4. Connecting the load
4 - 1
Method for selecting output voltage
A
WARNING
ELECTRIC SHOCK can kill.
■ Do not touch the circuit inside the machine during
operation to prevent decease due to electric shock.
* When open the control panel or the like for changing
the output voltage, turn OFF the breaker and stop the
machine in advance.
In the
parallel operation, be sure to shut down the
other machine.
Load Connection
(l)Method For Selecting Output Voltage
Select voltagwe according to the voltage of the load to be used.
tri_U2
a
zd
Ы > 2
ffi w?
CCX>
400/440V
(380V) {415V} [480V]
200/220V
(190V) [240V]
* Method For Selecting Output Voltage
The output voltage of 200/220V or 400/440V can be selected with the voltage change over
plates.
These generators are shipped from the plant with their output voltage set at 200/220V
unless otherwise specified.
Change over to the desired output voltage according to the following procedure, if
necessary.
Ф The voltage change over panel is located on the right-hand side of the control box.
Remove the protecting cover of the voltage change over panel first.
Ф
Change over to the desired output voltage by setting the change over plates.
Note that insecure tightening of the locking bolts results in burning.
-