Chapter 5 Parameters
|
VFD-M-D Series
Revision Jan. 2007, MDE2, SW V1.05
5-33
2 - 02
Motor No-load Current
Unit: 0.1
Settings
0%*FLA to motor rated current
Factory Setting: 40%*FLA
The rated current of the AC drive is regarded as 100%. The setting of the Motor no-load
current will affect the slip compensation.
The setting value must be less than Pr.2-00 (Motor Rated Current).
2 - 03
Torque Compensation
Unit: 0.1
Settings
0.0 to 10.0
Factory Setting: 1.0
This parameter may be set so that the AC drive will increase its voltage output to obtain a
higher torque. Only to be used for V/f control mode.
Too high torque compensation can overheat the motor.
2 - 04
Number of Motor Poles
Unit: 2
Settings
02 to 10
Factory Setting: 04
This parameter sets the number of motor poles (must be an even number).
2 - 05
Motor Line-to-line Resistance R1
Unit: 0.01
Settings
0.00 to 99.99
Ω
Factory Setting: 0.00
The motor auto tune procedure will set this parameter. The user may also set this parameter
without using Pr.2-05.
2 - 06
Motor Rated Slip
Unit: 0.01
Settings
0.00 to 20.00Hz
Factory Setting: 3.00
Refer to the rated rpm and the number of poles on the nameplate of the motor and use the following
equation to calculate the rated slip.
Rated Slip (Hz) = F
base
(Pr.1-01 base frequency) - (rated rpm x motor pole/120)
2 - 07
Slip Compensation Limit
Unit: 1
Settings
00 to 250%
Factory Setting: 200
This parameter sets the upper limit of the compensation frequency (the percentage of Pr.2-06).
Example: when Pr.2-06=5Hz and Pr.2-07=150%, the upper limit of the compensation
frequency is 7.5Hz. Therefore, for a 50Hz motor, the max. output is 57.5Hz.
Содержание VFD-M-D series
Страница 1: ...M D...
Страница 2: ......
Страница 3: ...M D...
Страница 9: ...C 2 General Precaution C 4 C 3 How to Choose a Suitable Motor C 5...
Страница 31: ...Chapter 3 Start Up VFD M D Series 3 4 Revision Jan 2007 MDE2 SW V1 05 This page intentionally left blank...
Страница 121: ...Chapter 5 Parameters VFD M D Series 5 88 Revision Jan 2007 MDE2 SW V1 05 This page intentionally left blank...
Страница 155: ...Appendix B Accessories VFD M D Series B 12 Revision 10 2005 BE13 This page intentionally left blank...