LYTE II DIN Rail Power Supply 

DRL-240W series / DRL-

V240W1EN

 

TECHNICAL DATASHEET

 

 

 

 

 

  

All parameters are specified at 25°C ambient and AC input unless otherwise indicated.

 

  www.DeltaPSU.com (March 2022, Rev. 04) 

 

10

 

Functions 

  Graph illustrating the Start-up Time, Rise Time, and Hold-up Time 

 

Start-up Time 

The time required for the output voltage to reach 90% of its final steady state set value, after the input voltage is applied.

 

 

 

Rise Time 

The time required for the output voltage to change from 10% to 90% of its final steady state set value. 

 

 

Hold-up Time 

Time between the collapse of the AC input voltage, and the output falling to 95% of its steady state set value. 

 

 

 

Inrush Current 

Inrush current is the peak, instantaneous, input current measured 

and, occurs when the input voltage is first applied. For AC input 

voltages, the maximum peak value of inrush current will occur 

during the first half cycle of the applied AC voltage. This peak value 

decreases exponentially during subsequent cycles of AC voltage. 

 

 

Dynamic Response 

The power supply output voltage will remains within ±10% of its 

steady state value, when subjected to a dynamic load from 10% to 

100% of its rated current. 

 

 

 

 

Содержание DRL-12V240W1EN

Страница 1: ...without compromising on quality and reliability The convection cooled LYTE II series will operate full power from 30 C to 50 C then de rating up to 70 C at 230 Vac It can operate in constant current m...

Страница 2: ...Output Voltage 12 Vdc 24 Vdc 48 Vdc Factory Set Point Tolerance 12 Vdc 1 24 Vdc 1 48 Vdc 1 Output Voltage Adjustment Range 10 8 13 2 Vdc 21 6 26 4 Vdc 43 2 52 8 Vdc Output Current 20 0 A 10 0 A 5 0 A...

Страница 3: ...r by 1 67 C 115 Vac 50 C de rate power by 2 5 C 230 Vac Input Voltage 100 Vac de rate power by 1 Vac Operating Humidity 20 to 90 RH Non Condensing Operating Altitude 0 to 5 000 Meters 16 400 ft Shock...

Страница 4: ...p Life Time 10 years 230 Vac 50 load 40 C Safety Standards Directives Electrical Safety CB scheme TUV Bauart UL cUL BSMI EAC KC IEC 62368 1 IEC 60950 1 IEC 61010 1 2 201 EN 62368 1 EN 61010 1 2 201 UL...

Страница 5: ...rical Fast Transient Burst IEC61000 4 4 Level 3 Criteria A1 2 kV Surge IEC61000 4 5 Level 4 Criteria A1 Common Mode4 4 kV Differential Mode5 2 kV Conducted IEC61000 4 6 Level 3 Criteria A1 150 kHz 80...

Страница 6: ...Converter Inrush current limit Filter DC DC Converter Output Rectifier Filter Over Temperature Protection PWM Control Over Power Protection Photo Coupler Feedback Control CV CC Photo Coupler Over Volt...

Страница 7: ...4 87 x 1 57 x 4 60 inch Unless otherwise specified tolerance of dimension are 0 5 mm AWG Wire Table Current Rating for PVC Wire 6 AWG 52 5 A 8 AWG 37 5 A 10 AWG 29 0 A 12 AWG 22 5 A 14 AWG 16 5 A 16...

Страница 8: ...when the surrounding air temperature 50 C the device will run into Over Temperature Protection When activated power supply will latch off until the surrounding air temperature is lowered or the load...

Страница 9: ...m the rail Safety Instructions Vertical Mounting ALWAYS switch mains of input power OFF before connecting and disconnecting the input voltage to the unit If mains are not turned OFF there is risk of e...

Страница 10: ...from 10 to 90 of its final steady state set value Hold up Time Time between the collapse of the AC input voltage and the output falling to 95 of its steady state set value Inrush Current Inrush curren...

Страница 11: ...ort circuits When a short circuit is applied the output current will operate in Hiccup mode The power supply will return to normal operation after the short circuit is removed Overvoltage Protection L...

Страница 12: ...r any claim or action arising from any error for the provided information in the datasheets Customer shall take its responsibility for evaluation of using the product before placing an order with Delt...