Installation
Multi
MAXX
HD
22
PR-2007-0350-GB • Subject to modifications • R2-04/2016
Minimum distance from wall A (see Fig. 7-3)
It is necessary to keep the minimum distance to allow sufficient air circulation and
provide sufficient access for maintenance.
Fig. 7-3:
Distance between units with wall mounting
Air throws
Air throws are specified in the following table:
The data in the chart are approximate and apply to the discharge temperuture if the
latter exceeds room temperature by 15 - 20 K.
Size
1
2
3
4
Distance to wall A,
not less (mm)
300
300
400
400
Unit model
Air throw (m)
Unit model
Air throw (m)
Outlet
Outlet
Outlet
Outlet
Bas. wall
SAL wall
Bas. wall
SAL wall
HD11
9,6 12,3
HD31
11,4 15,4
HD12
7,5 9,7
HD32
9,2 12,4
HD13
6,2 8,1
HD33
8 10,7
HD14
5,7 7,2
HD34
9,1 9,5
HD21
11,3 14,7
HD41
16 21
HD22
8,9 11,7
HD42
12,6 16,5
HD23
7,7 10
HD43
10,9 14,2
HD24
6,6 8,7
HD44
9,5 12,4
A
A
10 - 15 m
5 - 7 m
8 - 11 m
8 - 11 m