90
Operating the PV inverter
P/Pn
cosφ
1
0.9
0.9
inductive
capacitive
1
=
Figure 7.31.:
cos
φ(P) graph
There are two possible curves defined in the cos
φ(P) graph, curve A in blue (the default) and
curve B in red.
Pn = nominal power
Curve a (in blue on Figure 7.31)
A is identified from Plock-out = value from local grid operator and cosφ = 1
B is identified from Plock-in = value from local grid operator and cosφ = 1
C is identified from P = Pn and cos = cosφmax
Curve B (in red on Figure 7.31)
A is identified from Plock-out = P = value from local grid operator and cosφ = 1
B is identified from Plock-in = value from local grid operator and cosφ = 1
C is identified from P = Pn and cos = cosφmax
Important:
When Plock-out = Plock-in then Curve B will be followed.
When Plock-out is ≠ Plock-in then Curve A will be followed.