RMC200 Startup Guide
24
Delta Computer Systems, Inc.
Step 11: Set the Output Polarity
The Actual Position, Pressure, Force or Velocity
must increase
when
the RMC applies a
positive
Control Output percentage. If this condition
is not met, you will not be able to perform closed-loop control.
1.
Send the Direct Output command with a positive
Output
value
that is large enough to move the axis.
2.
On the
Basic
tab of the
Axis Status Registers
pane, observe the
Actual Position
and note whether it is increasing or decreasing:
Increasing
The Output Polarity is correct. Go to
Enable the Axes
below.
Decreasing
You must invert the Output Polarity:
A.
In the
Axis Parameters
pane, on the
Setup
tab, double-click
the
Invert Output Polarity
parameter to set it.
B.
Click the
Download
button to apply the change to the
RMC.
Enable the Axes
In order to send motion commands other than Direct Output, the axes
must be enabled after the RMC starts up.
1.
In the Command Tool, in the
Cmd
box,
type
Enable
, and choose
Enable Controller (7)
from the list.
2.
Click
Send
. All axes will be enabled.
Entering RUN Mode will also enable the
axes.
Содержание RMC200
Страница 1: ...RMC200 MOTION CONTROLLER STARTUP GUIDE With wiring diagrams Connect Control Optimize ...
Страница 56: ...RMC200 Startup Guide 52 Delta Computer Systems Inc B7 B11 B15 ...
Страница 58: ...RMC200 Startup Guide 54 Delta Computer Systems Inc Notes ...
Страница 59: ...Appendix C Agency Compliance deltamotion com 55 Notes ...
Страница 60: ...RMC200 Startup Guide 56 Delta Computer Systems Inc The RMC Family of Motion Control Connect Control Optimize ...