9.7.5 Line structure with stub line
The illustration shows the setup of the MATRIX.Net with line and stub line structure. A
sample connection of a control panel via a stub line in multiple groups is illustrated. The
maximum allowed stub line length amounts to 25 m.
Fig. 9-36: Set up of MATRIX.Net in
a line structure with stub line
*
As it is not allowed to connect three wires together, a
joining terminal must be provided. To do so, the intermediate
terminals (STV) mounted on the board (if not already occupied)
or terminals fitted on-site by others can be used.
1
2
3
X
NOTE!
The data transfer cable must be run as demonstrated in Fig. 9-36, in such a
way that only one side of the respective shielding is applied – see “Shielding /
Earthing” on page 55.
2-wires
2-wires
4-wires
Group 1
Group 2
Group X