RTC 1010 Unit Controller  

BACnet Communication Module User Guide

 

 

www.deos-controls.com

 

Page | 3 

 

Configuration Options 

The following Configuration options enable you to configure and run the BACnet features of the controllers quickly. 

Quick Setup 

Configure the controller for BACnet communication without programming.  

 

1. 

Ensure that no other device on the network has a MAC address of 0 (the controller's default address).  

2. 

Connect the controller to the network and power it up.  

3. 

The controller automatically configures the baud rate and device instance allowing BACnet Property 
Configuration through the Write Property service. See Table 1 - BACnet Properties Configuration.  

4. 

Repeat the steps for each controller.  

Manual Setup 

Configure the controller for BACnet communication with programming.  

1. 

Access Operation Mode (jumper set to RUN position).  

2. 

Press and hold both function buttons for 5 seconds to access the Quick Access menu.  

3. 

Enter the password, 

637

4. 

Follow the instructions to configure the MAC Address, MAX Master, Device Instance, and Baud Rate, 
manually. 

5. 

Disconnect the power to the controller, connect the controller to the network, and connect the power 
again.  

MAC Address and Max_Master  

The MAC address must be unique on the entire MS/TP network. However, having a unique MAC address and a high 
baud rate does not guarantee efficient operation of the controller and other MS/TP units on the MS/TP network. Some 
MAC  address and Max_Master combinations are more efficient than  others. BACnet requires token-passing units to 
occasionally “poll” for other masters based on the MAC address and Max_Master. 
A  poor  combination  of  MAC  addresses  and  Max_Master  can  lead  to  a  slower  network  due  to  lost  time  polling  for 
masters that are not present. Unless there are 126 other units on the MS/TP network, the default Max_Master value of 
127  is  not  the  most  efficient  choice  for  the  controller.  The  Max_Master  default  value  of  127  was  selected  to  ensure 
that any master, specifically a BACnet client can be found when the controller is initially started. 

Examples of MAC Address and Max_Master Configurations 

The  following  are  some  of  the  examples  to  indicate  the  optimum  combination  of  Mac  address  and  Max_Master 
configurations to ensure a quick and efficient output.  

Example 1 

 

MAC=0. Max_Master=127 

 

MAC=1, Max_Master=127 

This configuration is slow and inefficient because every time either unit is required to find another master unit, it has to 
poll 126 units until it finds the right one to pass the token. 

Example 2 

 

MAC=0. Max_Master=5 

 

MAC=1 to MAC=4 are not used 

 

MAC=5, Max_Master=5 

This configuration is better than Example 1 but it is still not optimal. The Max_Master is set to the most efficient value 
but  the gap  between the  two  MAC addresses is high. Therefore, each unit must poll four units until  it finds the right 
one to pass the token. 

 

Содержание RTC 1010

Страница 1: ...RTC 1010 BACnet Guide 170605 docx RTC 1010 Unit Controller BACnet Communication Module User Guide Zoning System...

Страница 2: ...ration 2 Configuration Options 3 Quick Setup 3 Manual Setup 3 MAC Address and Max_Master 3 Copy Config 4 Network Reset 4 Device Object Properties 5 Object Types Supported 6 Out of Service Property 7 O...

Страница 3: ...lay of 15 minutes to ensure a Tusage_timeout value within 20 minutes MS TP Support The controller supports a Full Master Node state machine for MS TP The Max_Master and the instances are configured to...

Страница 4: ...through the WriteProperty service to Device Object Object_Identifier The device s Object_Identifier is a combination of the Device Object_Type 8 and the Device_Instance 0 4194302 therefore its decimal...

Страница 5: ...guarantee efficient operation of the controller and other MS TP units on the MS TP network Some MAC address and Max_Master combinations are more efficient than others BACnet requires token passing uni...

Страница 6: ...uration of a controller over the network to controllers of the same type using the Copy Config feature 1 Access Operation Mode jumper set to RUN position 2 Press and hold both function buttons for 5 s...

Страница 7: ...me and or device ID change Max_APDU_Length_Accepted Always 480 Segmentation_Supported 3 No Segmentation APDU_Timeout 6 000 W Number_of_APDU_Retries Always 3 Local_Time 00 00 00 W Local_Date 02 Jan 201...

Страница 8: ...tion on page 7 for more information Object will automatically return to Normal after a programmable period of time Refer to Proprietary property 1002 of Device Object in Table 2 Device Object Properti...

Страница 9: ...is not writable for MSV Program Description Reliability Program_Change Only LOAD and RESTART are supported for Program Change Use LOAD to apply the new firmware File Description Archive File Size Onl...

Страница 10: ...sure Static pressure reading of 0 to 10 Vdc from SPD sensor on analog input 4 Out_of_Service COV Increment 0 Vdc to 10 Vdc Resolution 0 1 Vdc AI 5 AI5_SupplyRH Supply humidity percentage reading on an...

Страница 11: ...for return air temperature The cooling setpoint is restricted by the heating setpoint Com lost RAT control setpoints Present Value COV Increment 50 F to 104 F or 10 C to 40 C AV 11 to 104 F 40 C Reso...

Страница 12: ...COV Increment 0 RH to 100 RH Resolution 0 1 RH AV 32 USI_RH_Reading UPT 24 H RT humidity percentage sensor reading Out_of_Service COV Increment 0 RH to 100 RH Resolution 0 1 RH AV 35 Cfg_TimeoutDeman...

Страница 13: ...73 CDem3 Third highest cooling demand Out_of_Service 0 to 100 Resolution 0 1 AV 74 CDem4 Fourth highest cooling demand Out_of_Service 0 to 100 Resolution 0 1 AV 75 CDem5 Fifth highest cooling demand...

Страница 14: ...H to 100 RH Resolution 0 5 RH AV 126 Cfg_HumidificationIT Configuration value of integration time for humidification Present Value 0 minutes to 7 200 minutes Resolution 1 minute AV 127 Cfg_PressureDB...

Страница 15: ...cates the device identification instance The instance is configured as per the Auto Instance Setting Present Value 0 to 4194302 Resolution 1 unit AV 468 CopyCfgStartAdd When using copy config this val...

Страница 16: ...scription W Notes BO 1 BO1_W2 Contact status of the binary output 1 for heating 0 Off 1 On Present Value 0 Off 1 On BO 2 BO2_W1 Contact status of the binary output 2 for heating 0 Off 1 On Present Val...

Страница 17: ...inform if the humidity lock is active on outside air temperature 0 Off 1 On Read Only 0 Off 1 On BV 25 OverrideOccupancy Status value to inform whether the user can override the occupancy mode or not...

Страница 18: ...3 5CPH 4 6CPH 5 7CPH 6 8CPH MSV 6 Cfg_CoolingCPH Configuration that indicates cooling CPH 1 3CPH 2 4CPH Present Value 1 3CPH 2 4CPH MSV 12 Cfg_OperationLogic Configuration value to determine the opera...

Страница 19: ...temperature sensor 2 0 100 0 to 10Vdc input converted to 0 to 100 3 On Off Binary Input Present Value 1 Temperature 2 Percentage 3 On Off MSV 100 Cfg_ObjectList Configuration value of the object list...

Страница 20: ...Notes www deos controls com...

Отзывы: