Chapter 5 Parameters
|
VFD-M-D Series
5-18
Revision Jan. 2007, MDE2, SW V1.05
Setting 12: It is used to display the status of the external multi-function output terminals,
including relay1, relay2, MO1 and MO2. The value it displays is hexadecimal number. It needs
to be converted to binary to get the result as following diagram.
3
2 1 0
2 2 2 2
3 2 1 0
*0
OFF *1
ON
=
=
Relay 1
Relay 2
MO1
MO2
Weights
Bit
For example: when it displays o. C. After converting C(HEX) to binary (1100), it indicates that
the terminals MO1 and MO2 are ON.
2 2 2 2
3
2
1
0
1 1 0 0
Relay 1 =OFF
Relay 2 =OFF
MO1 =ON
MO2 =ON
*0
OFF *1
ON
=
=
The display value
=
=
=
=
bit0x2
1x2+1x2+0x2+0x2
8+4+0+0
12 C
(H)
=
2
1
0
2
1
0
3
NOTE:
2
1 2
8 2
64
2
2 2
16 2
128
2
4 2
32
=
=
=
=
=
=
=
=
0
1
2
3
4
5
6
7
Weights
Bit
0 - 05
User Defined Coefficient K
Unit: 0. 1
Settings
0.1 to 160.0
Factory Setting: 1.0
The coefficient K determines the multiplying factor for the user-defined unit.
The display value is calculated as follows:
U (User-defined unit) = Frequency Command * K (Pr.0-05)
H (actual output) = Actual output frequency * K (Pr.0-05)
Example:
A conveyor belt runs at 13.6m/s at motor speed 60Hz.
K = 13.6/60 = 0.21 (0.226667 rounded to 1 decimal), therefore Pr. 0-05=0.2
With Frequency command 35Hz, display shows U and 35*0.2=7.0m/s.
(To increase accuracy, use K=2.2 or K=22.7 and disregard decimal point.)
0 - 06
Software Version
Settings
Read
Only
Display
#.#
Содержание VFD-M-D series
Страница 1: ...M D...
Страница 2: ......
Страница 3: ...M D...
Страница 9: ...C 2 General Precaution C 4 C 3 How to Choose a Suitable Motor C 5...
Страница 31: ...Chapter 3 Start Up VFD M D Series 3 4 Revision Jan 2007 MDE2 SW V1 05 This page intentionally left blank...
Страница 121: ...Chapter 5 Parameters VFD M D Series 5 88 Revision Jan 2007 MDE2 SW V1 05 This page intentionally left blank...
Страница 155: ...Appendix B Accessories VFD M D Series B 12 Revision 10 2005 BE13 This page intentionally left blank...