RTC 1010 Unit Controller  

BACnet Communication Module User Guide

 

 

www.deos-controls.com

 

Page | 13 

 

ID 

Name 

Description 

W? 

Notes 

AV.165

 

MSTP_BaudRate 

Status value that indicates the rate at which the Baud rate can be configured on an MSTP 
network.  

Present Value 

(0)Auto, 9600, 19200, 38400, and 76800. Resolution 
Auto 

AV.166

 

MSTP_MAC_Address 

Status value that indicates the MAC address of the controllers on an MSTP network.  

Present Value

 

0 to 254, Resolution 1 unit 

AV.167

 

DeviceInstance 

Status value that indicates the device identification instance. The instance is configured as per the 
Auto Instance Setting. 

Present Value

 

0 to 4194302, Resolution 1 unit 

AV.468

 

CopyCfgStartAdd 

When using copy config, this value represents the first address in the range of copied controllers.

 

Present Value

 

0 to 254 (AV.468 to 254), Resolution 1 unit

 

AV.469

 

CopyCfgEndAdd 

When using copy config, this value represents the last address in the range of copied controllers.

 

Present Value

 

0 to 254 (AV.468 to AV.469), Resolution 1 unit

 

AV.470  CopyCfgResult 

When using copy config, this value is used to verify that the copy to the controllers was successful 
or failed. 

Present Value 

Succeed, Progerr, Typeerr, Modlerr, Memerr, Slave, 
Commerr 

 

 

Содержание RTC 1010

Страница 1: ...RTC 1010 BACnet Guide 170605 docx RTC 1010 Unit Controller BACnet Communication Module User Guide Zoning System...

Страница 2: ...ration 2 Configuration Options 3 Quick Setup 3 Manual Setup 3 MAC Address and Max_Master 3 Copy Config 4 Network Reset 4 Device Object Properties 5 Object Types Supported 6 Out of Service Property 7 O...

Страница 3: ...lay of 15 minutes to ensure a Tusage_timeout value within 20 minutes MS TP Support The controller supports a Full Master Node state machine for MS TP The Max_Master and the instances are configured to...

Страница 4: ...through the WriteProperty service to Device Object Object_Identifier The device s Object_Identifier is a combination of the Device Object_Type 8 and the Device_Instance 0 4194302 therefore its decimal...

Страница 5: ...guarantee efficient operation of the controller and other MS TP units on the MS TP network Some MAC address and Max_Master combinations are more efficient than others BACnet requires token passing uni...

Страница 6: ...uration of a controller over the network to controllers of the same type using the Copy Config feature 1 Access Operation Mode jumper set to RUN position 2 Press and hold both function buttons for 5 s...

Страница 7: ...me and or device ID change Max_APDU_Length_Accepted Always 480 Segmentation_Supported 3 No Segmentation APDU_Timeout 6 000 W Number_of_APDU_Retries Always 3 Local_Time 00 00 00 W Local_Date 02 Jan 201...

Страница 8: ...tion on page 7 for more information Object will automatically return to Normal after a programmable period of time Refer to Proprietary property 1002 of Device Object in Table 2 Device Object Properti...

Страница 9: ...is not writable for MSV Program Description Reliability Program_Change Only LOAD and RESTART are supported for Program Change Use LOAD to apply the new firmware File Description Archive File Size Onl...

Страница 10: ...sure Static pressure reading of 0 to 10 Vdc from SPD sensor on analog input 4 Out_of_Service COV Increment 0 Vdc to 10 Vdc Resolution 0 1 Vdc AI 5 AI5_SupplyRH Supply humidity percentage reading on an...

Страница 11: ...for return air temperature The cooling setpoint is restricted by the heating setpoint Com lost RAT control setpoints Present Value COV Increment 50 F to 104 F or 10 C to 40 C AV 11 to 104 F 40 C Reso...

Страница 12: ...COV Increment 0 RH to 100 RH Resolution 0 1 RH AV 32 USI_RH_Reading UPT 24 H RT humidity percentage sensor reading Out_of_Service COV Increment 0 RH to 100 RH Resolution 0 1 RH AV 35 Cfg_TimeoutDeman...

Страница 13: ...73 CDem3 Third highest cooling demand Out_of_Service 0 to 100 Resolution 0 1 AV 74 CDem4 Fourth highest cooling demand Out_of_Service 0 to 100 Resolution 0 1 AV 75 CDem5 Fifth highest cooling demand...

Страница 14: ...H to 100 RH Resolution 0 5 RH AV 126 Cfg_HumidificationIT Configuration value of integration time for humidification Present Value 0 minutes to 7 200 minutes Resolution 1 minute AV 127 Cfg_PressureDB...

Страница 15: ...cates the device identification instance The instance is configured as per the Auto Instance Setting Present Value 0 to 4194302 Resolution 1 unit AV 468 CopyCfgStartAdd When using copy config this val...

Страница 16: ...scription W Notes BO 1 BO1_W2 Contact status of the binary output 1 for heating 0 Off 1 On Present Value 0 Off 1 On BO 2 BO2_W1 Contact status of the binary output 2 for heating 0 Off 1 On Present Val...

Страница 17: ...inform if the humidity lock is active on outside air temperature 0 Off 1 On Read Only 0 Off 1 On BV 25 OverrideOccupancy Status value to inform whether the user can override the occupancy mode or not...

Страница 18: ...3 5CPH 4 6CPH 5 7CPH 6 8CPH MSV 6 Cfg_CoolingCPH Configuration that indicates cooling CPH 1 3CPH 2 4CPH Present Value 1 3CPH 2 4CPH MSV 12 Cfg_OperationLogic Configuration value to determine the opera...

Страница 19: ...temperature sensor 2 0 100 0 to 10Vdc input converted to 0 to 100 3 On Off Binary Input Present Value 1 Temperature 2 Percentage 3 On Off MSV 100 Cfg_ObjectList Configuration value of the object list...

Страница 20: ...Notes www deos controls com...

Отзывы: