C h a p t e r 3 I n t r o d u c t i o n t o F u n c t i o n s
3 - 4 9
3_
Description
Default
Slave Starting Address (decimal)
Set up the slave starting address for read/write the registers in a PLC.
Delta PLC:
Enter the internal D register number. If you need to read / write
D0, please enter 0 here.
Other:
Enter the Hexadecimal or Decimal actual address. For example:
Holding Register: 400100, take 0100 (decimal) that is 64 (hex).
N/A
Bit
For the X/Y type of Delta AH/AS series, the address input format is 0.0~X.15.
Enter the values before decimal point in the input field of Slave Starting Address,
while values after decimal point should be entered in the input field of Bit.
Device Starting Address (decimal)
Set up the device starting address (decimal, input range is from $2048 to $4095 for
word type data, input range is from M0 to M511 for bit type data). $ or M specifies
that the match must start at the beginning of a Device Starting Address.
N/A
Length (1-123)
Set the number of the continuous address followed by the starting address which
will be read or write. Input range is from 1 to 123.
N/A
Operation
Click the +/- button to add mapping or delete mapping.
N/A
Edit
Click an item of register mapping forms that can be edited.
N/A
3.4.6
Siemens TCP
Support Siemens TCP Client mode to perform data exchange with Siemens S7-300/S7-1200/S7-1500 through Ethernet.
Click Add Server to enter the setting page.
Содержание DX-2100 Series
Страница 3: ......
Страница 7: ...4 6 2 4 Registers View 6 6 6 2 5 Alarm List 6 7 ...
Страница 15: ...DX 2100 Series Industrial 3G Cloud Router 1 8 _1 Memo ...
Страница 36: ...Chapter 2 Introduction to User Interface 2 21 2_ ...
Страница 108: ...DX 2100 Series Industrial 3G Cloud Router 3 72 _3 MEMO ...
Страница 146: ...DX 2100 Series Industrial 3G Cloud Router 5 24 _5 MEMO ...
Страница 154: ...DX 2100 Series Industrial 3G Cloud Router 6 8 _6 MEMO ...