controller supports a Full Master Node state machine for MS TP The Max_Master and the instances are configured to...

Страница 4: ...through the WriteProperty service to Device Object Object_Identifier The device s Object_Identifier is a combination of the Device Object_Type 8 and the Device_Instance 0 4194302 therefore its decimal...

Страница 5: ...guarantee efficient operation of the controller and other MS TP units on the MS TP network Some MAC address and Max_Master combinations are more efficient than others BACnet requires token passing uni...

Страница 6: ...uration of a controller over the network to controllers of the same type using the Copy Config feature 1 Access Operation Mode jumper set to RUN position 2 Press and hold both function buttons for 5 s...

Страница 7: ...me and or device ID change Max_APDU_Length_Accepted Always 480 Segmentation_Supported 3 No Segmentation APDU_Timeout 6 000 W Number_of_APDU_Retries Always 3 Local_Time 00 00 00 W Local_Date 02 Jan 201...

Страница 8: ...tion on page 7 for more information Object will automatically return to Normal after a programmable period of time Refer to Proprietary property 1002 of Device Object in Table 2 Device Object Properti...

Страница 9: ...is not writable for MSV Program Description Reliability Program_Change Only LOAD and RESTART are supported for Program Change Use LOAD to apply the new firmware File Description Archive File Size Onl...

Страница 10: ...sure Static pressure reading of 0 to 10 Vdc from SPD sensor on analog input 4 Out_of_Service COV Increment 0 Vdc to 10 Vdc Resolution 0 1 Vdc AI 5 AI5_SupplyRH Supply humidity percentage reading on an...

Страница 11: ...for return air temperature The cooling setpoint is restricted by the heating setpoint Com lost RAT control setpoints Present Value COV Increment 50 F to 104 F or 10 C to 40 C AV 11 to 104 F 40 C Reso...

Страница 12: ...COV Increment 0 RH to 100 RH Resolution 0 1 RH AV 32 USI_RH_Reading UPT 24 H RT humidity percentage sensor reading Out_of_Service COV Increment 0 RH to 100 RH Resolution 0 1 RH AV 35 Cfg_TimeoutDeman...

Страница 13: ...73 CDem3 Third highest cooling demand Out_of_Service 0 to 100 Resolution 0 1 AV 74 CDem4 Fourth highest cooling demand Out_of_Service 0 to 100 Resolution 0 1 AV 75 CDem5 Fifth highest cooling demand...

Страница 14: ...H to 100 RH Resolution 0 5 RH AV 126 Cfg_HumidificationIT Configuration value of integration time for humidification Present Value 0 minutes to 7 200 minutes Resolution 1 minute AV 127 Cfg_PressureDB...

Страница 15: ...cates the device identification instance The instance is configured as per the Auto Instance Setting Present Value 0 to 4194302 Resolution 1 unit AV 468 CopyCfgStartAdd When using copy config this val...

Страница 16: ...scription W Notes BO 1 BO1_W2 Contact status of the binary output 1 for heating 0 Off 1 On Present Value 0 Off 1 On BO 2 BO2_W1 Contact status of the binary output 2 for heating 0 Off 1 On Present Val...

Страница 17: ...inform if the humidity lock is active on outside air temperature 0 Off 1 On Read Only 0 Off 1 On BV 25 OverrideOccupancy Status value to inform whether the user can override the occupancy mode or not...

Страница 18: ...3 5CPH 4 6CPH 5 7CPH 6 8CPH MSV 6 Cfg_CoolingCPH Configuration that indicates cooling CPH 1 3CPH 2 4CPH Present Value 1 3CPH 2 4CPH MSV 12 Cfg_OperationLogic Configuration value to determine the opera...

Страница 19: ...temperature sensor 2 0 100 0 to 10Vdc input converted to 0 to 100 3 On Off Binary Input Present Value 1 Temperature 2 Percentage 3 On Off MSV 100 Cfg_ObjectList Configuration value of the object list...

Страница 20: ...Notes www deos controls com...

Отзывы: