background image

LYTE II DIN Rail Power Supply 

DRL-240W series / DRL-

V240W1EN

 

TECHNICAL DATASHEET

 

 

 

 

 

  

All parameters are specified at 25°C ambient and AC input unless otherwise indicated.

 

  www.DeltaPSU.com (March 2022, Rev. 04) 

 

3

 

Model Number 

DRL-12V240W1EN 

DRL-24V240W1EN

 

DRL-48V240W1EN 

 

Mechanical 

 

Case Cover / Chassis 

 

SGCC / Aluminum 

Dimensions (H x W x D)   

123.6 x 40 x 116.8 mm (4.87 x 1.57 x 4.60 inch) 

Unit Weight 

 

0.62 kg (1.37 lb) 

Indicator 

 

Green LED (DC OK) 

Cooling System 

 

Convection 

Terminal*

4

 

Input  3 Pins (Rated 300 V / 30 A) 

 

Output  4 Pins (Rated 300 V / 20 A) 

Wire 

Input  AWG 18-12 (Current rating can refer to “AWG Wire Table”) 

 

Output  AWG 18-12 (Current rating can refer to “AWG Wire Table”) 

Mounting Rail 

 

Standard TS35 DIN Rail in accordance with EN 60715 

Noise (1 Meter from power supply) 

Sound Pressure Level (SPL) < 25 dBA 

*4 The torque at the terminal connector shall not exceed 4 Kgf.cm. (3.47 lbf.in). 

 

Environment 

 

Surrounding Air 
Temperature  

Operating  -30°C to +70°C (-40°C Cold Start) 

Storage  -40°C to +85°C 

Power De-rating 

Temperature 

> 40°C de-rate power by 1.67 % / °C @ 115 Vac 

> 50°C de-rate power by 2.5 % / °C @ 230 Vac 

Input 

Voltage  < 100 Vac de-rate power by 1% / Vac 

Operating Humidity 

  20 to 90% RH (Non-Condensing) 

Operating Altitude 

  0 to 5,000 Meters (16,400 ft.) 

Shock Test 

Non-

Operating 

IEC 60068-2-27, Half Sine Wave: 50 G for duration of 11 ms; 3 times per direction,  
9 times in total 

 

Operating  IEC 60068-2-27, Half Sine Wave: 10 G for duration of 11 ms; 1 time in X axis 

Vibration 

Non-

Operating  IEC 60068-2-6, Random: 5 Hz to 500 Hz (2.09 G); 20 min per axis for all X, Y, Z direction 

 

Operating  IEC 60068-2-6, Sine Wave: 10 Hz to 500 Hz @ 19.6 m/s

²

 (2 G peak);  

10 min per cycle, 60 min for X direction 

Over Voltage Category 

  II (Compliance to EN 62477-1 OVC III with 2000 meters altitude) 

Pollution Degree 

  2 

 

Protections 

 

Overvoltage 

<

 

17.4

 

V, SELV Output,  

Latch Mode 

<

 

33.6

 

V, SELV Output,  

Latch Mode 

<

 

64.8

 

V, SELV Output,  

Latch Mode 

Overload / Overcurrent 

105 - 150% of rated load current, Auto-recovery 
Continuous current limit Mode*

5

 (Vo

 

>

 

80%) 

Over Temperature 

Latch Mode 

Short Circuit 

Hiccup Mode, Non-Latching 

(Auto-Recovery when the fault is removed) 

Protection Against Shock 

Class I with PE

*6

 connection 

*5 Constant current limit protection for inductive and capacitive load applications 

*6 PE: Primary Earth

  

Содержание DRL-12V240W1EN

Страница 1: ...without compromising on quality and reliability The convection cooled LYTE II series will operate full power from 30 C to 50 C then de rating up to 70 C at 230 Vac It can operate in constant current m...

Страница 2: ...Output Voltage 12 Vdc 24 Vdc 48 Vdc Factory Set Point Tolerance 12 Vdc 1 24 Vdc 1 48 Vdc 1 Output Voltage Adjustment Range 10 8 13 2 Vdc 21 6 26 4 Vdc 43 2 52 8 Vdc Output Current 20 0 A 10 0 A 5 0 A...

Страница 3: ...r by 1 67 C 115 Vac 50 C de rate power by 2 5 C 230 Vac Input Voltage 100 Vac de rate power by 1 Vac Operating Humidity 20 to 90 RH Non Condensing Operating Altitude 0 to 5 000 Meters 16 400 ft Shock...

Страница 4: ...p Life Time 10 years 230 Vac 50 load 40 C Safety Standards Directives Electrical Safety CB scheme TUV Bauart UL cUL BSMI EAC KC IEC 62368 1 IEC 60950 1 IEC 61010 1 2 201 EN 62368 1 EN 61010 1 2 201 UL...

Страница 5: ...rical Fast Transient Burst IEC61000 4 4 Level 3 Criteria A1 2 kV Surge IEC61000 4 5 Level 4 Criteria A1 Common Mode4 4 kV Differential Mode5 2 kV Conducted IEC61000 4 6 Level 3 Criteria A1 150 kHz 80...

Страница 6: ...Converter Inrush current limit Filter DC DC Converter Output Rectifier Filter Over Temperature Protection PWM Control Over Power Protection Photo Coupler Feedback Control CV CC Photo Coupler Over Volt...

Страница 7: ...4 87 x 1 57 x 4 60 inch Unless otherwise specified tolerance of dimension are 0 5 mm AWG Wire Table Current Rating for PVC Wire 6 AWG 52 5 A 8 AWG 37 5 A 10 AWG 29 0 A 12 AWG 22 5 A 14 AWG 16 5 A 16...

Страница 8: ...when the surrounding air temperature 50 C the device will run into Over Temperature Protection When activated power supply will latch off until the surrounding air temperature is lowered or the load...

Страница 9: ...m the rail Safety Instructions Vertical Mounting ALWAYS switch mains of input power OFF before connecting and disconnecting the input voltage to the unit If mains are not turned OFF there is risk of e...

Страница 10: ...from 10 to 90 of its final steady state set value Hold up Time Time between the collapse of the AC input voltage and the output falling to 95 of its steady state set value Inrush Current Inrush curren...

Страница 11: ...ort circuits When a short circuit is applied the output current will operate in Hiccup mode The power supply will return to normal operation after the short circuit is removed Overvoltage Protection L...

Страница 12: ...r any claim or action arising from any error for the provided information in the datasheets Customer shall take its responsibility for evaluation of using the product before placing an order with Delt...