Electrical Connections
PR-2007-0350-GB • Subject to modifications • R2-04/2016
40
9.6.2 Connecting mains voltage for units with 400 V operating voltage
9.6.3 Connecting control cables
MATRIX
2002
2003
3002
3003
4002
4003
4002+IO
4003+IO
9
9
9
9
Pos. 1: Input 400 V AC / 50 Hz,
Fusing by others max. B 16 A
Pos. 2: Connection to 1st unit; L1, L2, L3 on fan switch
Pos. 3: Connection to 2nd unit; L1, L2, L3 on fan switch
Pos. 4:
To further units
•
Connect the mains voltage in accordance with the
wiring diagram.
Fig. 9-11: Connecting mains voltage for controller/unit
PE
PE
1
2
3
4
PE
L3
L2
L1
N
L1
L2
L3
N
N
PE
PE
L3
L2
L1
N
N
NOTE:
Use the following control cables for connection:
– Short cable lengths and/or location not prone to interference:
multi-core control cable, 0.5 mm
2
, shielded with aluminium-clad plastic
sleeve e.g. J-Y(ST)Y 1x2x0.8 / 3x2x0.8 / 4x2x0.8
– Longer cable lengths and/or location prone to interference:
multi-core control cable, 0.5 mm
2
with copper-weave shielding.