D P M - C 5 0 1 L / C 5 0 2 O p e r a t i o n M a n u a l
5 - 6
_5
value; alarm triggered)
3E
40063 Reserved
3F
40064 Dropout setpoint (line
voltage value exceeding
this value; alarm cleared)
0.000 - 99999.999
float
V
4
R/W
40
40065
41
40066 Reserved
Alarm - Over Voltage L-N
42
40067 Alarm Enable
0: Disable
1: Enable
word
2
R/W
43
40068 Pickup setpoint (phase
voltage value exceeding
this value; alarm triggered)
0.000 - 99999.999
float
V
4
R/W
44
40069
45
40070 Reserved
46
40071 Dropout setpoint (phase
voltage value below this
value; alarm cleared)
0.000 - 99999.999
float
V
4
R/W
47
40072
48
40073 Reserved
Alarm - Under Voltage L-N
49
40074 Alarm Enable
0: Disable
1: Enable
word
2
R/W
4A
40075 Pickup setpoint (phase
voltage value below this
value; alarm triggered)
0.000 - 99999.999
float
V
4
R/W
4B
40076
4C
40077 Reserved
4D
40078 Dropout setpoint (phase
voltage value exceeding
this value; alarm cleared)
0.000 - 99999.999
float
V
4
R/W
4E
40079
Содержание DPM-C501L
Страница 14: ...DPM C501L C502 Operation Manual 2 6 _2 2 4 Dimension Front Unit mm Back...
Страница 18: ...DPM C501L C502 Operation Manual 2 10 _2 MEMO...
Страница 26: ...DPM C501L C502 Operation Manual 3 8 _3 _3 MEMO...
Страница 71: ...DPM C501L C502 Operation Manual 5 34 _5 MEMO...
Страница 72: ...6 1 Chapter 6 Error Codes Table of Contents 6 1 Table of Error Codes 6 2 6...
Страница 74: ...A 1 Appendix A Accessories Table of Contents A 1 DCT1000 Series A 2 A 2 DCT2000 Series A 4 12 A...
Страница 79: ...DPM C501L C502 Operation Manual A 6 _A _1 MEMO...