Technical data
12. Technical data
12.1 specification
nOTE
The specification is subject to change. Please check the web site at
www.solar-inverter.com for the latest version.
10EUT4TL
15EUG4TL
20EUG4TL
30EUT4TL
InPUT (DC)
Max. recommended
PV power
1)
13.2 kW
P
19 kW
P
25 kW
P
38 kW
P
Recommended PV
power range
8.8 ... 13.2 kW
P
14 ... 19 kW
P
18 ... 25 kW
P
26 ... 38 kW
P
Nominal power
10.5 kW
15.3 kW
20.4 kW
31 kW
Operating voltage
250 ... 1000 V
MPP voltage range @
nominal power,
balanced inputs
350 ... 850 V
DC
350 ... 800
V
DC
350 ... 800 V
DC
480 ... 800 V
DC
MPP voltage range
unbalanced inputs
350 ... 850 V
DC
470 ... 800 V
DC
480 ... 800 V
DC
620 ... 800 V
DC
Nominal voltage
635 V
DC
650 V
DC
Start up power
40 W
Absolute maximum
voltage
1000 V
1000 V
1000 V
Number of inputs
4 inputs (2 MPP trackers)
6 inputs (2 MPP
trackers)
Max. current
30 A (20 A x 2)
48 A (24 A x 2)
60 A (30 A x 2)
68 A (34 A x 2)
OUTPUT (aC)
Max. apparent power
2)
10.5 kVA
15.75 kVA
21.0 kVA
31.5 kVA
Nominal apparent
power
10.0 kVA
15.0 kVA
20.0 kVA
30.0 kVA
Voltage range
(3 phase)
3)
3 x 230 / 400 V (± 20 %) + N + PE (3 phases, 5 wires)
Nominal current
14.5 A
22 A
29 A
43 A
Max. current
16 A
25 A
32 A
46 A
Nominal frequency
50/60 Hz
Frequency range
3)
50 / 60 Hz ± 5 Hz
Power factor adjust-
able
0.80 Cap ... 0.80 Ind
Содержание SOLIVIA 10 EU T4 TL
Страница 2: ......
Страница 99: ...99 EN Maintenance 2 3 4 1 Figure 8 1 Steps of removing the fan bracket from the inverter ...
Страница 101: ...101 EN Maintenance Figure 8 3 Removing the Vent Covers for Cleaning ...
Страница 117: ...117 EN Technical data 12 3 Earthing Systems for 10 TL 15 TL 20 TL 30 TL Figure 12 1 Earthing Systems ...
Страница 119: ...119 13 Certificates ...
Страница 121: ......