Chapter 5 Parameters
|
VFD-M-D Series
5-70
Revision Jan. 2007, MDE2, SW V1.05
O utput
F requenc y
O utput
Voltage
7-11
7-13=00
7-11
7-14=01
Delay Tim e
Speed S earc h
Speed
Sy nch roniz atio n
D ete ction
Delay Tim e
F ault oc cur F ault clear
F ault oc cur F ault cl ear
O pera ti on c ontinues after fault clear,
s peed s earc h s tar ts with th e M as ter
F requenc y referenc e v alue
O pera tion c ontinues after fault clear,
s peed s ear ch s tarts w ith the minim um freque ncy
7 - 14
Auto Reset Time at Restart after Fault
Unit: 1
Settings
00 to 9999 sec
Factory Setting: 600
7 - 15
Present Fault Record
7 - 16
Second Most Recent Fault Record
7 - 17
Third Most Recent Fault Record
7 - 18
Fourth Recent Fault Record
Factory Setting: 00
Readings
00
No
fault
01
Over-current
(oc)
02
Over-voltage
(ov)
03
Overheat
(oH)
04
Overload
(oL)
05
Overload1
(oL1)
06 External fault (EF)
07
Reserved
08 CPU failure (cF3)
09 Hardware protection failure (HPF)
10 Current exceeds 2 times rated current during accel.(ocA)
11
Current exceeds 2 times rated current during decel.(ocd)
12 Current exceeds 2 times rated current during steady state operation (ocn)
13
Ground
fault
(GFF)
14
Reserved
15 CPU READ failure (CF1)
16 CPU WRITE failure (CF2)
17
Reserved
Содержание VFD-M-D series
Страница 1: ...M D...
Страница 2: ......
Страница 3: ...M D...
Страница 9: ...C 2 General Precaution C 4 C 3 How to Choose a Suitable Motor C 5...
Страница 31: ...Chapter 3 Start Up VFD M D Series 3 4 Revision Jan 2007 MDE2 SW V1 05 This page intentionally left blank...
Страница 121: ...Chapter 5 Parameters VFD M D Series 5 88 Revision Jan 2007 MDE2 SW V1 05 This page intentionally left blank...
Страница 155: ...Appendix B Accessories VFD M D Series B 12 Revision 10 2005 BE13 This page intentionally left blank...