![Delta SOLIVIA 10 EU T4 TL Скачать руководство пользователя страница 85](http://html1.mh-extra.com/html/delta/solivia-10-eu-t4-tl/solivia-10-eu-t4-tl_operation-and-installation-manual_2472310085.webp)
85
EN
Operating the PV inverter
➀
➁
➂
➃
➀
No instability or disconnection from the network
➁
Feed-in reactive current depends on K factor
➂
Same as area 2, Feed-in reactive current depends on K factor
➃
Disconnects from the network
Figure 7.26.: Fault Ride Through settings page
adjustable parameters
Parameter
adjustable values Description
Dead band - Vhigh
+0 ... +20 %
Dead band - Vlow
-20 ... 0 %
K factor
0 ... 10
Vdrop
0 ... 90%
t1
0 ... 500 ms
U1
20 ... 90%
t2
0.01 ... 5 s
t3
0.01 ... 5 s
Mode
ON | OFF
This switches the feature on and off
Содержание SOLIVIA 10 EU T4 TL
Страница 2: ......
Страница 99: ...99 EN Maintenance 2 3 4 1 Figure 8 1 Steps of removing the fan bracket from the inverter ...
Страница 101: ...101 EN Maintenance Figure 8 3 Removing the Vent Covers for Cleaning ...
Страница 117: ...117 EN Technical data 12 3 Earthing Systems for 10 TL 15 TL 20 TL 30 TL Figure 12 1 Earthing Systems ...
Страница 119: ...119 13 Certificates ...
Страница 121: ......