RTC 1010 Unit Controller
BACnet Communication Module User Guide
www.deos-controls.com
Page | 15
Binary Value (BV)
Table 9 - Object Table Information: Binary Value (BV)
ID
Name
Description
W?
Notes
BV.1
Cfg_UnitBACnet
Configuration of the temperature units used in BACnet.
If set to (0), the temperature will be in Celsius scale. If set to (1), the temperature will be in
Fahrenheit scale.
Present Value
0 = Celsius,1 = Fahrenheit
BV.2
Cfg_LocalUnitDisplay
Configuration of the display units. If set to (0), the temperature will be in Celsius scale. If set to (1),
the temperature will be in Fahrenheit scale.
Present Value
0 = Celsius,1 = Fahrenheit
BV.15 Cfg_SPC_DeviceType
Configuration of the device type. If set to (0), the device type will be BPD. If set to (1), the device
type will be VFD.
Present Value
0 = BPD, 1 = VFD
BV.20 AL_OAT_HeatLockActive
Status value to inform if the heat lock is active on outside air temperature. (0) Off, (1) On
Read Only
0 = Off, 1 = On
BV.21 AL_OAT_CoolLockActive
Status value to inform if the cool lock is active on outside air temperature. (0) Off, (1) On
Read Only
0 = Off, 1 = On
BV.22 AL_SAT_HeatLockActive
Status value to inform if the heat lock is active on supply air temperature. (0) Off, (1) On
Read Only
0 = Off, 1 = On
BV.23 AL_SAT_CoolLockActive
Status value to inform if the cool lock is active on supply air temperature. (0) Off, (1) On
Read Only
0 = Off, 1 = On
BV.24 AL_OAT_HumLockActive
Status value to inform if the humidity lock is active on outside air temperature. (0) Off, (1) On
Read Only
0 = Off, 1 = On
BV.25 OverrideOccupancy
Status value to inform whether the user can override the occupancy mode or not. (0) Off, (1) On
Present Value
0 = Off, 1 = On
BV.26 LocalChangeoverMode
Status value of the actual changeover mode. (0) = Cool, (1) = Heat
Read Only
0 = Cool, 1 = Heat
BV.27 AL_ZoneCommLost
Status value to inform if the communication from the zone is lost. (0) Off, (1) On
Read Only
0 = Off, 1 = On
BV.28 Cfg_HeatingStages
Configuration value of heating stages. (0) 1 Stage, (1) 2 Stages
Present Value
0 = 1 Stage, 1 = 2 Stages
BV.29 Cfg_AnalogHeatUsed
Configuration value to indicate if analog heat can be used. (0) No, (1) Yes
Present Value
0 = No, 1 = Yes
BV.30 Cfg_CoolingStages
Configuration value of cooling stages. (0) 1 Stage, (1) 2 Stages
Present Value
0 = 1 Stage, 1 = 2 Stages
BV.31 Cfg_EconomizerInstalled
Configuration value to inform if the Economizer has been installed or not. (0) No, (1) Yes
Present Value
0 = No, 1 = Yes
BV.32 Cfg_RH_SensorUsed
Configuration value to inform about the sensor used. (0) Return Air RH, (1) USI RH Reading
Present Value
0 = Return Air RH, 1 = USI RH Reading
BV.36 Cfg_DigitalInput1Polarity
Configuration value to inform about the polarity of digital input 1. (0) Direct, (1) Reverse
Present Value
0 = Direct, 1 = Reverse
BV.37 Cfg_DigitalInput2Polarity
Configuration value to inform about the polarity of digital input 2. (0) Direct, (1) Reverse
Present Value
0 = Direct, 1 = Reverse
BV.40 BalancingModeActive
Configuration value to indicate whether the airflow balancing mode is active or not.
(0) No, (1) Yes
Present Value
0 = No, 1 = Yes