82
Operating the PV inverter
Figure 7.23.: cos φ(P) settings page
adjustable parameters
Parameter
adjustable values
Description
Upper limit - cos φ
Ind 0.80 ... Cap 0.80
The upper limit cos φ must be greater than the
lower limit cos φ
Lower Power
0 ... 100 %
Lower limit - cos φ
Ind 0.80 ... Cap 0.80
Upper Power
0 ... 100 %
The upper power must be greater than the lower
power
Lock-in Voltage
Not used for DE LVD/MVD
Lock-out Voltage
Not used for DE LVD/MVD
Mode
ON I OFF
This switches the feature on and off
7.3.6.3.5 Constant reactive Power
This feature is available for MVD grids only.
This feature allows a constant cos reactive power to be set.