LYTE II DIN Rail Power Supply 

DRL-240W series / DRL-

V240W1EN

 

TECHNICAL DATASHEET

 

 

 

 

 

  

All parameters are specified at 25°C ambient and AC input unless otherwise indicated.

 

  www.DeltaPSU.com (March 2022, Rev. 04) 

 

11

 

Overload & Overcurrent Protections (Continuous Current) 

The power supply offers constant current limit  protection for 

inductive and capacitive load applications when output current 

range is 105~150% of I

O

 (Max load) and output voltage is more 

than 80%. Upon such an occurrence, the V

O

 (output voltage) will 

start to droop. Once the power supply has reached its maximum 

power limit, the protection will be activated; and, the power supply 

will operate in continuous current. The power supply will recover 

once the cause of OLP or OCP is removed, and I

O

 (output current) 

is back within the specified range. 

 

 

 

 

Short Circuit Protection (Auto-Recovery) 

The power supply’s output Short Circuit Protection function also 

provides protection against short circuits. When a short circuit is 

applied, the output current will operate in “Hiccup mode”. The 

power supply will return to normal operation after the short circuit 

is removed. 

 

 

Overvoltage Protection (Latch Mode) 

The power supply’s overvoltage circuit will be activated when its 

internal feedback circuit fails. The output voltage shall not exceed 

its specifications as described in “Protections” section. Power 

supply will latch off, and require removal/re-application of input AC 

voltage in order to restart. 

 

The power supply should be latch.

 

 

 

 

 

Over Temperature Protection

 

(Latch Mode)

 

As described in load de-rating section, the power supply also has 

Over Temperature Protection (OTP). In the event of a higher 

operating temperature at 100% load; or, when the operating 

temperature is beyond what is recommended in the de-rating 

graph, the OTP circuit will be activated. When activated, power 

supply will latch off, until the surrounding air temperature drops to 

its normal operating temperature or the load is reduced as 

recommended in the de-rating graph. Removal/re-application of 

input AC voltage will then be required in order to restart. 

 

 

 

 

 

 

 

 

 

Содержание DRL-12V240W1EN

Страница 1: ...without compromising on quality and reliability The convection cooled LYTE II series will operate full power from 30 C to 50 C then de rating up to 70 C at 230 Vac It can operate in constant current m...

Страница 2: ...Output Voltage 12 Vdc 24 Vdc 48 Vdc Factory Set Point Tolerance 12 Vdc 1 24 Vdc 1 48 Vdc 1 Output Voltage Adjustment Range 10 8 13 2 Vdc 21 6 26 4 Vdc 43 2 52 8 Vdc Output Current 20 0 A 10 0 A 5 0 A...

Страница 3: ...r by 1 67 C 115 Vac 50 C de rate power by 2 5 C 230 Vac Input Voltage 100 Vac de rate power by 1 Vac Operating Humidity 20 to 90 RH Non Condensing Operating Altitude 0 to 5 000 Meters 16 400 ft Shock...

Страница 4: ...p Life Time 10 years 230 Vac 50 load 40 C Safety Standards Directives Electrical Safety CB scheme TUV Bauart UL cUL BSMI EAC KC IEC 62368 1 IEC 60950 1 IEC 61010 1 2 201 EN 62368 1 EN 61010 1 2 201 UL...

Страница 5: ...rical Fast Transient Burst IEC61000 4 4 Level 3 Criteria A1 2 kV Surge IEC61000 4 5 Level 4 Criteria A1 Common Mode4 4 kV Differential Mode5 2 kV Conducted IEC61000 4 6 Level 3 Criteria A1 150 kHz 80...

Страница 6: ...Converter Inrush current limit Filter DC DC Converter Output Rectifier Filter Over Temperature Protection PWM Control Over Power Protection Photo Coupler Feedback Control CV CC Photo Coupler Over Volt...

Страница 7: ...4 87 x 1 57 x 4 60 inch Unless otherwise specified tolerance of dimension are 0 5 mm AWG Wire Table Current Rating for PVC Wire 6 AWG 52 5 A 8 AWG 37 5 A 10 AWG 29 0 A 12 AWG 22 5 A 14 AWG 16 5 A 16...

Страница 8: ...when the surrounding air temperature 50 C the device will run into Over Temperature Protection When activated power supply will latch off until the surrounding air temperature is lowered or the load...

Страница 9: ...m the rail Safety Instructions Vertical Mounting ALWAYS switch mains of input power OFF before connecting and disconnecting the input voltage to the unit If mains are not turned OFF there is risk of e...

Страница 10: ...from 10 to 90 of its final steady state set value Hold up Time Time between the collapse of the AC input voltage and the output falling to 95 of its steady state set value Inrush Current Inrush curren...

Страница 11: ...ort circuits When a short circuit is applied the output current will operate in Hiccup mode The power supply will return to normal operation after the short circuit is removed Overvoltage Protection L...

Страница 12: ...r any claim or action arising from any error for the provided information in the datasheets Customer shall take its responsibility for evaluation of using the product before placing an order with Delt...

Отзывы: