RTC 1010 Unit Controller  

BACnet Communication Module User Guide

 

 

www.deos-controls.com

 

Page | 15 

 

Binary Value (BV) 

Table 9 - Object Table Information: Binary Value (BV) 

ID 

Name 

Description 

W? 

Notes 

BV.1 

Cfg_UnitBACnet 

Configuration of the temperature units used in BACnet.  
If set to (0), the temperature will be in Celsius scale. If set to (1), the temperature will be in 
Fahrenheit scale. 

Present Value 

0 = Celsius,1 = Fahrenheit 

BV.2 

Cfg_LocalUnitDisplay 

Configuration of the display units. If set to (0), the temperature will be in Celsius scale. If set to (1), 
the temperature will be in Fahrenheit scale. 

Present Value 

0 = Celsius,1 = Fahrenheit 

BV.15  Cfg_SPC_DeviceType 

Configuration of the device type. If set to (0), the device type will be BPD. If set to (1), the device 
type will be VFD.  

Present Value 

0 = BPD, 1 = VFD 

BV.20  AL_OAT_HeatLockActive 

Status value to inform if the heat lock is active on outside air temperature. (0) Off, (1) On 

Read Only 

0 = Off, 1 = On 

BV.21  AL_OAT_CoolLockActive 

Status value to inform if the cool lock is active on outside air temperature. (0) Off, (1) On 

Read Only 

0 = Off, 1 = On 

BV.22  AL_SAT_HeatLockActive 

Status value to inform if the heat lock is active on supply air temperature.  (0) Off, (1) On 

Read Only 

0 = Off, 1 = On 

BV.23  AL_SAT_CoolLockActive 

Status value to inform if the cool lock is active on supply air temperature. (0) Off, (1) On 

Read Only 

0 = Off, 1 = On 

BV.24  AL_OAT_HumLockActive 

Status value to inform if the humidity lock is active on outside air temperature. (0) Off, (1) On 

Read Only 

0 = Off, 1 = On 

BV.25  OverrideOccupancy 

Status value to inform whether the user can override the occupancy mode or not. (0) Off, (1) On 

Present Value 

0 = Off, 1 = On 

BV.26  LocalChangeoverMode 

Status value of the actual changeover mode. (0) = Cool, (1) = Heat 

Read Only 

0 = Cool, 1 = Heat 

BV.27  AL_ZoneCommLost 

Status value to inform if the communication from the zone is lost. (0) Off, (1) On 

Read Only 

0 = Off, 1 = On 

BV.28  Cfg_HeatingStages 

Configuration value of heating stages. (0) 1 Stage, (1) 2 Stages 

Present Value 

0 = 1 Stage, 1 = 2 Stages 

BV.29  Cfg_AnalogHeatUsed 

Configuration value to indicate if analog heat can be used. (0) No, (1) Yes 

Present Value 

0 = No, 1 = Yes 

BV.30  Cfg_CoolingStages 

Configuration value of cooling stages. (0) 1 Stage, (1) 2 Stages 

Present Value 

0 = 1 Stage, 1 = 2 Stages 

BV.31  Cfg_EconomizerInstalled 

Configuration value to inform if the Economizer has been installed or not. (0) No, (1) Yes 

Present Value 

0 = No, 1 = Yes 

BV.32  Cfg_RH_SensorUsed 

Configuration value to inform about the sensor used. (0) Return Air RH, (1) USI RH Reading 

Present Value 

0 = Return Air RH, 1 = USI RH Reading 

BV.36  Cfg_DigitalInput1Polarity 

Configuration value to inform about the polarity of digital input 1. (0) Direct, (1) Reverse 

Present Value 

0 = Direct, 1 = Reverse 

BV.37  Cfg_DigitalInput2Polarity 

Configuration value to inform about the polarity of digital input 2. (0) Direct, (1) Reverse 

Present Value 

0 = Direct, 1 = Reverse 

BV.40  BalancingModeActive 

Configuration value to indicate whether the airflow balancing mode is active or not.  
(0) No, (1) Yes 

Present Value 

0 = No, 1 = Yes 

Содержание RTC 1010

Страница 1: ...RTC 1010 BACnet Guide 170605 docx RTC 1010 Unit Controller BACnet Communication Module User Guide Zoning System...

Страница 2: ...ration 2 Configuration Options 3 Quick Setup 3 Manual Setup 3 MAC Address and Max_Master 3 Copy Config 4 Network Reset 4 Device Object Properties 5 Object Types Supported 6 Out of Service Property 7 O...

Страница 3: ...lay of 15 minutes to ensure a Tusage_timeout value within 20 minutes MS TP Support The controller supports a Full Master Node state machine for MS TP The Max_Master and the instances are configured to...

Страница 4: ...through the WriteProperty service to Device Object Object_Identifier The device s Object_Identifier is a combination of the Device Object_Type 8 and the Device_Instance 0 4194302 therefore its decimal...

Страница 5: ...guarantee efficient operation of the controller and other MS TP units on the MS TP network Some MAC address and Max_Master combinations are more efficient than others BACnet requires token passing uni...

Страница 6: ...uration of a controller over the network to controllers of the same type using the Copy Config feature 1 Access Operation Mode jumper set to RUN position 2 Press and hold both function buttons for 5 s...

Страница 7: ...me and or device ID change Max_APDU_Length_Accepted Always 480 Segmentation_Supported 3 No Segmentation APDU_Timeout 6 000 W Number_of_APDU_Retries Always 3 Local_Time 00 00 00 W Local_Date 02 Jan 201...

Страница 8: ...tion on page 7 for more information Object will automatically return to Normal after a programmable period of time Refer to Proprietary property 1002 of Device Object in Table 2 Device Object Properti...

Страница 9: ...is not writable for MSV Program Description Reliability Program_Change Only LOAD and RESTART are supported for Program Change Use LOAD to apply the new firmware File Description Archive File Size Onl...

Страница 10: ...sure Static pressure reading of 0 to 10 Vdc from SPD sensor on analog input 4 Out_of_Service COV Increment 0 Vdc to 10 Vdc Resolution 0 1 Vdc AI 5 AI5_SupplyRH Supply humidity percentage reading on an...

Страница 11: ...for return air temperature The cooling setpoint is restricted by the heating setpoint Com lost RAT control setpoints Present Value COV Increment 50 F to 104 F or 10 C to 40 C AV 11 to 104 F 40 C Reso...

Страница 12: ...COV Increment 0 RH to 100 RH Resolution 0 1 RH AV 32 USI_RH_Reading UPT 24 H RT humidity percentage sensor reading Out_of_Service COV Increment 0 RH to 100 RH Resolution 0 1 RH AV 35 Cfg_TimeoutDeman...

Страница 13: ...73 CDem3 Third highest cooling demand Out_of_Service 0 to 100 Resolution 0 1 AV 74 CDem4 Fourth highest cooling demand Out_of_Service 0 to 100 Resolution 0 1 AV 75 CDem5 Fifth highest cooling demand...

Страница 14: ...H to 100 RH Resolution 0 5 RH AV 126 Cfg_HumidificationIT Configuration value of integration time for humidification Present Value 0 minutes to 7 200 minutes Resolution 1 minute AV 127 Cfg_PressureDB...

Страница 15: ...cates the device identification instance The instance is configured as per the Auto Instance Setting Present Value 0 to 4194302 Resolution 1 unit AV 468 CopyCfgStartAdd When using copy config this val...

Страница 16: ...scription W Notes BO 1 BO1_W2 Contact status of the binary output 1 for heating 0 Off 1 On Present Value 0 Off 1 On BO 2 BO2_W1 Contact status of the binary output 2 for heating 0 Off 1 On Present Val...

Страница 17: ...inform if the humidity lock is active on outside air temperature 0 Off 1 On Read Only 0 Off 1 On BV 25 OverrideOccupancy Status value to inform whether the user can override the occupancy mode or not...

Страница 18: ...3 5CPH 4 6CPH 5 7CPH 6 8CPH MSV 6 Cfg_CoolingCPH Configuration that indicates cooling CPH 1 3CPH 2 4CPH Present Value 1 3CPH 2 4CPH MSV 12 Cfg_OperationLogic Configuration value to determine the opera...

Страница 19: ...temperature sensor 2 0 100 0 to 10Vdc input converted to 0 to 100 3 On Off Binary Input Present Value 1 Temperature 2 Percentage 3 On Off MSV 100 Cfg_ObjectList Configuration value of the object list...

Страница 20: ...Notes www deos controls com...

Отзывы: