RTC 1010 Unit Controller
BACnet Communication Module User Guide
www.deos-controls.com
Page | 14
Binary Input (BI)
Table 7 - Object Table Information: Binary Input (BI)
ID
Name
Description
W?
Notes
BI.1
BI1_AuxIn
Contact status of the binary input 1: (0) Off, (1) On.
Out_of_Service 0 = Off, 1 = On
BI.2
BI2_AuxIn
Contact status of the binary input 2: (0) Off, (1) On.
Out_of_Service 0 = Off, 1 = On
Binary Output (BO)
Table 8 - Object Table Information: Binary Output (BO)
ID
Name
Description
W?
Notes
BO.1
BO1_W2
Contact status of the binary output 1 for heating: (0) Off, (1) On.
Present Value
0 = Off, 1 = On
BO.2
BO2_W1
Contact status of the binary output 2 for heating: (0) Off, (1) On.
Present Value
0 = Off, 1 = On
BO.3
BO3_G
Contact status of the binary output 3 for fan: (0) Off, (1) On.
Present Value
0 = Off, 1 = On
BO.4
BO4_Y1
Contact status of the binary output 4 for cooling: (0) Off, (1) On.
Present Value
0 = Off, 1 = On
BO.5
BO5_Y2
Contact status of the binary output 5 for cooling: (0) Off, (1) On.
Present Value
0 = Off, 1 = On
BO.6
BO6_FreshAir_ExhaustAuthorize
Contact status of the binary output 6 to authorize exhaust operation: (0) Off, (1) On.
Present Value
0 = Off, 1 = On